Tri-Tech Medical - PowerPoint PPT Presentation

1 / 22
About This Presentation
Title:

Tri-Tech Medical

Description:

Tri-Tech Medical Medical Gas Alarm Panel Conversion Kits Why convert? Present alarm is not NFPA compliant Present alarm is not functioning properly and ... – PowerPoint PPT presentation

Number of Views:119
Avg rating:3.0/5.0
Slides: 23
Provided by: JimL78
Category:

less

Transcript and Presenter's Notes

Title: Tri-Tech Medical


1
Tri-Tech Medical
  • Medical Gas Alarm Panel
  • Conversion Kits

2
Why convert?
  • Present alarm is not NFPA compliant
  • Present alarm is not functioning properly and
    replacement / repair parts are not available
  • Received notice years ago from Hill-Rom about an
    alarm that can overheat and smoke or flame, and
    finally have money allocated to do something
    about it

3
Why convert?
  • Need to add gases to a zone of the hospital, and
    present alarm cannot be expanded
  • Need to link source alarm signals to Building
    Management System, and present alarm cannot
    provide that
  • Need to set up PC based interfacing of hospital
    alarm systems, and present alarms cannot provide
    that
  • Need to utilize existing alarm back box and
    allocated space to make any upgrades

4
Tri-Tech DU/DC Series Alarm Conversions
  • Area Alarms
  • Master Alarms
  • Combination Alarms
  • Convert from most major brands, including Ohio
    Medical, Chemetron, Amico, and both Tri-Tech
    older versions
  • Get a fully functioning, NFPA compliant,
    state-of-the-art Tri-Tech DU/DC series alarm

5
Conversion processDetermine sizing/configuration
of alarm to be converted
  • Determine make, model, number of area modules and
    master signals of old alarm
  • Measure alarm panel - dimensions of back box and
    front panel
  • Know how the converted alarm should be configured
  • More or different area alarm gas modules?
  • More master alarm signals?
  • Combination alarm?
  • Building management interface?
  • TNET?

6
Conversion processChoose the Tri-Tech
conversion that best fits the need
  • Three different standard sizes of Tri-Tech alarm
    panels, with corresponding number of area alarm
    and master alarm modules
  • 2 slot
  • 3 slot
  • 5 slot
  • Three different standard sizes of sub-mounting
    plates that correspond with those three sizes
  • Choose Tri-Tech conversion alarm panel
  • Unusual sizing? Standard conversion might still
    work!
  • Customized conversions and trim pieces are
    possible.
  • Call Tri-Tech for assistance.

7
Conversion processChoose the Tri-Tech
conversion that best fits the need
  • 2 slot sub-mounting plate
  • 3 slot sub-mounting plate
  • 5 slot sub-mounting plate

8
Conversion processDisconnect/Remove existing
components
  • Shut off and disconnect electrical power to the
    alarm
  • For Area Alarm, locate zone valves that provide
    gas to the alarm transducers, and shut off gas
    service
  • If Tri-Tech AU/AC series alarm, no need to shut
    off power or gas
  • We have made some live Area Alarm conversion
    kits that would not require shutting down the gas
    services, but this should be considered only when
    absolutely necessary
  • Label each Area Alarm transducer location with
    gas service!
  • Locate and remove existing Area Alarm
    transducers. Remove all non-DISS gas specific
    demand valve couplings.

9
Conversion processDisconnect/Remove existing
components.
  • Disconnect and remove existing power supply
  • If Tri-Tech AU/AC series, do not remove the power
    supply
  • Remove existing front panel
  • If existing front panel houses signal wiring for
    Master Alarm, label/record all source wire
    positions

10
Conversion processInstall Tri-Tech Transducers
with connectors
  • Included in all Area Alarm conversions are parts
    needed to properly install Tri-Tech transducers
  • Couplers for DISS demand checks
  • 90 transducer connections
  • If using a coupler, make sure gas service matches
    DISS demand check valve - gas ID is stamped on
    DISS demand check valve
  • If transducers are mounted remotely, follow
    Appendix A of DU/DC Medical Gas Alarm
    installation manual

11
Conversion processInstall Mounting Flange with
power supply
  • Power supply comes pre-installed on the flange of
    the sub-mounting plate, but can be moved to
    different sides of sub-mounting plate
  • As long as power supply fits in back box with
    transducers, sub-mounting plate/conversion alarm
    can be positioned as needed
  • With conversion from Tri-Tech AU/AC series
    alarms, use existing power supply and no
    sub-mounting plate needed
  • Position and install sub-mounting plate with
    power supply over back box
  • Mark 4 drill holes
  • Make sure no utility services behind
  • Make sure it is level
  • Drill holes
  • With provided mollie bolts, install sub-mounting
    plate
  • Connect the three wires from the power supply to
    the 110 VAC supply wires using wire nuts

12
Conversion processInstall Tri-Tech Medical
alarm front panel
  • Insert new front panel over the two hinges and
    attached lanyards to the flange screw mounts
  • Carefully connect CPU wiring harness, making sure
    it is properly aligned
  • Attach the grounding wires

13
Conversion processConnect transducer and/or
remote signal wires
  • Install the two wires from each transducer to the
    labeled BLK and WHT sensor slots
  • Install existing master signal wires into the NC
    labeled positions and the common wires into the C
    labeled positions. Follow same order as old panel
    had
  • If old master boards had been in back box, move
    wires from old points to new alarm connector
    points, and then remove old master boards

14
Complete the installation
  • Label the front panel as needed
  • Restore electrical power and medical gases to the
    alarm panel
  • Make sure fuse is installed on the power supply
    and turn alarm on
  • Program if necessary
  • Area Alarm modules come pre-programmed
  • Master alarm points are programmed normally
    closed and all signals active
  • Test functioning and cross-connections

15
Completed conversion
16
Troubleshooting tips
  • The alarm you need to convert is not shown in our
    catalog page
  • - Chances are Tri-Tech has a conversion that
    will work
  • - Compare the back box dimensions with the
    sub-mounting plates
  • - Know your riser connections
  • - Send us pictures
  • The conversion needs to fit in a very tight /
    limited space
  • - Tri-Tech conversion provides different
    mounting options
  • - Power supply can be positioned in different
    positions on the sub-mounting plate
  • - Sub-mounting plate can be positioned
    anywhere over the back box
  • The existing alarm has a large or a very small
    back box
  • - Additional backing plate can be installed
    behind the sub-mounting plate to cover over
    the existing alarm back box cavity
  • - It might be possible to cut out some wall to
    house the power supply, and transducers
    could still fit or could be mounted remotely.
    Unique accommodations are possible.
  • Transducers mounted remotely, or cannot be
    accessed
  • - Tri-Tech transducers can be mounted remotely
    and wired to the conversion panel
  • - New construction transducers can be supplied
    with risers to mount in the pipeline
  • When in doubt, call us or send us pictures
  • - Pictures tell a thousand words
  • - We are a knowledgeable bunch here at
    Tri-Tech

17
NFPA 5.1.9 Level 1 Warning Systems
  • All master, area local alarm systems used for
    medical gas vacuum systems shall include the
    following
  • Separate visual indicators for each condition
    monitored (except as permitted in 5.1.9.5.2)
  • Visual indicators that remain in alarm until the
    situation that had caused the alarm is resolved
  • A cancelable audible indication of each alarm
    condition that produces a sound with a minimum of
    80 dBA _at_ 3 ft
  • A means to visually indicate a lamp or LED
    failure
  • Visual audible indication that the wiring to an
    alarm initiating device is disconnected
  • Labeling of each indicator, indicating the
    condition monitored
  • Labeling of each alarm panel for its area of
    surveillance
  • Re-initiation of the audible signal if another
    alarm condition occurs while the audible alarm is
    silenced
  • Powered by the Life Safety branch of the
    emergency electrical system
  • Power for local alarms, dew point sensors, CO
    sensors permitted to be from the same essential
    electrical branch as is used to power the air
    compressor
  • Wiring from switches or sensors that is
    supervised or protected as required by Sect
    517.30 (C) (3) of NFPA 70
  • Assurance by the responsible authority of the
    facility that the labeling of the alarms, where
    room s or designations are used, is accurate
    up-to-date
  • Provisions for automatic restart after a power
    loss of 10 seconds without giving false signals
    or requiring manual reset

18
NFPA 5.1.9.3 Area Alarms
  • Area alarm panels shall be provided to monitor
    all medical gas, medical-surgical vacuum, and
    piped WAGD systems supplying anesthetizing
    locations, and other vital life support and
    critical areas
  • 5.1.9.3.1 Area alarms shall be located at a
    nurses station or other similar location that
    will provide for surveillance
  • 5.1.9.3.2 Area alarm panels for medical gas
    systems shall indicate if the pressure in the
    lines in the area being monitored increases or
    decreases by 20 from the normal line pressure
  • 5.1.9.3.3 Area alarm panels for medical-surgical
    vacuum systems shall indicate if the vacuum in
    the area drops to or below 300 mm (12 in Hg)
  • 5.1.9.3.4 Sensors for area alarms shall be
    located as follows
  • Vital life support critical areas shall have
    the alarm sensors installed on the patient or use
    side of any of the individual zone valve box
    assemblies
  • Areas for anesthetizing gas delivery shall have
    the sensors installed either on the source side
    of any of the individual room zone valve box
    assemblies or on the patient or use side of each
    of the individual zone valve assemblies
  • The placement of the sensors shall not be
    affected by valves located in areas accessible to
    authorized personnel only, such as service valves

19
NFPA 5.1.9.2 Master Alarms
  • A master alarm system shall be provided to
    monitor the operation and condition of the source
    supply, the reserve source, and the pressure in
    the main lines of each medical gas vacuum
    piping system
  • The master alarm system shall consist of two or
    more alarm panels located in at least two
    separate locations as follows
  • One master alarm panel shall be located in the
    office or work space of the on-site individual
    responsible for the maintenance of the medical
    gas vacuum systems
  • The second master alarm panel shall be located in
    an area of continuous observation
  • 5.1.9.2.2 A centralized computer system shall be
    permitted to be substituted for one of the master
    alarms, if it complies with 5.1.9.4
  • 5.1.9.2.3 The master alarm panels shall connect
    directly to the alarm devices they monitor
  • 5.1.9.2.3.1 Master alarm signals shall not be
    relayed from one master alarm panel to another
  • 5.1.9.2.3.2 Where multi-pole alarm relays are
    used to isolate the alarm initiating signals to
    master alarm panels, the control power source for
    the relays shall be independent of any of the
    master alarm panels
  • 5.1.9.2.3.3 Multiple master alarms shall be
    permitted to monitor a single initiating device

20
NFPA 5.1.9.2 Master Alarms
  • 5.1.9.2.4 Master alarm panels for medical gas
    vacuum systems shall each include the following
    signals
  • An alarm condition when or just before changeover
    occurs in a medical gas system that is supplied
    by a manifold or other alternating-type bulk
    system that has as a part of its normal operation
    a changeover from one portion of the operating
    supply to another
  • An alarm indication for a bulk cryogenic liquid
    system when the main supply reaches an average
    days supply, indicating low contents
  • An alarm indication when or just before the
    changeover to the reserve supply occurs in a
    medical gas system that consists of one or more
    units that continuously supply the piping system
    while another unit remains as the reserve supply
    operates only in the case of an emergency
  • An alarm indication for cylinder reserve pressure
    low when the content of a cylinder reserve header
    is reduced below one days supply
  • For bulk cryogenic liquid systems, an alarm when
    or at a predetermined set point before the
    reserve supply contents fall to one days average
    supply, indicating reserve low
  • Where a cryogenic liquid storage is used as a
    reserve for a bulk supply system, an alarm
    indication when the gas pressure available in the
    reserve unit is below that required for the
    medical gas system to function
  • An alarm indication when the pressure in the main
    line of each separate medical gas system
    increases 20 or decreases 20 from the normal
    operating pressure

21
NFPA 5.1.9.2 Master Alarms
  • 5.1.9.2.4 Master alarm panels for medical gas
    vacuum systems shall each include the following
    signals
  • An alarm indication when the medical-surgical
    vacuum pressure in the main line of each vacuum
    system drops to or below 300 mm (12 inHg)
  • An alarm indication(s) from the local alarm
    panel(s) as described in 5.1.9.5.2 to indicate
    when one or more of the conditions being
    monitored at a site is in alarm
  • A medical air dew point high alarm from each
    compressor site to indicate when the line
    pressure dew point is greater than 2 C (35
    F)
  • A WAGD low alarm when the WAGD vacuum level or
    flow is below effective operating limits
  • An instrument air dew point high alarm from each
    compressor site to indicate when the line
    pressure dew point is greater than -30C (-22F)
  • 5.1.9.2.5 The alarm indications required in
    5.1.9.2.4(7) and 5.1.9.2.4(8) shall originate
    from sensors installed in the main lines
    immediately downstream of the source valves.
    Where it is necessary to install a main line
    valve in addition to a source valve, the sensors
    shall be located downstream of the main valve.

22
Thank-you!
Write a Comment
User Comments (0)
About PowerShow.com