Title: Tri-Tech Medical
1Tri-Tech Medical
- Medical Gas Alarm Panel
- Conversion Kits
2Why convert?
- Present alarm is not NFPA compliant
- Present alarm is not functioning properly and
replacement / repair parts are not available - Received notice years ago from Hill-Rom about an
alarm that can overheat and smoke or flame, and
finally have money allocated to do something
about it
3Why convert?
- Need to add gases to a zone of the hospital, and
present alarm cannot be expanded - Need to link source alarm signals to Building
Management System, and present alarm cannot
provide that - Need to set up PC based interfacing of hospital
alarm systems, and present alarms cannot provide
that - Need to utilize existing alarm back box and
allocated space to make any upgrades
4Tri-Tech DU/DC Series Alarm Conversions
- Area Alarms
- Master Alarms
- Combination Alarms
- Convert from most major brands, including Ohio
Medical, Chemetron, Amico, and both Tri-Tech
older versions - Get a fully functioning, NFPA compliant,
state-of-the-art Tri-Tech DU/DC series alarm
5Conversion processDetermine sizing/configuration
of alarm to be converted
- Determine make, model, number of area modules and
master signals of old alarm - Measure alarm panel - dimensions of back box and
front panel - Know how the converted alarm should be configured
- More or different area alarm gas modules?
- More master alarm signals?
- Combination alarm?
- Building management interface?
- TNET?
6Conversion processChoose the Tri-Tech
conversion that best fits the need
- Three different standard sizes of Tri-Tech alarm
panels, with corresponding number of area alarm
and master alarm modules - 2 slot
- 3 slot
- 5 slot
- Three different standard sizes of sub-mounting
plates that correspond with those three sizes - Choose Tri-Tech conversion alarm panel
- Unusual sizing? Standard conversion might still
work! - Customized conversions and trim pieces are
possible. - Call Tri-Tech for assistance.
7Conversion processChoose the Tri-Tech
conversion that best fits the need
- 2 slot sub-mounting plate
- 3 slot sub-mounting plate
- 5 slot sub-mounting plate
8Conversion processDisconnect/Remove existing
components
- Shut off and disconnect electrical power to the
alarm - For Area Alarm, locate zone valves that provide
gas to the alarm transducers, and shut off gas
service - If Tri-Tech AU/AC series alarm, no need to shut
off power or gas - We have made some live Area Alarm conversion
kits that would not require shutting down the gas
services, but this should be considered only when
absolutely necessary - Label each Area Alarm transducer location with
gas service! - Locate and remove existing Area Alarm
transducers. Remove all non-DISS gas specific
demand valve couplings.
9Conversion processDisconnect/Remove existing
components.
- Disconnect and remove existing power supply
- If Tri-Tech AU/AC series, do not remove the power
supply - Remove existing front panel
- If existing front panel houses signal wiring for
Master Alarm, label/record all source wire
positions
10Conversion processInstall Tri-Tech Transducers
with connectors
- Included in all Area Alarm conversions are parts
needed to properly install Tri-Tech transducers - Couplers for DISS demand checks
- 90 transducer connections
- If using a coupler, make sure gas service matches
DISS demand check valve - gas ID is stamped on
DISS demand check valve - If transducers are mounted remotely, follow
Appendix A of DU/DC Medical Gas Alarm
installation manual
11Conversion processInstall Mounting Flange with
power supply
- Power supply comes pre-installed on the flange of
the sub-mounting plate, but can be moved to
different sides of sub-mounting plate - As long as power supply fits in back box with
transducers, sub-mounting plate/conversion alarm
can be positioned as needed - With conversion from Tri-Tech AU/AC series
alarms, use existing power supply and no
sub-mounting plate needed - Position and install sub-mounting plate with
power supply over back box - Mark 4 drill holes
- Make sure no utility services behind
- Make sure it is level
- Drill holes
- With provided mollie bolts, install sub-mounting
plate - Connect the three wires from the power supply to
the 110 VAC supply wires using wire nuts
12Conversion processInstall Tri-Tech Medical
alarm front panel
- Insert new front panel over the two hinges and
attached lanyards to the flange screw mounts - Carefully connect CPU wiring harness, making sure
it is properly aligned - Attach the grounding wires
13Conversion processConnect transducer and/or
remote signal wires
- Install the two wires from each transducer to the
labeled BLK and WHT sensor slots - Install existing master signal wires into the NC
labeled positions and the common wires into the C
labeled positions. Follow same order as old panel
had - If old master boards had been in back box, move
wires from old points to new alarm connector
points, and then remove old master boards
14Complete the installation
- Label the front panel as needed
- Restore electrical power and medical gases to the
alarm panel - Make sure fuse is installed on the power supply
and turn alarm on - Program if necessary
- Area Alarm modules come pre-programmed
- Master alarm points are programmed normally
closed and all signals active - Test functioning and cross-connections
15Completed conversion
16Troubleshooting tips
- The alarm you need to convert is not shown in our
catalog page - - Chances are Tri-Tech has a conversion that
will work - - Compare the back box dimensions with the
sub-mounting plates - - Know your riser connections
- - Send us pictures
- The conversion needs to fit in a very tight /
limited space - - Tri-Tech conversion provides different
mounting options - - Power supply can be positioned in different
positions on the sub-mounting plate - - Sub-mounting plate can be positioned
anywhere over the back box - The existing alarm has a large or a very small
back box - - Additional backing plate can be installed
behind the sub-mounting plate to cover over
the existing alarm back box cavity - - It might be possible to cut out some wall to
house the power supply, and transducers
could still fit or could be mounted remotely.
Unique accommodations are possible. - Transducers mounted remotely, or cannot be
accessed - - Tri-Tech transducers can be mounted remotely
and wired to the conversion panel - - New construction transducers can be supplied
with risers to mount in the pipeline - When in doubt, call us or send us pictures
- - Pictures tell a thousand words
- - We are a knowledgeable bunch here at
Tri-Tech -
17NFPA 5.1.9 Level 1 Warning Systems
- All master, area local alarm systems used for
medical gas vacuum systems shall include the
following - Separate visual indicators for each condition
monitored (except as permitted in 5.1.9.5.2) - Visual indicators that remain in alarm until the
situation that had caused the alarm is resolved - A cancelable audible indication of each alarm
condition that produces a sound with a minimum of
80 dBA _at_ 3 ft - A means to visually indicate a lamp or LED
failure - Visual audible indication that the wiring to an
alarm initiating device is disconnected - Labeling of each indicator, indicating the
condition monitored - Labeling of each alarm panel for its area of
surveillance - Re-initiation of the audible signal if another
alarm condition occurs while the audible alarm is
silenced - Powered by the Life Safety branch of the
emergency electrical system - Power for local alarms, dew point sensors, CO
sensors permitted to be from the same essential
electrical branch as is used to power the air
compressor - Wiring from switches or sensors that is
supervised or protected as required by Sect
517.30 (C) (3) of NFPA 70 - Assurance by the responsible authority of the
facility that the labeling of the alarms, where
room s or designations are used, is accurate
up-to-date - Provisions for automatic restart after a power
loss of 10 seconds without giving false signals
or requiring manual reset
18NFPA 5.1.9.3 Area Alarms
- Area alarm panels shall be provided to monitor
all medical gas, medical-surgical vacuum, and
piped WAGD systems supplying anesthetizing
locations, and other vital life support and
critical areas - 5.1.9.3.1 Area alarms shall be located at a
nurses station or other similar location that
will provide for surveillance - 5.1.9.3.2 Area alarm panels for medical gas
systems shall indicate if the pressure in the
lines in the area being monitored increases or
decreases by 20 from the normal line pressure - 5.1.9.3.3 Area alarm panels for medical-surgical
vacuum systems shall indicate if the vacuum in
the area drops to or below 300 mm (12 in Hg) - 5.1.9.3.4 Sensors for area alarms shall be
located as follows - Vital life support critical areas shall have
the alarm sensors installed on the patient or use
side of any of the individual zone valve box
assemblies - Areas for anesthetizing gas delivery shall have
the sensors installed either on the source side
of any of the individual room zone valve box
assemblies or on the patient or use side of each
of the individual zone valve assemblies - The placement of the sensors shall not be
affected by valves located in areas accessible to
authorized personnel only, such as service valves
19NFPA 5.1.9.2 Master Alarms
- A master alarm system shall be provided to
monitor the operation and condition of the source
supply, the reserve source, and the pressure in
the main lines of each medical gas vacuum
piping system - The master alarm system shall consist of two or
more alarm panels located in at least two
separate locations as follows - One master alarm panel shall be located in the
office or work space of the on-site individual
responsible for the maintenance of the medical
gas vacuum systems - The second master alarm panel shall be located in
an area of continuous observation - 5.1.9.2.2 A centralized computer system shall be
permitted to be substituted for one of the master
alarms, if it complies with 5.1.9.4 - 5.1.9.2.3 The master alarm panels shall connect
directly to the alarm devices they monitor - 5.1.9.2.3.1 Master alarm signals shall not be
relayed from one master alarm panel to another - 5.1.9.2.3.2 Where multi-pole alarm relays are
used to isolate the alarm initiating signals to
master alarm panels, the control power source for
the relays shall be independent of any of the
master alarm panels - 5.1.9.2.3.3 Multiple master alarms shall be
permitted to monitor a single initiating device
20NFPA 5.1.9.2 Master Alarms
- 5.1.9.2.4 Master alarm panels for medical gas
vacuum systems shall each include the following
signals - An alarm condition when or just before changeover
occurs in a medical gas system that is supplied
by a manifold or other alternating-type bulk
system that has as a part of its normal operation
a changeover from one portion of the operating
supply to another - An alarm indication for a bulk cryogenic liquid
system when the main supply reaches an average
days supply, indicating low contents - An alarm indication when or just before the
changeover to the reserve supply occurs in a
medical gas system that consists of one or more
units that continuously supply the piping system
while another unit remains as the reserve supply
operates only in the case of an emergency - An alarm indication for cylinder reserve pressure
low when the content of a cylinder reserve header
is reduced below one days supply - For bulk cryogenic liquid systems, an alarm when
or at a predetermined set point before the
reserve supply contents fall to one days average
supply, indicating reserve low - Where a cryogenic liquid storage is used as a
reserve for a bulk supply system, an alarm
indication when the gas pressure available in the
reserve unit is below that required for the
medical gas system to function - An alarm indication when the pressure in the main
line of each separate medical gas system
increases 20 or decreases 20 from the normal
operating pressure
21NFPA 5.1.9.2 Master Alarms
- 5.1.9.2.4 Master alarm panels for medical gas
vacuum systems shall each include the following
signals - An alarm indication when the medical-surgical
vacuum pressure in the main line of each vacuum
system drops to or below 300 mm (12 inHg) - An alarm indication(s) from the local alarm
panel(s) as described in 5.1.9.5.2 to indicate
when one or more of the conditions being
monitored at a site is in alarm - A medical air dew point high alarm from each
compressor site to indicate when the line
pressure dew point is greater than 2 C (35
F) - A WAGD low alarm when the WAGD vacuum level or
flow is below effective operating limits - An instrument air dew point high alarm from each
compressor site to indicate when the line
pressure dew point is greater than -30C (-22F) - 5.1.9.2.5 The alarm indications required in
5.1.9.2.4(7) and 5.1.9.2.4(8) shall originate
from sensors installed in the main lines
immediately downstream of the source valves.
Where it is necessary to install a main line
valve in addition to a source valve, the sensors
shall be located downstream of the main valve.
22Thank-you!