Title: Ultra High Performing HVAC OptimumLOOP
1Ultra-efficient Chilled Water Plants for Shopping
Centers The International Council of Shopping
Centers Ben Erpelding, P.E.May 19, 2009
2Chiller Plant miles per gallon
3Chiller Plant miles per gallon
4Package Unit 1.1 kW/ton (new) to 2.0 kW/ton (at
15 years) (2.6 kW/ton at 20 years)
5Las Vegas Load Profile
6Comfort Cooling Load Profiles
7Shopping Mall Design Rules
- All chilled water valves must be two-way and
fully modulating (0-100). - Network chilled water valves to central plant
control system. - Install variable frequency drives on all central
plant chillers, towers and CHW CDW pumps. - Outside air lockout of chilled water plant (62 to
64 deg F). - All variable speed controls optimization
sequences. - Sub metering and monitoring performance.
8All Variable Speed Chiller Plants
9Large Mall Central Plant (So. Ca)
- 4,500,000 ton-hrs per year
- Total central plant energy usage 5,660,000
kWh/yr - Water usage 11,000,000 gal/yr
- This equates to is a 1.23 kW/ton average central
plant efficiency and 2.4 gal per ton-hr water
usage. - Post retrofit 0.53 kW/ton and 2.0 gal per
ton-hr - 450,000/yr savings
- 1.4 year payback (74 IRR)
10Mall Central Plant (Midwest)
- 607,000 kWh per yr savings
- 273,000 gal per yr
- 60,300/yr
- 208,000 implementation cost
- 30,000 utility incentive
- 2.7 yr simple payback
- 33 IRR
- 327,000 NPV
11Mall Central Plant (New York)
- 793,000 kWh per yr savings
- 276,000 gal per yr
- 149,000/yr
- 475,000 implementation cost
- 135,000 utility incentive
- 2.2 yr simple payback
- 45 IRR
- 681,000 NPV
12Mall Central Plant (Florida)
- 966,000 kWh per yr savings
- 556,000 gal per yr
- 123,900/yr
- 493,000 implementation cost
- 0 utility incentive
- 4.0 yr simple payback
- 23 IRR
- 342,000 NPV
13Central Plant Utility Bills
14Before and After Total Plant Energy Usage (kW)
15DDC Performance Commissioning
16Water Usage in Cooling Towers
17- Additional questions and comments
- Utility incentives
- Comfort and reliability
- Demand Response
- LEED Buildings
- Maintaining energy savings over time
- ContactBen Erpelding, P.E., C.E.M.
- 619-417-9984
- ben.erpelding_at_optimumenergyco.com
- www.optimumenergyHVAC.com