Fire Walls, Fire Barriers - PowerPoint PPT Presentation

1 / 47
About This Presentation
Title:

Fire Walls, Fire Barriers

Description:

Fire Walls: Purpose, What, Where, Features, Extensions, Maintenance and the ... Visual Insp. - Monthly. Test - Annually. 31. Vertical ('Roll-Up') Fire Doors ... – PowerPoint PPT presentation

Number of Views:1902
Avg rating:3.0/5.0
Slides: 48
Provided by: scottg2
Category:
Tags: barriers | fire | insp | walls

less

Transcript and Presenter's Notes

Title: Fire Walls, Fire Barriers


1
Fire Walls, Fire Barriers Protection of
Penetrations
2
Fire Separations
  • Fire Walls Purpose, What, Where, Features,
    Extensions, Maintenance and the Sealing of
    Openings
  • Fire Separation or Barrier Walls "Not a fire
    wall! OBC calls these Fire Partitions
  • Penetration Protection What and Where

3
The Purpose of Fire Walls
  • Building Codes and Country Codes recommended fire
    walls for only two purposes
  • To make sure that everyone can evacuate the
    building safely during a fire
  • To make sure you do not affect your neighbors
    property following a fire
  • Effective fire risk management recommends fire
    walls serve two additional and very important
    purposes
  • To help protect business operations (production)
  • To protection assets and reduce total property
    damage.

4
Where are Fire Walls Provided?
  • To separate production operations and reduce
    business interruption potential
  • Separate manufacturing from warehousing
    operations
  • Protect from external exposure
  • As required by Building Codes to separate
    buildings

5
(No Transcript)
6
Features of a Fire Wall
  • Extend through all floors of a building
  • 2, 3 or 4 hour rated - time/temperature curve
  • Usually Masonry but may be a composite
    construction
  • Stable and Strong - often "free standing", the
    wall supports itself, nothing else supports it
  • Can absorb shock from collapse on either side
  • No openings - or protect openings with a physical
    barrier (such as a "fire door" or a "sealing
    system").
  • Parapets and Wing walls - provided when needed

7
The roof is not supported by the fire wall
The bar joists are parallel to the wall or, if
perpendicular, there will be a gap to allow for
expansion due to heat.
8
Fire Wall Extensions - Parapets and Wing Walls
  • Parapet Wall Fire wall extension above a roof.
  • Provided if the roof is considered combustible
    per NFPA 221 Chapter 6.
  • It is to stop fire spread at the roof.
  • Minimum parapet height 0.8 meters (30").
  • Wing Wall Fire wall extension outside a
    building.
  • Provided if the exterior walls are not
    noncombustible per NFPA 221.
  • Stop fire spread around the ends of the fire
    wall.

9
Fire Wall Extensions - Parapets
"Let's discuss the purpose of a parapet"
10
Fire Wall Extensions - Parapets
11
Fire Wall Extensions - Wing Walls
Manufacturing Area
  • Wing walls are extensions to a fire wall that
    stop fire traveling around its end.
  • 1 Wing walls can extend beyond a fire wall.
    This is an extension wall
  • 2 Wing walls can be part of the external
    perimeter wall.
  • This is an end wall (it is at the end of the
    fire wall).

1
2
Fire in the Warehousing Area
Per NFPA 221 1 .8m (30") minimum 2 1.8 -
4.3m (6' - 14')
12
Fire Wall Extensions - Wing Walls
  • This wing wall projects out
  • 1.2m (4') from the building.

13
Fire walls provided to meet fire risk management
goals
14
Fire Separation or Barrier Walls
  • A wall that is designed to limit the spread of
    fire and smoke from a controlled fire.
  • Usually rated a maximum of 1 to 2 hours
  • May be masonry or protected steel frame walls
  • Does not extend through all floors
  • Divides floors into areas - "fire areas
  • Used for shafts
  • Usually do not have parapet or wing walls
  • Openings are protected - but they are not as
    important as fire wall openings

15
Testing for Fire Protection Fire Endurance
  • "What is a "4 hour rating"?
  • See the next slide for the "Time - Temperature
    Curve"

16
Testing for Fire Protection Fire Endurance
  • The temperature during a fire test is increased
    in accord with this curve.
  • After 5 minutes the temperature is 538oC
    (1000oF).
  • After 4 hours the temperature is 1093oC (2000oF).

17
Openings in Fire Walls
  • The only true fire wall is a fire wall with no
    openings but few of these exists.
  • The number and size of openings should be limited
    as much as possible.
  • All fire wall openings big and small must be
    protected.
  • That includes opening such as pedestrian
    openings, truck doors, conveyors, duct
    penetrations, pipe and cable penetrations, etc.
  • Fire wall maintenance includes sealing all
    openings!

18
Sealing Openings in Fire Walls
19
Sealing Openings in Fire Walls
FOR PIPE OPENINGS
20
Sealing Openings in Fire Walls
  • A blocked up window or conveyor opening
  • Using concrete block to fill old unused openings
    is efficient and relatively inexpensive.
  • Be sure to fill the blocks with cement and then
    cement them in place!
  • The fill must be equal in fire resistance to the
    wall.

21
Dont get carried away!
22
Duct Penetrations
23
Penetration Protection
  • Horizontal Penetrations
  • Vertical Penetrations

24
Penetration Protection
  • Listed through penetration fires stop assemblies

25
The good, the bad, . . .
  • Listed assembly
  • A poor attempt

26
. . . And the Ugly
27
Fire Doors NFPA 80
  • A "fire door" is the door and the frame!
  • Tested and listed to stop fire only. Smoke may
    pass around the sides of the door.
  • Fire doors are rated by the number of hours of
    fire protection they provide.
  • 4, 3 and 1-1/2 hour ratings are common.
  • 1, 3/4 hour and 20 minute ratings are used for
    fire partitions and for life safety purposes.
  • The door is matched to the wall.
  • A three or four hour wall will have a three or
    four hour door.
  • PG usually provides one fire door at each wall
    opening. Good maintenance is needed to ensure it
    will close if there is a fire!

28
Fire Doors- Personnel Door
Listing mark on door
Listing mark on frame
29
Vertical (Roll-Up) Fire Doors
  • This is a motorized roll up fire door.
  • Roll up fire doors are all uninsulated.
  • The motor allows easy testing and resetting of
    the door.

30
Vertical (Roll-Up) Fire Doors
  • What can cause roll up doors to fail?
  • 1. Rail damage
  • 2. Fusible links (circled) painted or replaced by
    wire
  • 3. Blocked open
  • 4. Cover damaged
  • 5. Other causes?
  • Perform
  • Visual Insp. - Monthly
  • Test - Annually

31
Vertical (Roll-Up) Fire Doors
  • A damaged cover for a roll up fire door.

32
Horizontal (Sliding) Fire Door
  • This is a horizontal fire door.
  • It is 3 hour rated and insulated.
  • The weights on the right hold it open.

33
Horizontal (Sliding) Fire Door
34
Horizontal (Sliding) Fire Door
  • Fusible link at the top of the opening for a
    doorway.
  • Theoretically a fire on either side of the wall
    will operate it!
  • The fusible link is 57oC (135oF) or 74oC (165oF).

35
Horizontal (Sliding) Fire Door
  • A horizontal fire door stay roll (roller/wedge)
    assembly pushes the door against the wall when
    the door shuts and prevents it being pushed away
    from the wall.
  • Fire door binders stop the rolling door and hold
    it in place. They are also known as "doorstops".

36
Fire Doors - Hidden Above False Ceilings
  • This is a smoke detector that controls a fire
    door.
  • The door is above the false ceiling.
  • Access is through the hatch.

37
Oops. . . Alwaystest on completion
38
Window Openings in Fire Walls
Looks out into the manufacturing area
39
Conveyor Openings in Fire Walls
Will an opening with sprinklers on each side stop
a fire?
40
Conveyor Openings in Fire Walls
Fire doors above conveyors. How would they be
controlled?
41
Conveyor Openings in Fire Walls
Fire doors that close down and block off the
conveyors.
42
Vertical Door for a Conveyor Opening
  • This door and the one on the next page contain
    fire stop material in the body of the door.
  • Operates by smoke detector and manually.

43
Horizontal Fire Door for a Conveyor Opening
44
Conveyor Opening
  • This non breakable conveyor passes through a fire
    wall.
  • Sprinklers are provided on each side of the wall.
    Each is supplied from the "other" side of the
    wall.
  • Is this permitted?

45
Inspection, Testing Maintenance
46
Proper maintenance required
  • Fire walls and barriers only work when properly
    maintained.
  • Protectives must be inspected, tested and
    maintained.

47
  • QUESTIONS
Write a Comment
User Comments (0)
About PowerShow.com