Title: Advances in protection criteria for storage occupancies
1Advances in protection criteria for storage
occupancies
- James Golinveaux
- Sr. VP Research Development
2(No Transcript)
3Test 70
Base Line Tests Design Curves Class I, II,
III IV Commodity20-ft High Rack Storage165F
Ceiling Sprinklers
Class II Class III Class IV
Test 78
Test 75
Test 64
Test 65 66
Test 99
Class II Curve
Class III Curve
Class IV Curve
Class I Curve
Test 74
Test 68
4NFPA 13 2002-2007Significant Technical Changes
- James Golinveaux
- Sr. VP Research and Development
5Solid-Pile Palletized Storage
Solid Pile Storage
Palletized Storage
6Typical Storage Arrangements
- Rack Storage (No Solid Shelves)
- Single Row
- Racks that have no longitudinal flue space and
that have a width up to 6ft (1.8m) with aisles at
least 3.5ft (1.1m) from other storage. - Double Row
- Two single-row racks placed back-to-back having a
combined width up to 12ft (3.7m), with aisles at
least 3.5ft (1.1m) on each side. - Multiple Row
- Racks greater than 12ft (3.7m) wide or single- or
double-row racks separated by aisles less than
3.5ft (1.1m) wide having an overall width greater
than 12ft (3.7m).
7Self Storage
- Shelf Storage. Storage on structures less than
30 (76.2 cm) deep with shelves usually 2 (0.6
m) apart vertically and separated by
approximately 30 (76.2-cm) aisles.
8Solid Shelving
- Fixed in place, slatted, wire mesh or other type
of shelves located within racks. - The area of a solid shelf is defined by perimeter
aisle or flue space on all four sides. - Solid shelves having an area equal to or less
than 20 sq. ft. are open racks. - Shelves of wire mesh, slates, or other materials
more than 50 open, where the flue spaces are
maintained are open racks.
9Storage on Solid Shelving
- Where the area of the solid shelving is less than
20 ft2 - In-rack sprinklers are not required
- Where the area of solid shelving is 20 - 64 ft2
- In-rack sprinklers are not required below every
shelf - In-rack sprinklers shall be installed at the
ceiling below shelves at intermediate levels
not more than 6 ft apart vertically. - Where the area of solid shelving is greater than
64 ft2 - In-rack sprinklers shall be installed at the
ceiling below each level of shelving.
10Chapter 5Classification of Occupancies and
Commodities
11Chapter 5
- 5.3.2 Ordinary Hazard (Group 2). Ordinary hazard
(Group 2) occupancies shall be defined as
occupancies or portions of other occupancies
where the quantity and combustibility of contents
are moderate to high, where stockpiles of
contents with moderate rates of heat release do
not exceed 12 ft and stockpiles of contents with
high rates of heat release do not exceed 8 ft.
Dedicated and Miscellaneous storage shall be
protected in accordance with Chapter 12 and 13 as
applicable.
12Chapter 5
- A.5.3.2 Exterior loading docks only utilized for
loading and unloading should be classified as
OH2. Where utilized for storage exterior loading
docks and all interior loading docks should be
protected based upon the actual occupancy, the
materials handled on the dock, as if the
materials were actually stored in that
configuration.
13Chapter 7 Dry Pipe - Preaction
- Size of Dry Pipe and Double Interlock Preaction
Systems - 60 Seconds to inspectors test connection
- Calculated for water delivery in accordance with
Table - Water delivery to a test manifold in accordance
with the Table. Added annex figure for Test
Manifold - 500 gal and 750 gal options Not Applicable to
Dwelling Unit Applications.
14Chapter 8
- Add to A.8.1.1
- Based upon experience and testing, sprinklers
have been found to be effective and necessary at
heights in excess of 50 ft. For a building to
meet the intended level of protection afforded by
NFPA 13, sprinklers must not be omitted from such
high ceiling spaces.
15Chapter 8 - ESFR
- ESFR Sprinklers
- Minimum Protection Area of Coverage. The minimum
allowable protection area of coverage for a
sprinkler (As) shall not be less than 64 ft2
(6m2).
16Chapter 12Storage
17Chapter 12
- 12 - General Requirements for Storage
- 12.1 NFPA 13 2002
- 13 - Storage of Miscellaneous Commodities
- 12.1.10 NFPA 13 2002
- 14 - Storage of Palletized, Solid Pile, Bin Box,
or Shelf Storage of Class I through IV
Commodities - 12.2.1 and 12.2.2 NFPA 13 2002
18Chapter 12
- 15 - Storage of Palletized, Solid Pile, Bin Box,
or Shelf Storage of Plastic and Rubber
Commodities - 12.2.1 and 12.2.3 NFPA 13 2002
- 16 Rack Storage of Class I through IV
Commodities - 12.3.1, 12.3.2, 12.3.4 NFPA 13 2002
19Chapter 12
- 17 Rack Storage of Plastic Commodities
- 12.3.1, 12.3.3, 12.3.5 NFPA 13 2002
- 18 Protection of Rubber Tire Storage
- 12.4 NFPA 13 2002
- 19 Protection of Rolled Paper
- 12.6 NFPA 13 2002
- 20 Special Designs
- 12.7 and 12.5 NFPA 13 2002
- Automotive Components/Retail/Baled Cotton
20Chapter 12General Requirements for Storage
21Chapter 12
- 12.1.2.5 For ceiling heights that exceed 30 ft,
where the distance between the ceiling height and
top of storage exceeds 20 ft (6.1 m), protection
shall be provided for the storage height that
would result in a 20-ft (6.1-m) distance between
the ceiling height and top of storage. - Added annex material to address history and
intent.
22Chapter 12
- Deleted Section 12.1.6.3
- All Dry Pipe and Preaction Systems protecting
storage require a 30 remote area increase.
23Chapter 13Storage of Miscellaneous Commodities
24Miscellaneous Storage
- Incidental Storage lt 12ft (3.7m)
- Storage lt 10 of building area or 4000 ft2 (372
m2) of the sprinklered area, whichever is greater - Storage shall not exceed 1000 ft2 (93 m2) in one
pile or area - Each such pile or area shall be separated from
other storage areas by at least 25ft (7.6m)
25Commodity Classes Class I
- Noncombustible product that meets one of the
following criteria - Placed directly on wooden pallets
- Placed in single-layer corrugated cartons, with
or without single-thickness cardboard dividers,
with or without pallets - Shrink-wrapped or paper-wrapped as a unit load
with or without pallets
26Commodity Classes Class II
- Noncombustible product that is in slatted wooden
crates, solid wood boxes, multiple-layered
corrugated cartons, or equivalent combustible
packaging material, with or without pallets.
Metal-lined double tri-wall corrugated carton on
a wood pallet
27Commodity Classes Class III
- A product fashioned from wood, paper, natural
fibers, or Group C plastics with or without
cartons, boxes, or crates and with or without
pallets. - Group C plastics
- Fluoroplastics (PCTFE polychlorotrifluoroethylen
e PTFE polytetrafluoroethylene) - Melamine (melamine formaldehyde)
- Phenolic
- PVC (polyvinyl chloride flexible PVCs with
plasticizer content up to 20 percent) - PVDC (polyvinylidene chloride)
- PVDF (polyvinylidene fluoride)
- PVF (polyvinyl fluoride)
- Urea (urea formaldehyde)
- A limited amount (5 by weight or volume or less)
of Group A or Group B plastics.
Paper cups in compartmented cardboard cartons on
wood pallets
28Commodity Classes Class IV
- A product, with or without pallets, that meets
one of the following criteria - Constructed partially or totally of Group B
plastics - Group B plastics
- Cellulosics (cellulose acetate, cellulose acetate
butyrate, ethyl cellulose) - Chloroprene rubber
- Fluoroplastics (ECTFE ethylene-chlorotrifluoro-e
thylene copolymer ETFE ethylene
tetrafluoroethylene-copolymer FEPfluorinated
ethylene-propylene copolymer) - Nylon (nylon 6, nylon 6/6)
- Silicone rubber
- Consists of free-flowing Group A plastic
materials - Contains within itself or its packaging an
appreciable amount (5 to 15 by weight or 5
to 25 by volume) of Group A plastics
A mixture of paper and plastic cups (15 plastic
by weight) on wood pallets.
29Commodity Classes Group A
- Plastic materials
- Cartoned vs. Uncartoned (Exposed)
- Expanded vs. Unexpanded
16-oz (450 g) Polystyrene Plastic Jars in
compartmented cardboard cartons
Expanded Polystyrene Trays Exposed
30Encapsulation
- Plastic sheet completely enclosing the sides and
top of a pallet load containing a combustible
commodity - Combustible commodities individually wrapped in
plastic sheeting and stored exposed in a pallet
load - Where there are holes or voids in the plastic on
the top of the carton that exceed more than half
of the area of the cover, the term encapsulated
does not apply
31Chapter 5 Classification of Commodities (Old
Chapter 2)
- For Class I - IV commodities stored on
non-reinforced polypropylene or non-reinforced
high-density polyethylene plastic pallets - The classification of the commodity is increased
one class (e.g., Class III becomes Class IV
Class IV becomes Group A plastics) - For Class I - IV commodities stored on reinforced
polypropylene or reinforced high-density
polyethylene plastic pallets - The classification of the commodity is increased
two classes (e.g., Class II becomes Class IV
Class III becomes Group A plastics) - No increase in the commodity classification is
required for Group A plastics stored on plastic
pallets
32Plastic Pallets and Storage
- Use will require you to increase by one (1)
commodity classification (ieclass III commodity
increases to class IV) - Plastic Pallets Very Desirable Method For
Storage Options - Easy to Maintain
- Lasts Longer
- Recyclable
- Food Service
- Ability to Sterilize
33Plastic Pallet Types
- Un-reinforced plastic pallets
- Melt fairly easily in a fire and are less of a
fire challenge - Material
- Polypropylene
- high-density polyethylene
- Reinforced plastic pallets
- Hold their structure and integrity longer
allowing air gaps to remain longer within the
pallet, which fuels the flames and creates a more
intense fire - Material
- Polypropylene
- high-density polyethylene
34Storing Materials on Plastic Pallets
- One class upgrade for un-reinforced plastic
pallets - Class II -gt Class III
- Class IV -gt Group A Plastics
- Two class upgrade for reinforced plastic pallets
- Class II -gt Class IV
- Class IV -gt Group A Plastics
- 2007 Assume all plastic Pallets are reinforced
unless proven otherwise
35Why is Changing the Classification of a Commodity
so important?(8 (2.44 m) Isles, High Temp Std.
Spray Sprinklers)
36Successful Fire Testing With Plastic Pallets in
Racks K17-231 Sprinklers
- Successful Testing With K17-231 sprinklers will
Result in Keeping Same Class - (No Increase)
- Same Design Area and Density
- Pressure Requirements Very Low
37What's the Alternative?
- NFPA 2002 -135.6.2.6 For ceiling-only sprinkler
protection, the commodity class increase
requirements of 5.6.2.2 and 5.6.2.3 shall not
apply where plastic pallets are used and where
the sprinkler system uses spray sprinklers with a
K-factor of 16.8. - NFPA 2007 -135.6.2.6 For ceiling-only sprinkler
protection, the requirements of 5.6.2.2 and
5.6.2.3 shall not apply where plastic pallets are
used and where the sprinkler system uses spray
sprinklers with a minimum K-factor of 16.8.
TFP K17-231
38Idle Wood Pallets Chapter 12
39Idle Plastic Pallets Storage
- Store Plastic Pallets Outside
- Store Plastic Pallets in Detached Structure
- Store Plastic Pallets Indoors
- Stored in cutoff room
- Must have at least 1 exterior wall
- 3-hour separation required
- 0.6 gpm/sq. ft. over entire room, high expansion
foam, or ESFR protection - Max. Storage Height 12
- Columns must be protected
- Stored without cutoff room
- Max. Storage Height 4
- High temperature rated sprinklers
- Each pallet pile of no more than two stacks must
be separated from other pallet piles by at least
8 or 25 of stored commodity.
40Idle Plastic Pallets Storage
- Indoor storage of plastic pallets shall be
permitted to be protected in accordance with the
following arrangement - Maximum storage height of 10
- Maximum ceiling height of 30
- Sprinkler density 0.6 gpm/sq. ft. over 2000 sq.
ft. - Minimum sprinkler K-factor of 16.8
TFP K17-231
TFP EC-25
41Standard Coverage Upright Pendent 11.2 (160)
14.0 (200) K-factor Class I IV Cartoned
Uncartoned (Exposed) Group A Unexpanded plastics
25 (7.6m) Building 20 (6.1m) Storage .6
gpm/ft2 (24.5 mm/min)
27 (8.2m) Building 20 (6.1m) Storage .6
gpm/ft2 (24.5 mm/min)
42Standard Coverage Upright Pendent 16.8 (240)
K-factor Class I IV Cartoned Uncartoned
(Exposed) Group A Unexpanded plastics
30 (9.1m) Building 25 (7.6m) Storage .8
gpm/ft2 (32.6 mm/min)
25 (7.6m) Building 20 (6.1m) Storage .6
gpm/ft2 (24.5 mm/min)
27 (8.2m) Building 20 (6.1m) Storage .6
gpm/ft2 (24.5 mm/min)
43Control Mode Density/Area Extended Coverage
- Sprinkler Type
- 25.2 (360) K Up
- Max Area of Coverage
- 196ft2 (18.2m2)
- Max Distance Between Sprinklers
- 14ft (4.3m)
- Design
- Calculate all the sprinklers within a given
geometric area at a specific density
44Extended Coverage Sprinklers for Extra Hazard
Storage Occupancies
- Traditional Sprinklers limited to 100 ft2 EC-25
can cover up to 196 ft2 - Big Box Industry committed to using this
sprinkler (Wal-Mart, Best Buy, Target, Office
Depot, Sams Club Bed, Bath Beyond, Costco
Home Depot)
20 high storage of Class II commodity in a 30
high building
45Performance Analysis on Temperature Control
15 of Plastic in a 25 Building
46Branch Line Savings
EC-25 2 Branch Lines
Std. Spray 3 Branch Lines
47EC-25 Operating Pressure at Various Spacings
48EC-25 Design Pressure Comparisons
EC-25s typically requires less pressure than
standard spray sprinklers with fewer sprinklers
in the design area far greater spacings
49EC Storage Upright
50Extended Coverage Upright25.2 (360) K-factor
Class I IV Cartoned Uncartoned (Exposed)
Group A Unexpanded plastics
30 (9.1m) Building 20 (6.1m) Storage .6
gpm/ft2 (24.5 mm/min)
25 (7.6m) Building 20 (6.1m) Storage .6
gpm/ft2 (24.5 mm/min)
51Comparative Testing - 15 ft High Rack Storage of
Group A Plastics in a 25 ft High Building
52EC-17
- Application
- EC Density/Area
- Extra Hazard High Pile Storage
- Approvals Pending
- Max. Working Pressure 175 psi
- K-factor 16.8
- Temperature Rating
- 165F - 212F
53Spacing Area of Coverage
Two Branch Lines in a 30 Bay
54Extended Coverage K17 (K17EC) at Various Spacings
55EC-25 Operating Pressure at Various Spacings
56Flow Pressure Comparison
57Effect of High Discharge Pressure
- Of more than 400 control-mode tests for which
data is available, 5 used discharge pressures
greater than 75 psi.
58NFPA 13 K-factor Requirements for Storage
Protection
59Control Mode Specific Application (CMSA)
sprinklers
- Specific Application Control Mode Sprinkler For
Storage Use. A type of spray sprinkler listed at
a minimum operating pressure or density with a
specific number of operating sprinklers for a
given protection scheme. - Large Drop Sprinkler. A type of specific
application control mode sprinkler that is
capable of producing characteristic large water
droplets and that is listed for its capability to
provide fire control of specific high-challenge
fire hazards. - Design
- Calculate a specific of sprinklers at a
specific pressure
60Control Mode Specific Application Upright 16.8
(240) K-factor Cartoned Uncartoned (Exposed)
Group A Unexpanded plastics
30 (9.1m) Building 25 (7.7m) Storage 22 psi
(1.5 bar)
61Large Drop Sprinklers
- The Ultra K17 to be substituted anywhere FM Loss
Prevention Data Sheets reference Large Drop
sprinklers.
62Protecting Dry Pipe Refrigerated Warehouses
with Control-Mode Specific Application (CMSA)
Sprinklers
63NFPA 13 Appendix Examples of Commodities
- Examples of Class III Commodities
- Butter
- Whipped spread
- Cheese
- Packaged, cartoned
- Wheels, cartoned
- Fish or Fish Products
- Frozen - Plastic trays, cartoned
- Margarine
- Up to 50 oil (in paper or plastic containers)
- Examples of Class II Commodities
- Baked Goods
- Cookies, cakes, pies Frozen, packaged in cartons
- Fish or Fish Products
- Frozen - Waxed-paper containers, cartoned
- Boxed or barreled
- Frozen Foods
- Waxed-paper containers, cartoned
- Meat, Meat Products
- Frozen, waxed-paper containers
- Frozen, expanded plastic trays
- Poultry Products
- Frozen (on paper or expanded plastic trays)
64FM Testing of Dry Systems Using Large Drop
Sprinkles in the 1990s
60 sec. Delay
30 sec. Delay
65Class II 60 sec. Delay
66Class II 30 sec. Delay
67FM 8-9
68The Problem
- December 21, 2004
- FM Approvals suspended Approval of all large drop
automatic fire sprinklers - Benchmark Testing
Tyco Large Drop Sprinklers successfully passed
full-scale fire testing at UL and remain UL listed
69Ultra K17 (TY7151) CMSA Sprinkler
70Class IIDouble Row Rack(FM)
71New changes to NFPA 13 (2007) for Rack Storage of
Class I - IV Commodities Over 7.6 m (25 ft)
72FM Approved for the Protection of Class II
Commodities up to 10.5 m (35 ft) high
- Commodity Hazard Class 1 and 2 in closed-top
non-plastic or noncombustible containers - Maximum Storage Height 35 ft (10.5 m)
- Maximum Building Height 40 ft (12.2 m)
- Storage Arrangement Solid-Piled, Palletized,
Shelf, Bin-Box, as well as Open-Framed
Single-Row, Double-Row and Multiple-Row Racks - Sprinkler System Type Dry
- Maximum Water Delivery Time 30 seconds upon
operation of first sprinkler - System Design 25 AS _at_ 22 psi (1.5 bar) plus 500
gpm (1,900 l/min) hose allowance - The 30 second delivery time needs to be confirmed
via an analysis by Engineering Hazards or by a
software program that is listed in the
Specification Tested Product section of the FM
Global - Approval Guide. If confirmed by a listed software
program, the sprinkler operation sequence should
be based on the simultaneous opening of the most
remote 4 sprinklers (2 sprinklers on 2 lines).
73Class III Free Burn Sprinkler Activation Time
74(No Transcript)
75Class II Testing UL (Multiple Row)
76(No Transcript)
77Class III Testing
78The key is predicting water transit time
79How can I use this New Technology if its not
Referenced in NFPA 13?
- NFPA 132002 Section 1.5 1.6
- Equivalency.
- Nothing in this standard is intended to prevent
the use of systems, methods, or devices of
equivalent or superior quality, strength, fire
resistance, effectiveness, durability, and safety
over those prescribed by this standard. - Technical documentation shall be submitted to the
authority having jurisdiction to demonstrate
equivalency. - The system, method, or device shall be approved
for the intended purpose by the authority having
jurisdiction. - New Technology.
- Nothing in this standard shall be intended to
restrict new technologies or alternate
arrangements, provided the level of safety
prescribed by this standard is not lowered.
80How does the Building Code deal with New
Technology?
- IFC(2003) 104.9 Alternate materials methods
- The provisions of this code are not intended to
prevent the installation of any material or to
prohibit any method of construction not
specifically prescribed by this code, provided
that any such alternative has been approved. - The fire code official is authorized to approve
an alternative material or method of construction
where the fire code official finds that the
proposed design is satisfactory and complies with
the intent of the provisions of this code, and
that the material, method or work offered is, for
the purpose intended, at least the equivalent of
that prescribed in this code in quality,
strength, effectiveness, fire resistance,
durability and safety.
81Why Choose an ESFR?
14 (200) 16.8 (240) K ESFRs 40 (12,2 m)
Build. 35 (10,7 m) Stor. ESFR-1 75 psi (5,17
bar) ESFR-17 52 psi (3,59 bar)
25.2 (360) K ESFRs 45 (13,7 m) Build. 40 (12,2
m) Stor. 40 psi (2,76 bar)
16.8 (240) K Spray Sprinkler 30 (9.1m)
Building 20 (6.1m) Storage .8 gpm/ft2 (32.6
mm/min)
11.2 (160) 14 (200) K Spray Sprinklers 27
(8.2m) Building 20 (6.1m) Storage .6 gpm/ft2
(24.5 mm/min)
82Suppression Mode Sprinklers
- Sprinkler Type
- 14.0 (200) K Up Pend
- 16.8 (240) K Up Pend
- 22.4 (326) K Pend
- 25.2 (360) K Pend
- Max Area of Coverage
- 100 sq.ft. (9.3 m2)
- Max Distance Between Sprinklers
- 12 (3.7m) 30 (9.1m) Building
- 10 (3.01m) gt30 (9.1m) Building
- Design
- Calculate a specific of sprinklers at a
specific pressure
83ESFR Pendent - 14.0 (200) K-factor Class I IV
Cartoned Uncartoned (Exposed) Group A
Unexpanded plastics
13,7 m (45) Building 12,2 m (40) Storage 6,2
bar (90 psi) 1 Level of in-rack sprinklers
12,2 m (40) Building 10,7 m (35) Storage 5,1
bar (75 psi)
9,75 m (32) Building 7,62 m (25) Storage 4,1
bar (60 psi)
30 (9,14m) Building 7,62 m (25) Storage 3,4 bar
(50 psi)
84ESFR (14K) Pendent
85ESFR Pendent - 14.0 (200) K-factor
Uncartoned (Exposed) expanded Group A plastics FM
Only 9,14 m (30) Building 7,62 m (25)
Storage 6,8 bar (100 psi)
Cartoned expanded Group A plastics 9,75 m (32)
Building 7,62 m (25) Storage 4,1 bar (60 psi)
Uncartoned (Exposed) expanded Group A plastics FM
Only 7,62 m (25) Building 6,1 m (20)
Storage 5,1 bar (75 psi)
Cartoned expanded Group A plastics 9,14 m (30)
Building 7,62 m (25) Storage 3,4 bar (50 psi)
86ESFR-17 Pendent - 16.8 (240) K-factorClass I
IV Cartoned Uncartoned (Exposed) Group A
Unexpanded plastics
13,7 m (45) Building 12,2 m (40) Storage 4,3
bar (63 psi) 1 Level of in-rack sprinklers
12,2 m (40) Building 10,7 m (35) Storage 3,6
bar (52 psi)
9,75 m (32) Building 7,62 m (25) Storage 2,9
bar (42 psi)
9,14 m (30) Building 7,62 m (25) Storage 2,4
bar (35 psi)
87Obstructions to Sprinkler Discharge -
Obstructions at or Near the Ceiling (FM)
88(No Transcript)
89ESFR Upright - 14.0 (200) K-factorClass I IV
Cartoned Uncartoned (Exposed) Group A
Unexpanded plastics
10,7 m (35) Building 9,14 m (30) Storage 5,1
bar (75 psi)
9,75 m (32) Building 7,62 m (25) Storage 4,1
bar (60 psi)
9,14 m (30) Building 7,62 m (25) Storage 3,4
bar (50 psi)
90ESFR Upright - 16.8 (240) K-factorClass I IV
Cartoned Uncartoned (Exposed) Group A
Unexpanded plastics
10,7 m (35) Building 9,14 m (30) Storage 3,6
bar (52 psi)
9,75 m (32) Building 7,62 m (25) Storage 2,9
bar (42 psi)
9,14 m (30) Building 7,62 m (25) Storage 2,4
bar (35 psi)
91ESFR (K17) Upright
92ESFR-17 UprightFM Obstruction Criteria
- When FM Research Approved upright suppression
mode sprinklers are used obstructions below
sprinklers can be ignored if - They are open-web bar joists or trusses having
chords no more than 102 mm (4) wide, or - They are bridging or wind bracing no more than
102 mm (4) wide, or
93ESFR-17 UprightFM Obstruction Criteria
- They are individual pipes conduit 102 mm (4)
in diameter or less, or - individual groups of smaller pipe or conduit
having a total width of 102 mm (4) or less.
94ESFR Pendent - 22.4 (326) K-factor Class I IV
Cartoned Uncartoned (Exposed) Group A
Unexpanded plastics
13,7 m (45) Building 12,2 m (40) Storage 2,7
bar (40 psi)
12,2 m (40) Building 10,7 m (35) Storage 2,7
bar (40 psi)
10,7 m (35) Building 9,14 m (30) Storage 2,4
bar (35 psi)
9,14 m (30) Building 7,62 m (25) Storage 1,7
bar (25 psi)
95ESFR Pendent - 25.2 (360) K-factor Class I IV
Cartoned Uncartoned (Exposed) Group A
Unexpanded plastics
New Testing at FM on Cartoned Expanded and
Exposed Expanded
13,7 m (45) Building 12,2 m (40) Storage 2,7
bar (40 psi)
12,2 m (40) Building 10,7 m (35) Storage 1,7
bar (25 psi)
10,7 m (35) Building 9,14 m (30) Storage 1,4
bar (20 psi)
9,14 m (30) Building 7,62 m (25) Storage 1,0
bar (15 psi)
96ESFR (25K) Pendent
97Ceiling only protection criteria for Rack Storage
of Cartoned Group A Plastics
98Retail Fire Research Coalition
99Self Storage
- Shelf Storage. Storage on structures less than
30 (76.2 cm) deep with shelves usually 2 (0.6
m) apart vertically and separated by
approximately 30 (76.2-cm) aisles.
100Solid Shelving
- Fixed in place, slatted, wire mesh or other type
of shelves located within racks. - The area of a solid shelf is defined by perimeter
aisle or flue space on all four sides. - Solid shelves having an area equal to or less
than 20 sq. ft. are open racks. - Shelves of wire mesh, slates, or other materials
more than 50 open, where the flue spaces are
maintained are open racks.
101Storage on Solid Shelving
- Where the area of the solid shelving is less than
20 ft2 - In-rack sprinklers are not required
- Where the area of solid shelving is 20 - 64 ft2
- In-rack sprinklers are not required below every
shelf - In-rack sprinklers shall be installed at the
ceiling below shelves at intermediate levels
not more than 6 ft apart vertically. - Where the area of solid shelving is greater than
64 ft2 - In-rack sprinklers shall be installed at the
ceiling below each level of shelving.
102The Home Depot (20.3.1)
- Max. Storage height 22 (6.7 m)
- Max. Ceiling height 30 (9.1 m)
- Design (EC-25 sprinklers only)
- 0.6 gpm/ft2 - 2000 ft2 (24.5mm/min-186m2)
- 0.7 gpm/ft2 (28.5mm/min) for the four most
demanding sprinklers - Min. aisle width 8 (2.4 m)
- Storage in aisle permissible where aisle storage
is 4 (1.2) or less high min. clear aisle of 4
(1.2) is maintained. - Slatted shelves using 2x6 slats with spacers
maintaining a min. 2 (51 mm) opening between
each slat. - No slatted shelf levels in the rack above 12
(3.7 m) level. - Wire mesh over 50 open permitted for shelf
levels above 12 (3.7 m).
- Solid shelving 3.58.25 (1.1mx2.5m) allowed
over slats at 5 (1.5m) level. - Perforated metal over 40 open allowed over slats
to 60 (1.5m) level. - Solid veneered displays allowed when all flues
are maintained only one display is installed
per bay. Other solid plywood or similar
materials shall not be placed on the slatted
shelves. - Min. 6 (162mm)long. flue 3 (76mm) tran. flue
at rack uprights
103Wal-Mart (20.3.2)
- Max. Storage height 12 (3.7 m) on gondola
shelving with metal shelves - Max. Ceiling height 22 (6.7 m)
- Design (EC-25 sprinklers only)
- 0.425 gpm/ft2 / 2000 ft2 (17.3mm/min-186m2)
- 0.5 gpm/ft2 (20.4 mm/min) for the four most
demanding sprinklers - Min. aisle width 5 (1.5 m)
- Gondola structure does not exceed 48 (1.2 m)
aggregate depth, or 78 (2 m) height - Max. Rack length 70 (21.3 m)
104Best Buy (20.3.3)
- Max. Storage height 15 (4.6 m) on gondola
shelving with metal shelves - Max. Ceiling height 25 (7.6 m)
- Design (EC-25 sprinklers only)
- 0.425 gpm/ft2 / 2000 ft2 (17.3mm/min-186m2)
- 0.5 gpm/ft2 (20.4 mm/min) for the four most
demanding sprinklers - Min. aisle width 6 (1.8 m)
- Gondola rack structure shall not exceed 60 (1.5
m) aggregate depth or 8 (2.4m) height. - A perforated metal deck at 8 (2.4m) level
permissible with storage placed on top with or
without flue spaces to a max. height from floor
of 15 (4.6 m) - Max. Rack length 70 (21.3 m)
105Target Stock Room (20.3.4)
- Max. Storage height 15 (4.6 m)
- Max. Ceiling height 20.5 (6.3 m)
- Design (EC-25 sprinklers only)
- 0.45 gpm/ft2 / 2000 ft2 (18.3mm/min-186m2)
- 0.55 gpm/ft2 (22.4 mm/min) for the four most
demanding sprinklers - Min. aisle width 3 (0.9 m)
- Shelving structure shall not exceed 48 (1.2 m)
aggregate depth or 12 (3.7 m) height. - Shelving shall be permitted to be made of solid
particleboard. - Max. Rack length 70 (21.3 m)
106Office Depot (20.3.5)
- Max. Storage height 14 (4.3 m)
- Max. Ceiling height 20 (6.1 m)
- Design (EC-25 sprinklers only)
- 0.38 gpm/ft2 / 2000 ft2 (15.5mm/min-186m2)
- 0.45 gpm/ft2 (18.3mm/min ) for the four most
demanding sprinklers - Min. aisle width 5 (1.5 m)
- Solid metal shelving permissible up to the 72
(1.8 m) level wire shelving shall be
permissible up to the 10 (3.1 m) level. - The solid metal shelving shall not exceed 66
(1.7 m) aggregate depth and shall have a min. 6
(150 mm) longitudinal flue between two 30 (762
mm) deep shelves. - Max. Rack length 70 (21.3 m)
107Bed Bath Beyond (20.3.6)
- Max. Storage height 16.5 (5.0 m)
- Max. Ceiling height 22 (6.7 m)
- Design (EC-25 sprinklers only)
- 0.49 gpm/ft2 / 2000 ft2 (20.0mm/min-186m2)
- 0.55 gpm/ft2 (22.4 mm/min) for the four most
demanding sprinklers - Min. aisle width 4 (1.2 m) between shelf units
and other displays - Shelving structure shall not exceed 51 (1.3 m)
aggregate depth or 148 (3.8 m) height. - The intersection of perpendicular steel racks
shall be permissible as long as no storage is
placed within the void space at the junction of
the racks. - The top shelf shall be wire mesh.
108Thank you for your participation
- To our customers We would like your feedback on
today's session to help improve future
presentations. Please take a moment to complete
the survey (included in your information packet)
and return to the room monitor. - Risk Engineering staff will receive an electronic
evaluation in the next few days via e-mail - Conference presentations are available for
download at - www.zurichservices.com
109Thank You