Title: Design Criteria for LP BYPASS SYSTEM


1
Design Criteria forLP BYPASS SYSTEM
2
LP Bypass system provide a very effective means
of controlling reheat steam flow during
  • Startup
  • Low-load / part load operation
  • Sudden load rejection

3
It enhances fast starting capability of turbines
from all initial conditions e.g.
  • Cold condition
  • Warm condition
  • Hot Condition

4
LP steam-bypass system operate in parallel with
the turbine
  • Protect Condenser from excessive temperature and
    pressure that could result from sudden injection
    of superheated steam

5
  • Ensure coordinated control between HP and IP
    turbine control valves and the steam bypass
    systems to operate at any remaining load
  • Subsequently reloaded in a controlled manner

6
Schematic Diagram of Bypass System
7
  • The controls for LP Bypass system are combination
    of electrical and well proven hydraulic system
  • Electro-hydraulic converter provides the
    necessary link between hydraulic actuator and
    electrical system

8
  • The LPBypass Controller acts as a maximum
    pressure Controller
  • It regulates the reheater pressure either to the
    fixed set value or suitably derived variable set
    value
  • If the reheater pressure exceeds this set value,
    the Controller causes the electro-hydraulic
    converter to operate and initiate bypass operation

9
Set Value formation
  • The Two set values fixed and variable are
    formed for the LPBypass control system
  • set value to be used is determined by a maximum
    value selector
  • For the formation of variable set point, a
    pressure transducer is used to measure the steam
    pressure in HP turbine

10
SEQUENCE OF EVENTS RESULTING FROM LOAD REJECTION
  • Upon receiving load rejection signal from
    electrical system
  • Turbine Speed Controller assumes control of the
    TG set
  • It initiates fast closure of HP IP turbine
    control valves through position controller
  • Fast closure of turbine control valves cause an
    immediate decrease in HP 1st. Stage pressure

11
SEQUENCE OF EVENTS RESULTING FROM LOAD REJECTION
  • Pressure increases in main and reheat steam
    systems
  • These pressure changes are sensed by HP and LP
    Bypass controllers
  • Respective bypass valves are opened

12
  • If LP steam- bypass system fails or the
    condenser cannot accept LP bypass steam , Safety
    Valves open and dump steam to atmosphere

13
Hydraulic Mode of Operation
  • The controller controls plunger coil of Electro
    Hydraulic Converter
  • With increase in voltage, the jet pipe is
    deflected towards right
  • Converter piston moves downwards leading to
    generation of LPB signal oil through Follow-up
    pistons provided in the hydraulic control system

14
Hydraulic Mode of Operation
  • Two Follow-up Pistons actuate and open first
    stage of water injection valve
  • Remaining two Follow-up Pistons generate signal
    oil for opening LPBypass stop and control valve

15
  • ADJUSTMENT
  • OF
  • LPBYPASS
  • CONVERTER

16
Design of LPBypass Valves for 210 MW Steam Turbine
  • Controlled by 8 bar mineral oil

17
Design of LPBypass Valve for 500 MW Steam Turbine
  • Controlled by 36 bar FRF

18
Protection Devices
  • Low Vacuum Condensor Protection
  • Spray Water Pressure Switch
  • Condensor Temperature Protection

19
Protection Devices cause closure of bypass
station in case of following eventualities
  • Condensor vacuum is low ( gt 0.6 bar absolute )
  • Spray water pressure is low (lt 8.5 / 9.5 bar )
  • Temperature of condenser body is high (gt 90 C )

20
Water Injection Valves operate in two stages
  • Second stage Water Injection Valves open when
    steam flow through LPBypass Valves increases more
    than 45

21
CURVE FOR LPBYPASS CONTROLLER
22
  • Damping device

23
(No Transcript)
24
(No Transcript)
25
(No Transcript)