Title: 17th EDITION WIRING REGS WHATS NEW
117th EDITION WIRING REGS WHATS NEW?
Chris Johnston - Senior Electrical Tutor City
Guilds Chief Examiner
2Introduction
- Issued on 1st January 2008
- Came into effect 1st July 2008
- The Regulations are fully aligned with the IEC
60364 series of standards (world standards) and
CENELEC harmonization documents (European
standards).
3Content
- Part Title
- 1 Scope, Object and Fundamental Principles
- 2 Definitions
- 3 Assessment of General Characteristics
- 4 Protection for Safety
- 5 Selection and Erection of Equipment
- 6 Inspection and Testing
- 7 Special Installations or Locations
- Appendices 1-15
4Using the Regulations
5Numbering System
6The Appendices
- British Standards to which reference is made in
the regulations - Statutory regulations and associated memoranda
- Time/current characteristics of overcurrent
protective devices - Current-carrying capacity and voltage drop for
cable and flexible cords - Classification of external influences
- Model forms for certification and reporting
- Harmonized cable core colours
7The Appendices
- Current-carrying capacity and voltage drop for
busbar trunking and powertrack systems - Definitions-Multiple source, d.c. and other
systems - Protection of conductors in parallel against
overcurrent - Harmonic currents in three-phase systems
- Voltage drop in consumers installations
- Methods for measuring insulation resistance of
floors and walls - Measurement of fault loop impedance increase of
resistance of conductors with temperature - Radial and ring final circuit arrangements
8Part 1
- Chapter 11 Scope
- Chapter 12 Object and Effect
- Chapter 13 Fundamental Principles
9Scope
- 110.1 General
- The Regulations apply to the design and
verification of electrical installations such as
those of - (ix) Marinas
- (xi) Mobile or transportable units
- (xii) Photovoltaic systems
- (xii) Low voltage generating sets
10Object and Effect
- Regulation 120.3
- Any intended departure . requires special
consideration by the designer The resulting
degree of safety of the installation shall be not
less than that obtained by compliance with the
regulations
11Fundamental Principles
- 131.7 Where danger or damage is expected to arise
due to an interruption of supply, suitable
provisions shall be made in the installation or
installed equipment - 132.13 Every electrical installation shall be
provided with appropriate documentation
12Fundamental Principles
- 134.1.1 Good workmanship by competent persons or
persons under their supervision and proper
materials - 135.1 It is recommended that every electrical
installation is subjected to periodic inspection
and testing
13Part 2 - Definitions
- Aligned with the International Electrotechnical
Vocabulary - There is an increase in the number of
definitions from around 160 to about 230.
14Part 2 - Definitions
- Competent Person
- A person who possesses sufficient technical
knowledge and experience for the nature of the
electrical work undertaken and is able at all
times to prevent danger, and where appropriate,
injury, to him/herself and others.
15Part 2 - Definitions
- Ordinary person A person who is neither skilled
nor an instructed person. - Skilled person A person with technical
knowledge or sufficient experience to enable
him/her to avoid dangers which electricity may
create. - Instructed person A person adequately advised
or supervised by skilled persons to enable
him/her to avoid dangers which electricity may
create.
16Part 2 - Definitions
- Basic Protection (Protection against direct
contact) - Protection against electric shock under
fault-free conditions - Fault Protection (Protection against indirect
contact) - Protection against electric shock under single
fault conditions - Additional protection (Supplementary protection)
- (Not defined in Part 2)
17Part 2 - Definitions
- Line conductor replaces Phase conductor
- The term Live conductor still includes the
neutral conductor
18Part 3 Assessment of General Characteristics
- Purpose, Supplies and structure
- Classification of external Influences
- Compatibility
- Maintainability
- Safety Services
- Continuity of Service
19Chapter 31
- 311.1 For economic and reliable design, the
maximum demand of an installation shall be
assessed. - 314.1 Every installation shall be divided into
circuits, as necessary to
- (iii) Take account of the hazard that may arise
from the failure of a single circuit such as a
lighting circuit .
20Part 4 Protection for Safety
- Protection against electric shock
- Protection against thermal effects
- Protection against overcurrent
- Protection against voltage disturbances and
electromagnetic disturbances
21Comparison with 16th Edition
22Protection Against Electric Shock
- 410.3.2 A protective measure shall consist of
- An appropriate combination of a provision for
basic protection and an independent provision for
fault protection, or - An enhanced protective provision which provides
both basic protection and fault protection.
23Protection Against Electric Shock
- Basic Protection (Protection against direct
contact) - Protection against electric shock under
fault-free conditions - Insulation, barriers and enclosures
- Fault Protection (Protection against indirect
contact) - Protection against electric shock under single
fault conditions - Automatic disconnection of supply
24Protection Against Electric Shock
- The following protective measures are generally
permitted - Automatic disconnection of supply (ADS) (most
commonly used) - Double or reinforced insulation
- Electrical separation for the supply to one item
of current-using equipment - Extra-low voltage (SELV or PELV)
25Disconnection Times
If an earth fault occurs then all final circuits
rated at 230 V to earth and having a current
rating of 32 A or less must disconnect in the
time shown below.
26TN-S
Supply
Fuse Operates (0.4 s for circuits up 32 A )
LOAD
27Disconnection Times
- In a TN system the maximum disconnection time may
be extended to 5 s for distribution circuits and
other circuits having a rating exceeding 32 A. - In a TT system the maximum disconnection time may
be extended to 1 s for distribution circuits and
other circuits having a rating exceeding 32 A.
28Earth Loop Impedance
- In order to confirm that fuses and circuit
breakers will meet the appropriate disconnection
times, reference to tables 41.2, 41.3 and 41.4
must be made. (Previously Tables 41B1, 41B2 and
41D) - These are now based on 230 V (Uo) and not 240 V
(Uoc)
29Additional Protection
- 411.3.3 In a.c. systems, additional protection by
means of an RCD (having I?n not exceeding 30 mA)
shall be provided for - Socket-outlets not exceeding 20 A rating for use
by ordinary persons and intended for general use,
and - Mobile equipment not exceeding 32 A rating for
use outdoors.
30Additional Protection
- 411.3.3
- An exception is permitted for
- (iii) socket-outlets for use under the
supervision of skilled or instructed persons e.g.
in some commercial or industrial locations, or - (iv) A specific labelled or otherwise suitably
identified socket-outlet provided for connection
of a particular item of equipment.
31Installations with Restricted Access
- 410.3.5
- The protective measures specified in Section
417, i.e. the use of obstacles and placing out of
reach, shall be used only in installations where
access is restricted to - Skilled or instructed persons
- Persons under the supervision of skilled or
instructed persons.
32Installations with Restricted Access
- 410.3.6
- The protective measures specified in Section
418. i.e. - non-conducting location
- Earth-free local equipotential bonding
- Electrical separation for the supply to more than
one item of equipment - shall be applied only where the installation is
under the supervision of skilled or instructed
persons so that unauthorised changes cannot be
made.
33Protection against thermal effects
-
- There are few changes to this chapter.
-
- It does include Chapter 48 from the 16th Edition
, Precautions where particular risks of fire
exist.
34Protection Against Overcurrent
- There are few changes to Chapter 43
- Appendix 4 cable current rating
- Now includes data for cables buried directly in
the ground - Cable installation methods now are lettered
rather than numbered - Correction factors now referred to as Rating
factors
35Protection against voltage disturbances and
electromagnetic disturbances
- Additional information relating to protection of
low voltage installations against temporary
overvoltages due to earth faults in the high
voltage system is now included
36Part 5
- Selection and Erection of Wiring Systems
- 521.8.2
- The line and neutral conductors of each final
circuit shall be electrically separate from those
of every other final circuit.
37Cables in Walls
- 522.6.7
- requires cables which are buried in a wall at a
depth not exceeding 50 mm which are part of an
installation not under the supervision of a
skilled or instructed person and the cable is not
substantially mechanically protected, must be run
in the safe zones AND - be protected by a 30 mA RCD.
38Cables in Walls
- 522.6.8
- If the cables are in a wall that includes metal
parts and is not under the supervision of a
skilled or instructed person and the cable is not
substantially mechanically protected, then - a 30 mA RCD must be used to protect the circuit
irrespective of the depth of the cable.
39Voltage Drop
40Protection Against Overcurrent
- 533.3
- Where a protective device specifies a rated
service short-circuit breaking capacity and an
ultimate short-circuit breaking capacity, the
device may be selected on the basis of the
ultimate short-circuit conditions. - Operational circumstances may, however, make it
desirable to select the protective device on the
service short-circuit breaking capacity.
41Safety Circuits
-
- 560.7.9
- In addition to a general schematic diagram, full
details of all electrical safety sources shall be
given. The information shall be maintained and
displayed adjacent to the relevant distribution
board. A single-line diagram is sufficient.
42Part 6 Inspection and Testing
- Inspection and testing is now Part 6 rather than
Part 7 and has few changes.
43Insulation Resistance
44Insulation Resistance
- Note to previous table
- Where it is not reasonably practicable to
disconnect surge protective devices (e.g. in case
of fixed socket-outlets incorporating an SPD),
the test voltage for the particular circuit may
be reduced to 250 V d.c., but the insulation
resistance shall have a value of at least 1 M?.
45Phase Sequence and Voltage Drop
- Regulation 612.12 requires that the phase
sequence is maintained - Regulation 612.14 requires cable voltage drop to
be verified. This is not normally required for
initial verification.
46Earth Loop Impedance
- Appendix 14 provides information relating to the
interpretation of earth loop impedance test
results. - It states that compliance is met when
-
- A more precise assessment may be necessary and
guidance on how this may be achieved is also
given.
47Periodic Inspection
- 621.5 Periodic inspection and testing shall be
undertaken by a skilled person, competent in such
work. - 634.2 Any damage, deterioration, defects,
dangerous conditions and non-compliance with the
requirements of the Regulations, which may give
rise to danger, together with any significant
limitations of the inspection and testing,
including their reasons, shall be recorded.
48Part 7
- Numbering System
- The number appearing after a section number
generally refers to the corresponding Part,
Chapter, Section or Regulation within Parts 1-6
of the Regulations and therefore may not follow
sequentially. - E.g. 701.414.4.5 Requirements for SELV
and PELV circuits
49Locations Containing a Bath or Shower
-
- 701.411.3.3
- Additional protection shall be provided for all
circuits of the location, by the use of one or
more RCDs having the characteristics specified in
Regulation 415.1.1(30 mA)
50Locations Containing a Bath or Shower
-
- Supplementary equipotential bonding may be
omitted where all of the following conditions are
met - All final circuits of the location meet the
appropriate disconnection time - All final circuits of the location have
additional protection by means of a 30 mA RCD - All extraneous conductive parts of the location
are effectively connected to the protective
equipotential bonding
51Locations Containing a Bath or Shower
-
-
- Socket-outlets may be installed within a
bathroom providing they are at least 3 m from
zone 1
52Construction and Demolition Site Installations
- Reduced low voltage systems are strongly
preferred for the supply to portable hand lamps
for general use and portable hand tools and local
lighting up to 2 kW - For circuits supplying one or more
socket-outlets with a rated current exceeding 32
A, an RCD having a rated residual operating
current not exceeding 500 mA shall be provided
53Thank you for your attention