Project
  • FINAL PROJECT DELIVERABLES
  •  
  • 1) PROJECT REPORT
  • - Project statement (introduction) 2 pages
  • Explain what are you designing/analyzing and why
    is that important
  • On the second page
    clearly identify (bullet list) project outcomes
  • - Building description (geometry) 1-3 pages
  • Schematics that focus on your system(s)
  • Identify all assumptions and simplifications
    you introduced
  • - Methodology 1-3 pages
  • Describe methodology (equations, schematics, )
  • Provide a list of assumptions used in your
    methodology
  • - Results 3-5 pages
  • Formatted results with comments
  • Tables, Charts, Diagrams,
  • Analysis and Results discussion
  • - Summary 0.5-1 page
  • Summary of most important results

3
Project
  • Grading criteria
  •  
  • 1) Approach and solution quality 60
  • - Methodology 20
  • - Accuracy 20
  • Result analysis 20
  • 2) Deliverables 40
  • - Final report 40
  • - clarity
  • - completeness
  • - steed assumptions and limitations
  • - quality of graphs, tables schematics,.

4
Objectives
  • Learn about
  • 1) DOAS
  • - Principle of operation
  • - Design
  • - Advantages and disadvantages
  • 2) Control for HVAC systems
  • - Economizers (Psychrometrics) and control
  • - Heat recovery systems (Psychrometrics)

5
www.doas.psu.eduDOAS with multi-split systems
  • Fresh air?

6
DOAS fresh air configurations
7
DOAS fresh air configurations
8
Issues Related to DOAS
  • Split of sensible and latent load
  • Selection of hydronic system
  • Winter vs. summer operation
  • Winter operation with DX systems (heat pump)

9
Economizer
  • Economizer (fresh air volume flow rate control)
  • Controlled device is damper
  • - Damper for the air
  • - Valve for the CC

fresh air
damper
mixing
recirc. air
T RH sensors
10
Economizer cooling regime
  • How to control the fresh air volume flow rate?
  • If TOA lt Tset-point ? Supply more fresh air
    than the minimum required
  • The question is how much?
  • Open the damper for the fresh air
  • and compare the Troom with the Tset-point .
  • Open till you get the Troom Tset-point
  • If you have 100 fresh air and your
  • still need cooling use cooling coil.
  • What are the priorities
  • - Control the dampers and then the cooling coils
    or
  • - Control the valves of cooling coil and then
    the dampers ?
  • Defend by SEQUENCE OF OERATION
  • the set of operation which HVAC designer provides
    to the automatic control engineer

fresh air
100
Minimum for ventilation
11
Economizer cooling regime
  • Example of SEQUENCE OF OERATIONS
  • If TOA lt Tset-point open the fresh air damper
    the maximum position
  • Then, if Tindoor air lt Tset-point start
    closing the cooling coil valve
  • If cooling coil valve is closed and T indoor air
    lt Tset-point start closing the damper
  • till you get T indoor air T set-point
  • Other variations are possible

12
Sequence of operation for the humidity control
system design
Adiabatic humidifier
CC
HC
SA
OA
  • mixing

RA
  • Define the sequence of operation for
  • WINTER operation and
  • - case when humidity is not controlled
  • - case when humidity is precisely controlled

13
Sensible and Enthalpy and Desiccant wheels
14
Sensible and Enthalpy Wheels
15
Desiccant wheel