Title: IMO Audit Findings - IT


1
IMO Audit Findings - ITs
2
IMO Audit Findings - ITs
  • As per Market Rules, ITs must be Measurement
    Canada approved or operating under Measurement
    Canada Temporary Permit - which expires May 1,
    2004
  • ITs must be operating on the MC approved tap and
    within the burden and rating factor limits
  • Number of installations consisting of MC approved
    ITs but not operating on the MC approved tap.
    ITs listed on MC Temp Permit.
  • Number of installations have non MC approved ITs
    and are not listed on the MC Temporary Permit.
    Subject to compliance.

3
IMO Audit Findings - ITs
  • Meter installation consists of distribution
    transformers for VTs (non MC approved and no
    accuracy rating).
  • May or may not be on MC Temp Permit
  • In some cases, distribution transformers are also
    used as station service transformers.
  • Auto transformers used in CT circuits of some
    meter installations.
  • Unable to determine IT accuracy in some cases.