Title: Infiltration/Ventilation
1Infiltration/Ventilation
- HVAC 7a
- CNST 305
- Environmental Systems 1
- Dr. Berryman
2Infiltration
Types of heat losses?
Types of heat gains?
3Calculating Infiltration
- Crack method
- Air change method
- Effective leakage-area method
Sensible BH 1.08 x ?T x CFM Latent BH 0.68 x
?G x CFM
Equations w/ Air Constants
4Air Crack Method
Divide by 60 min for CFM
Lower pressure differentials mean tighter
construction
5Crack Example (winter)
BHsens 1.08 x ?T x CFM
- Given
- 3o 5o Double Hung Window
- No added humidification
- IA conditions DB75oF
- OA conditions DB-5oF
- Medium Construction
- How many BTUH are lost due to frame wall
infiltration?
1.08 x 80oF x (16LF)(21 CF/60)
EXAMPLE
484 BH
6Air Change
- Converts equation to cubic feet
- Equals one room change
- Designer will use 0.3 to 2.0 room changes per
hour - Occupancy
- Climatic condition (i.e. winter vs. summer)
- Construction (tight or loose)
- Least accurate of the three methods
7Air Change Example
- Given
- 20 x 60 x 10 room
- Winter - 0.35 RCH
- No added humidification
- IA conditions DB75oF
- OA conditions DB-5oF
- How many BTUH lost due to infiltration?
EXAMPLE
BHsens 6,048
8Ventilation
FA
200 CFM
SA
1600 CFM
RA
pressure
1400 CFM
9Calculating Ventilation
- CFM per Person
- Use ASHARE chart
- Room Air Change per Hour
- 0.5 2.0 RCH
10Determining Ventilation Requirements
- Determinates
- Building Application
- Occupants
11Ventilation - CFM per Person
- Given
- 2000 SF Coin Operated Laundry
- Winter design
- No added humidification
- IA conditions DB75oF
- OA conditions DB-5oF
- How many BTUH lost due to ventilation?
BHsens 1.08 x ?T x CFM
EXAMPLE
(1.08)(80oF)(15cfm)(40 people)
BHsens 51,840
12Ventilation - Room Change
- Given
- 2000 SF Coin Operated Laundry - 10 walls
- Winter design 2.0 RCH
- No added humidification
- IA conditions DB75oF
- OA conditions DB-5oF
How many BTUH lost due to ventilation?
BHsens 57,600
13Summer Conditions- CFM per Person
- Given
- 2000 SF Coin Operated Laundry
- 15 CFM/person summer
- IA conditions DB75oF 40RH
- OA conditions DB 95oF WB80oF
- How many BTUH gained due to ventilation?
BHsens 1.08 x ?T x CFM
(1.08)(20oF)(15cfm)(40 people)
BHsens 12,960
BHlat 0.68 x ?G x CFM
(0.68)(80g)(15cfm)(40 people)
BHlat 32,640
BHsummer 45,600
14In Class
Summer Conditions- Room Change
- Given
- 2000 SF Coin Operated Laundry 10 walls
- 1.5 RCH
- IA conditions DB75oF 40RH
- OA conditions DB 95oF WB80oF
- How many BTUH gained due to ventilation?
15Next Time
- Heat Gains
- Chapter 2.6 2.8 (Toa)