Title: INTRODUCTION TO T
1INTRODUCTION TO TT ELECTRICAL WIRING CODETTS
171 PART 1 2002
- By GEORGE SAMPSON
- ELECTRICAL INSPECTOR III
- GOVERNMENT ELECTRICAL INSPECTORATE
2What is the TT Wiring Code?
- Revised edition of TTS 26 20 505-1978
- REQUIREMENTS FOR THE ELECTRICAL WIRING OF
BUILDINGS AND EQUIPMENT -
- More Comprehensive
- Additional technical information.
3WHO BENEFITS?
- Electrical Fraternity members and clients
- AREAS
- Designing
- Planning
- The actual installation of a wiring system
4 SCOPE
- COVERS
- Installations up to 600 volts
- NOT COVERED
- Installations operated by Authorities for
- the Generation Distribution of
- electrical power such as
- Powergen
- InnCogen
- TTEC
5ENFORCEMENT
- HOW?
- The CEI is the authority with jurisdiction
- Interpretation
- Enforcement of this standard
6CONFLICT
- If ever, any conflict arises between TTS 171 and
any other standard, the CEI shall be the sole
arbitrator and his decision shall be final
7WHATS NEW?The terminologies are in harmony
with international standards Examples
2002 1978
Ground Earth
Grounding Conductor Earth Continuity Conductor
Grounding Electrode Conductor Earthing Lead (MEC)
Receptacle Outlet Socket Outlet
8WHATS NEW ? ( Contd )
- Ground Fault Circuit Interrupter Ground Fault
Protection of equipment are also new to the list
of definitions.
9ANNEX C
- Revision of TTS 1978 ( Table 21 )
- Guidelines on sub-circuit requirements for
- Residential
- Commercial
- Industrial Installations
10 - Simple Formulae and Worked Example for voltage
drop calculation ( section D.1.7.3) - New to this standard
- It was included to assist with the application of
the Voltage Drop Tables
11ANNEX EMaximum conductor fill for Conduits
Boxes
- Consider a practical case
- Install the following conductors within a common
raceway - 6 x 1.5mm sq.
- 8 x 2.5mm sq.
- 4 x 6.0mm sq.
- 6 x 4.0mm sq.
12Comply with section 6.2.7
- A space factor of 40 is not to be exceeded.
- The cables are not to be damaged.
- No more than two ( 2 ) 90 degrees bends are
allowed along the conduit work.
13DISTRIBUTION AND PROTECTION (Section 4.1.1)
- Every consumers installation shall be adequately
controlled by a service disconnect. i.e. Main
Switch or Circuit Breaker - Does this requirement apply to systems utilizing
standby power from a Generator?
14 - The CEI requires that all wiring systems are to
comply with section 4.1.1 whether they utilize a
standby Generator or not. - In addition, those with standby power must
incorporate suitable Transfer Equipment.
15Why Transfer Equipment?
- This is to prevent the inadvertent or accidental
interconnection of the normal (TTEC) and the
standby ( Generator) sources of power.
16- HIGHLIGHTS FROM OTHER SECTIONS OF THE CODE
17MARKINGS
- Section 3.10.1 requires each piece of electrical
apparatus and material to bear such markings to
identify it - To ensure its suitability for the particular
application
18Examples of Markings
- Manufacturers name, trademark, or other
recognized symbols of identification - Rated load in amperes
- Rated frequency or frequency ranges in hertz
- Whether for continuous load or intermittent
19Consequences of failure to conform to technical
data
- Persons could receive a severe electric shock
- Explosion or fire may occur
- Serious injury may occur from a fall or flying
objects - Electrocution is also a very, very real
possibility
20- The foregoing are sufficient reasons to be
meticulous when selecting equipment and materials.
21GROUNDING ELECTRODE CONDUCTOR GROUNDING
CONDUCTOR
22- Why should we give the Grounding Electrode
Conductor and the Grounding Conductor the respect
they deserve?
23Three basic reasons for grounding
- Limits the voltage caused by lightning, or by
accidental contact with conductors of higher
voltages. - Stabilizes the voltage under normal operating
conditions - to maintain the voltage at one level
relative to ground so equipment connected to the
system is subjected only to that potential
difference. - Facilitates the operation of over current devices
such as fuses, circuit breakers or relays under
ground fault conditions.
24Selection and application of
- The Grounding Electrode Conductor and the
Grounding Conductor deserves our keenness
attention - Sizes of grounding conductors
- ( Sec 9.5 )
- See Current Ed. Of NFPA 70 Tables
- 250-66 and 250-122
25APPARATUS IN GARAGES (Section 8.5)
- Where motor-driven vehicles are
- Stored
- Serviced
- Repaired
- All apparatus shall, unless of a totally enclosed
or flameproof type, be installed at a minimum
height of 1200mm ( 4ft ) above the general floor
level.
26SEGREGATION OF CIRCUITS (Section 5.23 )
- Lighting and power cables operating at voltages
above extra-low ( i.e.exceeding 50 V a.c. or - 120 V d.c. whether between conductor or to
ground). - Shall not be drawn into the same conduit or duct
as cables of extra-low voltage or of radio
systems. - Unless the latter are insulated for the higher
voltage present.
27Note
- Failure to observe these guidelines
- may result in Electromagnetic
- Induction (EMI ) and disruption of
- the extra-low voltage equipment.
28RACEWAY INSTALLATIONS (section 6.1.1)
- Conduit works shall be completed before any
cables are drawn in. - Ends shall be reamed and bushed to avoid
abrasion. - Inspection boxes shall remain accessible
throughout the life of the installation.
29TESTING AND INSPECTION(Section 10 )
- To determine what malfunctions are possible
- To determine what protection is necessary and
sufficient - To minimize the ill-effects of such malfunctions
30Section 10.1.1
- Requires that every new installation and
- any alteration to an existing installation
- shall be inspected and tested to ensure
- compliance with TTS 171
31Inspection and Testing
- Involves
- Visual examination of workmanship
- Verification of polarity (I.R.test)
- Effectiveness of grounding
- Continuity
- A verification of polarity shall be made to
ensure that all fuses, circuit breakers and
single pole control devices, are connected to
live conductors only.
32Since ground fault protection relies on
operation of fuses or circuit breakers, the
resistance or impedance between the electrode and
the remote end of every grounding conductor,
shall not exceed 1 ohm.
- Where metal conduit forms part or whole of the
grounding conductor, the above shall also apply.
33Electrical Metallic Tubing ( EMT )
- Shall be protected against any risk of mechanical
damage. - Not to be exposed to rain, dripping water,
condensation, oil, corrosive substances and
hazardous location. - Not bend, as to damage the tubing or to
effectively reduce its internal diameter. - Not be buried directly in the ground.
34CONTROL OF MOTORS (Section 8.12.2)
- Each motor and its control equipment shall have a
disconnecting means. - For remote disconnecting means
- an additional means of isolation adjacent to the
motor shall be installed OR - a lockout device shall be installed adjacent to
the motor - The remote means of isolation shall be able to be
locked in the off-position.
35Conclusion
- Section 3.1.2 reads in part
- This standard contains minimum provision
considered necessary for safety, but is not to be
regarded as a design specification or an
instruction manual for untrained persons.
36