Title: CABLE FAULT ANALYSIS BY


1
CABLE FAULT ANALYSIS BY
  • UTMANCO SYSTEMS (P) LTD

2
What is a Fault ?
  • DEFECTWEAKNESSINCONSISTENCYOR NON-
    HOMOGENEITYTHAT AFFECTS THEPERFORMANCE OF THE
    CABLE

3
COMMON TYPES OF FAULT
  • CONTACT FAULTS (SHORT CIRCUIT FAULTS)
  • BREAKS (OPEN CIRCUIT FAULT)

4
CONTACT FAULT
  • A connection or part connection between one core
    (conductor) and another or others or between
    core(s) and the metallic sheath.
  • Value of fault resistance varies between zero
    ohms and many megohms.

5
BREAK FAULT
  • (OPEN CIRCUIT OR SERIES FAULT)
  • CLEAN BREAK IN CONDUCTOR
  • DIRTY BREAK
  • PARTIAL BREAK

6
CORRECT APPROACH TO CABLE FAULT LOCATION
  • DIAGNOSIS
  • PRE-CONDITIONING
  • PRE-LOCATION
  • PIN-POINTING

7
DIAGNOSIS
  1. Find out type of cable,length,time in service,
    how the fault occurred, protection operation etc.
  2. Ensure both ends of the cable are disconnected
  3. Test the insulation resistance between all
    conductors and sheath
  4. Use an analog multimeter (avo) to measure the
    value of the fault resistance.
  5. Check the continuity of all cores with the avo.

8
PRE-CONDITIONING
  • It may be necessary to alter the fault
    characteristics from a high resistance to low
    resistance or from an unstable flashing condition
    to a stable resistive fault
  • How?
  • Passing current through the fault to carbonise
    insulation (fault burner)
  • Re-energising cable
  • Leaving the cable dead for sufficient time to
    allow moisture to penetrate.

9
PRE-LOCATION
  • To determine the distance to fault either
    as a percentage of cable length or directly in
    units of distance.
  • Utmanco offers two equipment for
    pre-location
  • Pulse echo tester
  • Digital cable fault locator.

10
PIN-POINTING
  • Positively confirms the exact position
    of fault
  • 1. Test cable from both ends with cable fault
    locator . if the two readings add up to give the
    total length of cable, then the location of fault
    is confirmed.
  • 2. Excavate cable at the distance obtained
    perhaps 3 metres on either side of fault
    position. Connect 230v phase to faulty core. Use
    utmanco non-contact voltage detector to detect
    voltage leakage point on the exposed cable to
    pin-point fault.