17th EDITION WIRING REGS WHATS NEW - PowerPoint PPT Presentation

1 / 53
About This Presentation
Title:

17th EDITION WIRING REGS WHATS NEW

Description:

6 Inspection and Testing. 7 Special Installations or Locations. Appendices 1-15 ... Inspection and testing is now Part 6 rather than Part 7 and has few changes. ... – PowerPoint PPT presentation

Number of Views:292
Avg rating:3.0/5.0
Slides: 54
Provided by: aue3
Category:

less

Transcript and Presenter's Notes

Title: 17th EDITION WIRING REGS WHATS NEW


1
17th EDITION WIRING REGS WHATS NEW?
Chris Johnston - Senior Electrical Tutor City
Guilds Chief Examiner
2
Introduction
  • Issued on 1st January 2008
  • Came into effect 1st July 2008
  • The Regulations are fully aligned with the IEC
    60364 series of standards (world standards) and
    CENELEC harmonization documents (European
    standards).

3
Content
  • Part Title
  • 1 Scope, Object and Fundamental Principles
  • 2 Definitions
  • 3 Assessment of General Characteristics
  • 4 Protection for Safety
  • 5 Selection and Erection of Equipment
  • 6 Inspection and Testing
  • 7 Special Installations or Locations
  • Appendices 1-15

4
Using the Regulations
5
Numbering System
6
The Appendices
  • British Standards to which reference is made in
    the regulations
  • Statutory regulations and associated memoranda
  • Time/current characteristics of overcurrent
    protective devices
  • Current-carrying capacity and voltage drop for
    cable and flexible cords
  • Classification of external influences
  • Model forms for certification and reporting
  • Harmonized cable core colours

7
The Appendices
  • Current-carrying capacity and voltage drop for
    busbar trunking and powertrack systems
  • Definitions-Multiple source, d.c. and other
    systems
  • Protection of conductors in parallel against
    overcurrent
  • Harmonic currents in three-phase systems
  • Voltage drop in consumers installations
  • Methods for measuring insulation resistance of
    floors and walls
  • Measurement of fault loop impedance increase of
    resistance of conductors with temperature
  • Radial and ring final circuit arrangements

8
Part 1
  • Chapter 11 Scope
  • Chapter 12 Object and Effect
  • Chapter 13 Fundamental Principles

9
Scope
  • 110.1 General
  • The Regulations apply to the design and
    verification of electrical installations such as
    those of
  • (ix) Marinas
  • (xi) Mobile or transportable units
  • (xii) Photovoltaic systems
  • (xii) Low voltage generating sets

10
Object and Effect
  • Regulation 120.3
  • Any intended departure . requires special
    consideration by the designer The resulting
    degree of safety of the installation shall be not
    less than that obtained by compliance with the
    regulations

11
Fundamental Principles
  • 131.7 Where danger or damage is expected to arise
    due to an interruption of supply, suitable
    provisions shall be made in the installation or
    installed equipment
  • 132.13 Every electrical installation shall be
    provided with appropriate documentation

12
Fundamental Principles
  • 134.1.1 Good workmanship by competent persons or
    persons under their supervision and proper
    materials
  • 135.1 It is recommended that every electrical
    installation is subjected to periodic inspection
    and testing

13
Part 2 - Definitions
  • Aligned with the International Electrotechnical
    Vocabulary
  • There is an increase in the number of
    definitions from around 160 to about 230.

14
Part 2 - Definitions
  • Competent Person
  • A person who possesses sufficient technical
    knowledge and experience for the nature of the
    electrical work undertaken and is able at all
    times to prevent danger, and where appropriate,
    injury, to him/herself and others.

15
Part 2 - Definitions
  • Ordinary person A person who is neither skilled
    nor an instructed person.
  • Skilled person A person with technical
    knowledge or sufficient experience to enable
    him/her to avoid dangers which electricity may
    create.
  • Instructed person A person adequately advised
    or supervised by skilled persons to enable
    him/her to avoid dangers which electricity may
    create.

16
Part 2 - Definitions
  • Basic Protection (Protection against direct
    contact)
  • Protection against electric shock under
    fault-free conditions
  • Fault Protection (Protection against indirect
    contact)
  • Protection against electric shock under single
    fault conditions
  • Additional protection (Supplementary protection)
  • (Not defined in Part 2)

17
Part 2 - Definitions
  • Line conductor replaces Phase conductor
  • The term Live conductor still includes the
    neutral conductor

18
Part 3 Assessment of General Characteristics
  • Purpose, Supplies and structure
  • Classification of external Influences
  • Compatibility
  • Maintainability
  • Safety Services
  • Continuity of Service

19
Chapter 31
  • 311.1 For economic and reliable design, the
    maximum demand of an installation shall be
    assessed.
  • 314.1 Every installation shall be divided into
    circuits, as necessary to
  • (iii) Take account of the hazard that may arise
    from the failure of a single circuit such as a
    lighting circuit .

20
Part 4 Protection for Safety
  • Protection against electric shock
  • Protection against thermal effects
  • Protection against overcurrent
  • Protection against voltage disturbances and
    electromagnetic disturbances

21
Comparison with 16th Edition
22
Protection Against Electric Shock
  • 410.3.2 A protective measure shall consist of
  • An appropriate combination of a provision for
    basic protection and an independent provision for
    fault protection, or
  • An enhanced protective provision which provides
    both basic protection and fault protection.

23
Protection Against Electric Shock
  • Basic Protection (Protection against direct
    contact)
  • Protection against electric shock under
    fault-free conditions
  • Insulation, barriers and enclosures
  • Fault Protection (Protection against indirect
    contact)
  • Protection against electric shock under single
    fault conditions
  • Automatic disconnection of supply

24
Protection Against Electric Shock
  • The following protective measures are generally
    permitted
  • Automatic disconnection of supply (ADS) (most
    commonly used)
  • Double or reinforced insulation
  • Electrical separation for the supply to one item
    of current-using equipment
  • Extra-low voltage (SELV or PELV)

25
Disconnection Times
If an earth fault occurs then all final circuits
rated at 230 V to earth and having a current
rating of 32 A or less must disconnect in the
time shown below.
26
TN-S
Supply
Fuse Operates (0.4 s for circuits up 32 A )
LOAD
27
Disconnection Times
  • In a TN system the maximum disconnection time may
    be extended to 5 s for distribution circuits and
    other circuits having a rating exceeding 32 A.
  • In a TT system the maximum disconnection time may
    be extended to 1 s for distribution circuits and
    other circuits having a rating exceeding 32 A.

28
Earth Loop Impedance
  • In order to confirm that fuses and circuit
    breakers will meet the appropriate disconnection
    times, reference to tables 41.2, 41.3 and 41.4
    must be made. (Previously Tables 41B1, 41B2 and
    41D)
  • These are now based on 230 V (Uo) and not 240 V
    (Uoc)

29
Additional Protection
  • 411.3.3 In a.c. systems, additional protection by
    means of an RCD (having I?n not exceeding 30 mA)
    shall be provided for
  • Socket-outlets not exceeding 20 A rating for use
    by ordinary persons and intended for general use,
    and
  • Mobile equipment not exceeding 32 A rating for
    use outdoors.

30
Additional Protection
  • 411.3.3
  • An exception is permitted for
  • (iii) socket-outlets for use under the
    supervision of skilled or instructed persons e.g.
    in some commercial or industrial locations, or
  • (iv) A specific labelled or otherwise suitably
    identified socket-outlet provided for connection
    of a particular item of equipment.

31
Installations with Restricted Access
  • 410.3.5
  • The protective measures specified in Section
    417, i.e. the use of obstacles and placing out of
    reach, shall be used only in installations where
    access is restricted to
  • Skilled or instructed persons
  • Persons under the supervision of skilled or
    instructed persons.

32
Installations with Restricted Access
  • 410.3.6
  • The protective measures specified in Section
    418. i.e.
  • non-conducting location
  • Earth-free local equipotential bonding
  • Electrical separation for the supply to more than
    one item of equipment
  • shall be applied only where the installation is
    under the supervision of skilled or instructed
    persons so that unauthorised changes cannot be
    made.

33
Protection against thermal effects
  • There are few changes to this chapter.
  • It does include Chapter 48 from the 16th Edition
    , Precautions where particular risks of fire
    exist.

34
Protection Against Overcurrent
  • There are few changes to Chapter 43
  • Appendix 4 cable current rating
  • Now includes data for cables buried directly in
    the ground
  • Cable installation methods now are lettered
    rather than numbered
  • Correction factors now referred to as Rating
    factors

35
Protection against voltage disturbances and
electromagnetic disturbances
  • Additional information relating to protection of
    low voltage installations against temporary
    overvoltages due to earth faults in the high
    voltage system is now included

36
Part 5
  • Selection and Erection of Wiring Systems
  • 521.8.2
  • The line and neutral conductors of each final
    circuit shall be electrically separate from those
    of every other final circuit.

37
Cables in Walls
  • 522.6.7
  • requires cables which are buried in a wall at a
    depth not exceeding 50 mm which are part of an
    installation not under the supervision of a
    skilled or instructed person and the cable is not
    substantially mechanically protected, must be run
    in the safe zones AND
  • be protected by a 30 mA RCD.

38
Cables in Walls
  • 522.6.8
  • If the cables are in a wall that includes metal
    parts and is not under the supervision of a
    skilled or instructed person and the cable is not
    substantially mechanically protected, then
  • a 30 mA RCD must be used to protect the circuit
    irrespective of the depth of the cable.

39
Voltage Drop
40
Protection Against Overcurrent
  • 533.3
  • Where a protective device specifies a rated
    service short-circuit breaking capacity and an
    ultimate short-circuit breaking capacity, the
    device may be selected on the basis of the
    ultimate short-circuit conditions.
  • Operational circumstances may, however, make it
    desirable to select the protective device on the
    service short-circuit breaking capacity.

41
Safety Circuits
  • 560.7.9
  • In addition to a general schematic diagram, full
    details of all electrical safety sources shall be
    given. The information shall be maintained and
    displayed adjacent to the relevant distribution
    board. A single-line diagram is sufficient.

42
Part 6 Inspection and Testing
  • Inspection and testing is now Part 6 rather than
    Part 7 and has few changes.

43
Insulation Resistance
44
Insulation Resistance
  • Note to previous table
  • Where it is not reasonably practicable to
    disconnect surge protective devices (e.g. in case
    of fixed socket-outlets incorporating an SPD),
    the test voltage for the particular circuit may
    be reduced to 250 V d.c., but the insulation
    resistance shall have a value of at least 1 M?.

45
Phase Sequence and Voltage Drop
  • Regulation 612.12 requires that the phase
    sequence is maintained
  • Regulation 612.14 requires cable voltage drop to
    be verified. This is not normally required for
    initial verification.

46
Earth Loop Impedance
  • Appendix 14 provides information relating to the
    interpretation of earth loop impedance test
    results.
  • It states that compliance is met when
  • A more precise assessment may be necessary and
    guidance on how this may be achieved is also
    given.

47
Periodic Inspection
  • 621.5 Periodic inspection and testing shall be
    undertaken by a skilled person, competent in such
    work.
  • 634.2 Any damage, deterioration, defects,
    dangerous conditions and non-compliance with the
    requirements of the Regulations, which may give
    rise to danger, together with any significant
    limitations of the inspection and testing,
    including their reasons, shall be recorded.

48
Part 7
  • Numbering System
  • The number appearing after a section number
    generally refers to the corresponding Part,
    Chapter, Section or Regulation within Parts 1-6
    of the Regulations and therefore may not follow
    sequentially.
  • E.g. 701.414.4.5 Requirements for SELV
    and PELV circuits

49
Locations Containing a Bath or Shower
  • 701.411.3.3
  • Additional protection shall be provided for all
    circuits of the location, by the use of one or
    more RCDs having the characteristics specified in
    Regulation 415.1.1(30 mA)

50
Locations Containing a Bath or Shower
  • Supplementary equipotential bonding may be
    omitted where all of the following conditions are
    met
  • All final circuits of the location meet the
    appropriate disconnection time
  • All final circuits of the location have
    additional protection by means of a 30 mA RCD
  • All extraneous conductive parts of the location
    are effectively connected to the protective
    equipotential bonding

51
Locations Containing a Bath or Shower
  • Socket-outlets may be installed within a
    bathroom providing they are at least 3 m from
    zone 1

52
Construction and Demolition Site Installations
  • Reduced low voltage systems are strongly
    preferred for the supply to portable hand lamps
    for general use and portable hand tools and local
    lighting up to 2 kW
  • For circuits supplying one or more
    socket-outlets with a rated current exceeding 32
    A, an RCD having a rated residual operating
    current not exceeding 500 mA shall be provided

53
Thank you for your attention
Write a Comment
User Comments (0)
About PowerShow.com