Presentazione di PowerPoint - PowerPoint PPT Presentation

1 / 18
About This Presentation
Title:

Presentazione di PowerPoint

Description:

Diagnosis of battery status. 1 flash = Reverse polarity, wrong battery voltage ... Ready for charging most battery types. Jumper positions: ... – PowerPoint PPT presentation

Number of Views:93
Avg rating:3.0/5.0
Slides: 19
Provided by: adels
Category:

less

Transcript and Presenter's Notes

Title: Presentazione di PowerPoint


1
CBI
ALL IN ONE
A revolution in Battery Charging
2
Technology
  • The CBI series is a new range of battery chargers
    based on switching technology that offers three
    main features in the same unit
  • Stabilized Power Supply
  • Back UP Module
  • Battery charger
  • Switching technology, micro-processor control and
    solid state switching optimize level of charge
    and life time of the batteries. Features such as
    the software management of boost and trickle
    charge and the continuous monitoring of battery
    life status (life test check) allow a risk-free
    operation even in permanent connection conditions.

ADEL system
CBI Series
3
Available models
  • Input110230Vac
  • Output 24 Vdc
  • CBI242A
  • CBI245A
  • CBI2410A
  • Input110230Vac
  • Output 48 Vdc
  • CBI485A
  • Input110230Vac
  • Output 12 Vdc
  • CBI123A
  • CBI126A
  • CBI1210A

CBI Series
4
All models feature double output
  • A CBI unit can be used as
  • a simple battery charger or
  • an energy stations able to deliver continuous
    power supply to the load, even if the mains is
    off, like a UPS

Output for direct power supply to the load.
Output to the battery
CBI Series
5
Display features
  • Clear and straightforward identification of
    units operating status by means of LEDs display

Mains loss
- Battery fault alarm, when the mains is on -
Battery capacity below 30, when the mains is off
Two functions - Trickle or boost charge - Fault
diagnostics with flashing code
CBI Series
6
Signals on Voltage-free Contacts
  • CBI features the contact signals normally
    available on low voltage UPS systems

Mains on - Back UP Change over NA NC contact
galvanic insulation
Low Battery - Battery replacement Change over NA
NC contact galvanic insulation
CBI Series
7
Three charging modes
Boost (fast)
2 flash every sec
Trickle
1 flash every sec.
Recovery
5 flash every 1 sec
  • Mode switching occurs automatically

CBI Series
8
Diagnosis of battery status
  • CBI makes installation and maintenance easier.
  • A flashing sequence code allows to discriminate
    among various possible malfunctions.

1 flash Reverse polarity, wrong battery voltage
2 flashes Disconnected battery.
3 flashes Battery element in short circuit
4 flashes Overload.
5 flashes Battery to be replaced.
CBI Series
9
Battery life test
  • The smart features over viewing battery charge
    status and life test diagnostics ensure high
    efficiency and risk-free operation
  • A pulse stimulation is sent to the battery by a
    specific circuitry. The electric signal received
    back in response is analysed by evaluation
    algorithms able to discriminate surfeited battery
    conditions or elements in short circuit.

Pulse stimulation and assessment of battery
status
CBI Series
10
Recovery charging
  • CBI is able to recharge batteries even when their
    voltage is close to zero.
  • In this demanding condition. CBI insures
    continued power supply to the load

Typical charging curve for recovery of batteries
with voltage close to zero.
CBI Series
11
No Deep Discharge
  • Deep discharge and consequent battery damages are
    prevented
  • In case of mains off, the load is supplied till
    when the voltage reaches the value of 1.95V per
    cell.

Switch contact Low Battery triggers when the
remaining charge reaches 30 of rated capacity.
CBI Series
12
Setting of charging current
  • Setting is possible in the range 20 - 100 of
    rated charger current

CBI Series
13
Ready for charging most battery types
Position of jumper pins
  • Jumper positions
  • Open Lead Acid Trickle 2.23V Boost 2.40V
  • Sealed Lead Acid (1) Trickle 2.25 Boost 2.40V
  • Sealed Lead Acid (2) Trickle 2.27 Boost 2.40V
  • Gel Trickle 2.30V Boost 2.40V
  • No battery life test
  • Without jumper no boost charging (pos. 5)
  • Option Ni/Cd

CBI Series
14
Remote link for selection of trickle/boost
charging
Selection pins
  • On an AMP Connector
  • Allows remote control of
  • Trickle/Boost charging of the
  • battery

CBI Series
15
Protections
  • The output is protected against short circuit and
    overload
  • Protection against deep battery discharge
  • Protection against reverse polarity connection

CBI Series
16
Diagnostic checks
  • Check for elements in short circuit
  • During trickle charge the quality (resistance) on
    the battery connection is checked every 20 sec
  • During trickle charge the internal resistance of
    the battery is checked every 4 hours.
  • Appropriate voltage check, to prevent connection
    of wrong battery types
  • End of charging check
  • Check for accidental disconnection of the battery
    cables
  • Reverse polarity check

CBI Series
17
Accessories
All CBI units can be made available with the
following options
Temperature sensor for Boost (fast) charging
Cable voltage drop compensation
Remote repetition of LEDs
CBI Series
18
Typical applications
  • Remote measurement stations
  • As Mini UPS in industrial applications Power
    Supply BackUp Module
  • As simple battery chargers for
  • Gen Sets
  • Automotive
  • Nautical

CBI Series