Title: Optimizing Central Chilled Water Systems
1Optimizing CentralChilled Water Systems
- Kent W. Peterson, P.E.
- P2S Engineering, Inc.
2Everything should be as simple as possible, but
no simpler - Albert Einstein
3Foundation of Design
- Goal -
- Why look outside the plant?
- Understand how loads impact plant operation
- Understand how distribution system will operate
- Understand how temperature differential will be
effected by dynamics of system - Apply findings to chilled water system operation
Deliver CHW to all loads under various load
conditions as efficiently as possible throughout
the year
4Chilled Water Plant Efficiency
- Target kW/ton achievable in modern plants
(includes chillers, cooling towers and pumps) - 0.5 - 0.7 Excellent
- 0.7 - 0.85 Good
- gt1.0 Needs Improvement
- Do you know how your plant is performing?
5Typical Facility Load Information
- Chilled water required for each building is
determined by the building block cooling load - Central chiller plant loads depend on the actual
simultaneous load expected at the central plant - Central plant chilled water system load diversity
for multiple building facilities varies between
55-75
6Understanding Loads
- Estimated annual load profiles must be understood
to design a chilled water system that will meet
your performance expectations - Valuable data to measure and trend
- Chilled water load profiles
- Anticipated load diversity
- Know your facility central plant diversity
- Usually 400-500 GSF/ton
7Understanding Hydronics
- The pumping system will be required to operate
under various load conditions - Variable flow system differential pressures
throughout the system can be very dynamic - Hydronic system modeling should be used to design
or troubleshoot complex piping distribution
systems under various load conditions
8Purpose of Pumping Systems
- Purpose is to move enough water through system at
a differential pressure that will satisfy all
connected loads - CAUTION - Over sizing pumps can cause systems to
not function as designed and waste considerable
energy
9Hydronic Fundamentals
Variable Flow System Dynamics
10Hydronic Fundamentals
Variable Flow System Dynamics
11Balancing Considerations
Variable Flow Systems
- Too large a balancing valve pressure drop will
affect the performance and flow characteristic of
the control valve. - ASHRAE 2003 Applications Handbook, page 37.8
- Options to Consider
- No balancing valves, no balancing
- Automatic differential pressure control valves to
control differential pressure at close loads - Pressure-independent control valves
- Options NOT to Consider
- Balancing valves at variable speed pumps
12Hydronic Pumping Conclusions
- Coil heat transfer is easier to control in low
head (lt50 ft head) systems - Remote, high head loads can be served more
efficiently with variable speed series booster
pumping - Looped systems can offer redundancy and reduced
differential pressure in mains
13CHW Temperature Differential
- Lack of chilled water ?T is the largest
contributor to poor chilled water plant
performance - To predict ?T, you must know
- Characteristics of cooling coils in system
- Control valve requirements and limitations
- Control valve control algorithms and setpoints
- Load characteristics on coil
14CHW Temperature Differential
- Cooling Coil Characteristics
- Lower CHWS temperature will typically yield
higher CHWR temperature assuming load is adequate - Higher CHWS temperature will typically yield
lower CHWR temperature - CHWR temperature will begin to lower when EAT
gets close to CHWR temperature
15Factors that Degrade ?T
Assuming Coils Are Selected for Desired ?T
- Air economizers and 100 OSA systems
- Excessive distribution differential pressure
- Higher CHWS temperature - collapsing ?T
- Account for heat gain on above grade piping
- Coil control valves (specify close-off pressure)
- Not capable of controlling against differential
pressure - 3-way valves or 3-way converted to 2-way valves
- Controls not controlling
- Supply air setpoint cannot be achieved
- Valves not interlocked with AHU, out of
calibration - Improper coil selections
16?T Conclusions
- Design, construction and operation errors that
cause low ?T can be avoided - Other causes for low ?T can never be eliminated
- ?T degradation is inevitable, therefore, system
design must accommodate level of degradation
anticipated
17?T Selection
- What is the optimum ?T for chilled water and
condenser water systems? - There is no optimum ?T for all systems,
however, the following guidelines can lead to an
answer - Select chillers at various ?Ts and estimate life
cycle costs (12-20F) - If majority of chiller operating hours are at
reduced load, consider 2 gpm/ton on condenser
water
18Understanding Refrigerant Lift
- Lift SCT SST
- Saturated Condensing Temperature (SCT) is
dependent upon LEAVING condenser water
temperature - Saturated Suction Temperature (SST) is based off
of LEAVING chilled water temperature
19Lift Effect on Part Load Chiller Efficiencies
20VFD Effect on Part Load Chiller Efficiencies
21Chilled Water Plant Design
- Optimize equipment sizing, selection and
operation to efficiently provide chilled water to
the loads under various load conditions - Consider maintenance when selecting and laying
out equipment - Select a plant configuration that best suits the
system requirements - Do not make control sequences too complicated -
the plant operator must understand the sequences
22Chiller Selection
- Pick a short list of vendors based on past
experience, local representation, etc. - Determine the functional and operational
requirements by assessing the cooling load and
load profiles including hours of operation - Estimate energy usage of options
- Select system (chillers) based on lowest life
cycle cost considering capital costs, recurring
costs of operation including maintenance and
repairs
23Primary-Secondary Variable Flow
Part Load Operation - 1500 Tons
DP
750 tons
750 tons
Off
4000 GPM
VFD
42 F
51 F
Secondary Pumps
42 F
LOAD 1500 TONS
1600 GPM
57 F
FM
2400 GPM
24Variable Primary Flow
Part Load Operation - 1500 Tons
TYPICAL
DP
DP
- Auto isolation valves
- preferred to dedicated pumps
- allows slow staging
- better redundancy
- extends 1 pump operation
750 tons
750 tons
Off
2400 GPM
42 F
VFD
Primary Pumps On VFDs
42 F
LOAD 1500 TONS
NO FLOW
57 F
57 F
FM
FM
2400 GPM
2400 GPM
25Advantages of Variable Primary Flow
- Lower First Costs
- Less Plant Space Required
- Reduced Pump Energy
- Higher efficiency pumps
- Reduced pressure drop due to fewer pump
connections, less piping
26Variable Primary Flow Design Issues
- Evaporator flow
- Typically minimum 3 fps extended
- Rate of change limits (usually maximum 30 per
minute) - Complexity of control
- Not as fail-safe - what if bypass valve fails at
low flow? - Must avoid abrupt flow shut-off (e.g. valves
interlocked with AHUs all timed to stop at same
time) - Flow fluctuation when staging chillers on
- CHW TES integration can be difficult
27Thermal Storage
- Chilled water thermal storage is a viable means
of increasing chiller plant efficiencies to
reduce KW/ton of delivered chilled water - Near full load operation during charge
- Ambient relief on tower to reduce condenser water
temperatures - Reduction in peak chiller capacity requirement
- Keep it simple
28Control Issues
- Control strategies should consider impact on
complete system including HVAC systems - Control strategies should try to continually
optimize energy consumption for entire system - Reliable controls are essential
- Remember to keep it as simple as possible
29Building Interface Considerations
- Avoid chilled water tertiary loops whenever
possible - Remember cooling coil fundamentals
- A variable speed booster pump should be used to
boost differential pressure when required
30A Case for Metering
- Most efficiently designed systems are horribly
inefficient after several years of operation - Do you really know how your systems are
operating? - How can we improve if we dont monitor key
metrics? - Load and utility consumption data are essential
for efficient operations
31A Case for Commissioning
- Commissioning is a systematic process of assuring
that a system performs in accordance with the
design intent and the owners operational needs - Re-commissioning
32Summary
- Start design process outside the plant
- Understand parameters that affect chiller plant
and overall system performance - Right size your equipment to deliver CHW to all
loads under various load conditions as
efficiently as possible throughout the year - Commission plant
- Optimize control sequences
33Energy Trend
- World energy demand is forecasted to increase
170 from 2000 to 2030 - Electrical demand will double
- Fossil fuel will provide 90 of increase in
demand - Carbon dioxide emissions will increase 170
- Energy Efficiency is a Must
- What is our responsibility?
34For More Information
- ASHRAE Self Directed Learning Course
Fundamentals of Water System Design - ASHRAE 2003 HVAC Systems and Equipment Handbook
- ASHRAE Transactions and Journal
- Hydronic System Design Operation by E.G. Hansen
35Optimizing CentralChilled Water Systems