Title: Understanding Micrologic
1Understanding Micrologic
2Contents
- Range
- Protection against overloads
- Protection against short-circuits
- Protection against insulation faults
- Hardware
- Metering
- Others functions
- Monitoring and/or protection of loads
- Load shedding and reconnection
- Programmable controller
- Harmonic
- Asic and microprocessor self-protection
3MicrologicRange
Micrologic 6. 0 P
Measurement type version Current
protection type
Without
Measurement type
P
A
H
Current protection type
5.0 H 6.0 H 7.0 H
5.0 P 6.0 P 7.0 P
2.0 A 5.0 A 6.0 A 7.0 A
2 Distribution L, I 5 Selective L, S, I 6
Selective and ground fault L, S, I, G 7
Selective and earth leakage L, S, I, V
2.0
5.0
Return to contents
4Protection against overloadsphases
LT setting
- Long-time protection (i²t) of the phases and the
neutral - Protect against premature ageing of cables
- Adjustable setting range using rating plugs
- standard 0.4 - 1, low 0.4 - 0.8, High 0.8 -
1, plug OFF - Setting to within one Amp with keypad or via
Communication
é8
Protection against risk of fire
5Protection against overloadsneutral conductor
- Neutral protection
- Adjustment
- by three position dial on the 4th pole 4P 3D,
3DN/2, 4P 4D - by keypad OFF, 1/2, Full, 1.6 (3 pole breaker
only) - Settings
- N/2 IrN 1/2 IrP, IsdN 1/2 IsdP, IiN IiP,
IgN IgP - 1.6N IrN 1.6 IrP, IsdN 1.6 IsdP, IiN IiP,
IgN IgP - Oversized neutral protection
- protection against 3rd-order harmonics summed up
in the neutral conductor - 3Pole breaker only
6Protection against overloads3rd harmonic in
neutral conductor
7Protection against overloadsIDMTL
- Long-time protection of the phases IDMTL type
(Inverse definite minimum time lag) - High voltage fuse
- Extremely inverse time
- Very inverse time
- Standard inverse time
- Definite time
Improvement of discrimination with HV
fuses Better protection of switchgears
Return to contents
8Protection against short-circuits
- Short-time protection
- For low impedance short-circuits (80 of faults)
- I²t ON to improve discrimination with downstream
protection, inverse time protection up to 10Ir - Instantaneous protection
- For solid short-circuits
- N1 and H1 breaker OFF position inhibits the
instantaneous protection - H2, H3 and L1 breaker OFF postion DIN value
(shown on screen) - RMS measurement with 20ms fixed time delay
ST pick-up
ST delay
Inst.
pick-up
Protection against risk of damage
9Protection against short-circuits Zone selective
interlocking (ZSI)
- Principle
- ZSI enables the control units to communicate with
each other. The system is able to locate the
short circuit or ground fault and clear it. - Functionning
- ZSI allows the circuit breaker to ignore its
preset delay when necessary. The fault is
cleared by the nearest upstream circuit breaker
with no intentional time delay. - Advantages
- Faster tripping time without sacrificing
coordination - Limitation of system stress by reducing amount of
let through energy.
Maximum 100 circuit breakers interconnected
whatever the configuration
Return to contents
10Protection against insulation faultsGround fault
- Ground fault protection
- Micrologic 6.0P
- Made mandatory by NEC
- Residual current Source Ground Return
Ig
Prevent risk of fire
11Protection against insulation faultsEarth
leakage
New
- Earth-leakage protection
- Micrologic 7.0P
- Mandatory per standards NFC 15100 and IEC 364
- In a TT system, protects property against low
level fault currents - In a TNS system, protects installations where
long cables are installed
Return to contents
12Hardware Principle and power supply
ZSI
M2C/M6C
COM Module
ASIC Basic protection L S I G V
Microprocessor Additional functions (monitoring,
measurement, analyses...)
Synchronous Exchange data
Mitop
Air CT
Isolation
Plugs Calibre/ perform.
Optical coupling
Iron CT
Power supply
Trip unit power supply
Surplus
- Optional external 24V DC power supply for
- programmable contact power supply and
- when breaker is open
- Powers display,
- Identification, adjustments through Com module
Test kit
Standard Internal voltage sensor lt690v
or optional external voltage sensor for µP power
supply and measurement
24V DC BUS power supply
Return to contents
13MeteringPrinciple
Refresh
Sampling
544µs
1 s
1s Integration Instant. data
15 s (sliding) 5..60 min (fixed)
5 to 60 min Integration Demand data
Return to contents
14RMS measurement
- Sampling frequency
- 1838Hz
- One measurement point every 544µs
- 36 points per cycle
- RMS value calculation
20ms
15Others functionsPrinciple
Meter
Programmable Controller
Monitor
Logging Data Logs Historical Data
Maintenance Data
Instant. data
IRMS P Q S EP EQ
Min / Max
Max I1 Min f17
Thresholds (pickup dropout)
Demand
Iavg Pavg
Relay Activation M2C/M6C
Breaker trip Mitop
Return to contents
16Demand measurementsfixed or sliding window
- fixed window
- Measurement of active reactive and apparent power
- time intervals programmable between 5mn and 1h
- values are refreshed at the end of the time
interval - Sliding window
- Measurement of current and active reactive and
apparent power - time intervals programmable between 5mn and 1h
- values are refreshed every 15 sec
sliding
fixed
5mn to 1h
t
15s
17Power factor PF
- Power factor
- PF P/S P active powerS apparent
powerNota cos ? P1/S1P1
Fundamental active powerS1 Fundamental
apparent power
apparent power S kVA
reactive power Q kvar
active power P kW
18Power factor PFSign convention
Reactive Power
Watts VArs P.F
Watts - VArs P.F -
Active Power
Active Power
Active Power
Watts VArs - P.F
Watts - VArs - P.F -
IEEE PF sign - Q sign(P/S)
IEEE altenate PF sign Q sign(P/S)
IEC PF sign sign(P/S)
19Monitoring and/or protection of loadsbased on
current, voltage, power, frequency
- Current and voltage unbalance
- Maximum current (per phases neutral)
- Minimum / maximum voltage
- Minimum / maximum frequency
20Monitoring and/or protection of loads Principle
of operation
variable
T1
Activation threshold
Deactivation threshold
T2
t
Alarm generated by Micrologic
21Monitoring and/or protection of loads Current
unbalance ANSI 46
- Application
- Protect rotating machines (motors, generators)
operating on balanced three-phase supplies
against ageing and slowing - Balance single-phase loads on three-phase
distribution systems - Detect phase loss
- Principle
- the function compares the current unbalance to
the threshold previously set by the user, for a
time greater than the time delay - Example
- I1 2500A I2 4000A IÂ 3 3400A
- Iaverage. 3300A
- Emax I1 - Iave. 800A
- DI Emax /Iaverage 24
I average
I1
I2
I3
22Monitoring and/or protection of loads Maximum
current per phase and N
- Application
- Obtain the maximum current demand in the presence
of major load fluctuations (welding machines,
crushers, hoists) - Principle
- This function calculates the maximum demand value
of the current in each Ph and Neutral over a
sliding time interval. - The interval can be adjusted between five
minutes and one hour. - The value is refreshed every 15s
I max demand
t1
t2
23Monitoring and/or protection of loads Voltage
unbalance ANSI 47
U average
- Application
- Protect loads against vibrations, temperature
rise and premature ageing - Principle
- The function compares the voltage unbalance to
the threshold previously set by the user, for a
time greater than the time delay. - Example
- U12 330v
- U23 390v
- U31 10V
- U average. 243v
- Emax U31 - U average. 233v
- DU Emax /U average. 96
E max
U12
U23
U31
24Monitoring and/or protection of loads Minimum
voltage ANSI 27
- Application
- Protect motors against voltage drops resulting in
loss of torque and a major increase in the
current drawn by the motor - Check the output voltage of a generator
- Principle
- The function is activated when one of the phase
to phase voltages is below the threshold set by
the user, for a time greater than the time delay. - The function is desactivated when all 3 phase are
above the threshold.
U12
U23
U31
Activation threshold U min
dectivation threshold U min
25Monitoring and/or protection of loads Minimum
voltage ANSI 27
U
U max activation threshold (maxi 1200V)
U min deactivation threshold
T2
T1
U min activation threshold (mini 100V)
100V
Alarm
t
26Monitoring and/or protection of loads Maximun
voltage ANSI 59
- Application
- Protect loads (motor and transformer) against
abnormally high voltages that can result in
irreversible damage - Avoid saturation of transformers
- Principle
- The function is activated when one of the phase
to phase voltages is above the threshold set by
the user, for a time greater than the time delay - The function is desactivated when all 3 phases
are under the threshold
Activation threshold U max
deativation threshold U max
27Monitoring and/or protection of loads Maximum
voltage ANSI 27
U
1200V
T1
U max activation threshold (maxi 1200V)
T2
Deactivation threshold
U min activation threshold (mini 100V)
Alarm
t
28Monitoring and/or protection of loads Reverse
power ANSI 32P
t
- Application
- Protect diesel engines from generators operating
as motors - marine applications, generator sets
- Avoid power transfers between two
parallel-connected sources - Principle
- The function is activated when the active power
flowing in the direction opposite set by the user
is greater than the activation threshold for a
time greater than the time delay.
Reconnection
Activation
Load shedding
Deactivation
Reverse power
P kW
29Monitoring and/or protection of loads Minimum
frequency ANSI 81
- Application
- Check the frequency of a generator
- Check the frequency across the terminals of a
motor - Avoid saturation of transformers following a drop
in frequency - Principle
- The function is activated when the frequency
exceeds the set threshold for a time greater than
the time delay
30Monitoring and/or protection of loads Minimum
frequency ANSI 81
F
F max activation threshold (maxi 540Hz)
T2
F min deactivation threshold
T1
F min activation threshold (mini 45Hz)
45Hz
Alarm
t
31Monitoring and/or protection of loads Maximum
frequency ANSI 81
- Application
- Check the frequency of a generator
- Check the frequency across the terminals of a
motor - Principle
- The function is activated when the frequency
exceeds the set threshold for a time greater than
the time delay
32Monitoring and/or protection of loads Maximum
frequency ANSI 81
F
540Hz
T1
F max activation threshold (maxi 540Hz)
T2
F max deactivation threshold
F min activation threshold (mini 45Hz)
Alarm
33Monitoring and/or protection of loads Phase
rotation
F2
- Application
- Avoid reversed rotation of motors
- Check on coupling between generator and
distribution system (phase sequence) - Principle
- The function compares the actual phase sequence
with the selected sequence - Alarm only
- Not available if the 400 Hz frequency is set
F1
F3
34Load shedding and reconnectionbased on current
t
- Application
- Ensure the continuity of service of priority
circuits by disconnecting non-priority loads - Principle
- The function is activated when the current
exceeds the set threshold for a time greater than
the time delay
reconnection
shedding
I
35Load shedding and reconnectionbased on power
P kW
- Application
- Ensure the continuity of service of priority
circuits by disconnecting non-priority loads - Principle
- The function is activated when the power exceeds
the set threshold for a time greater than the
time delay
10MW
Activation
Deactivation
100 kW
t
Alarm
shedding
reconnection
36Programmable controllerAlarms and relay outputs
with distinct thresholds
Activation
T1
- Alarm
- on supervisor via Com module
- activation and desactivation after a
programmable time delay - M2C or M6C relay outputs
- without latching gt follows the state of the
alarm - with temporary latching
- programmable from 1s to 6mn
- with permanent latching gt needs a resetting
Deactivation
T2
t
Alarm
Relays without latching
Relays with temporary latching
from 1s to 360s
possible Resetting
Relays with permanent latching
Reset
37Programmable controller Alarms and relay outputs
with identical thresholds
- Alarm
- on supervisor via Com module
- activation and desactivation after a
programmable time delay - M2C or M6C relay outputs
- without latching gt follows the state of the
alarm - with temporary latching
- programmable from 1s to 6mn
- with permanent latching gt needs to be reset
Activation/
T2
Deactivation
Alarm
Relays without latching
from 1s to 360s
Relays with temporary latching
possible resetting
Relays with permanent latching
Reset
38HarmonicDefinition
- A periodic signal is a combination of
- The original sinusoidal signal at the fundamental
frequency - Other sinusoidal signals (the harmonics) with
frequencies that are whole-number multiples of
the fundamental frequency - A DC component, where applicable
Return to contents
39HarmonicOrigin and effects
- OriginHarmonics are caused by non linear loads
such as - Welding machines
- arc/induction furnaces
- Variable speed drive
- office equipment (computer, copy machine, neon
lighting) - EffectsThe flow of harmonics in distribution
systems can cause serious problems such as - Increased currents (oversized neutral)
- Additional losses and premature aging
- Disturbances to loads due to voltage harmonics
- Disturbances in communication networks
Return to contents
40HarmonicQuality indicators
- These indicators are the indispensable tools used
to determine any required corrective action - Measurement of the fundamental
- Phase displacement of the fundamental
- Harmonic distorsion THD
- cos ?, power factor
- K factor, crest factor
- Distorsion power, distorsion factor
- Amplitude spectrum up to order 31 st
- Displacement spectrum
Return to contents
41Harmonic Total Harmonic Distortion
- Current THD
- Current per phase
- Neutral current
- Voltage THD
- Phase to phase voltage
- Phase - Neutral voltage
42Harmonic Fast Fourier Transfert
- Current harmonics
- each phase plus neutral
- up to 31st order
- Voltage harmonics
- phase to phase
- phase to Neutral
- up to 31st order
Return to contents
43Harmonic Waveform capture (WFC)
- Triggered manually
- 4 cycles
- magnitude I 0- 1.5 In
- magnitude V 0- 690V
- 64 points /cycle
- Triggered on event (alarm gt 1s)
- 4 cycles (on supervisor)
- magnitude I 0- 1.5 In
- magnitude V 0- 690V
- 64 points /cycle
- triggered by a fault
- 11/13 cycles (50/60 Hz)
- magnitude I 0- 20 In
- magnitude V 0- 690V
- 18/15 points /cycle (50/60 Hz)
- WFC available through the COM option only
44Asic and microprocessor self-protection
ASIC
Self protection - temperature - power supply
deficiency
Data exchange reading
45Asic and microprocessor self-protection
- ASIC self protection
- resulting in a circuit breaker tripping
- excessive temperature gt120
- ASIC power supply deficiency (overvoltage)
- Indication
- LED Ap  ONÂ
- display of error code on LCD screen
- Events log recording gtsupervisor
- µP self protection
- never trip the circuit-breaker
- Memory check sum
- Time-out
- Detection by the µPro of a serial link failure
between µP and the ASIC - Indication
- Events log recording gtsupervisor (if
communication still healthy)
46That s all for today !
- Isn t it simple and nice ?