Overcurrent Protection: Fuses and Circuit Breakers - PowerPoint PPT Presentation

1 / 41
About This Presentation
Title:

Overcurrent Protection: Fuses and Circuit Breakers

Description:

Chapter 17 Overcurrent Protection: Fuses and Circuit Breakers * * * * * * * * * * * * * * * * * * Series-Rated Applications (cont'd.) Where high available fault ... – PowerPoint PPT presentation

Number of Views:4092
Avg rating:3.0/5.0
Slides: 42
Provided by: fortiselec
Category:

less

Transcript and Presenter's Notes

Title: Overcurrent Protection: Fuses and Circuit Breakers


1
Chapter 17
  • Overcurrent ProtectionFuses and Circuit Breakers

2
Objectives
  • List and identify the types, classes, and ratings
    of fuses and circuit breakers
  • Describe the operation of fuses and circuit
    breakers
  • Develop an understanding of switch sizes,
    ratings, and requirements

3
Objectives (cont'd.)
  • Define interrupting rating, short-circuit
    currents, I2t, Ip, RMS, and current limitation
  • Apply the National Electrical Code to the
    selection and installation of overcurrent
    protective devices
  • Use the time-current characteristics curves and
    peak let-through charts

4
Overcurrent Protection
  • NEC Article 240 states the requirements for
    overcurrent protection
  • NEC 240.1 (FPN) use if the current reaches a
    value that will cause excessive temperature in
    conductors or conductor insulation
  • Two types of overcurrent protective devices are
    commonly used
  • Fuses and circuit breakers

5
Overcurrent Protection (cont'd.)
  • Underwriters Laboratories, Inc. (UL) and National
    Electrical Manufacturers Association (NEMA)
    establish standards for ratings, types,
    classifications, and testing procedures for fuses
    and circuit breakers

6
Disconnect Switches
  • Fused switches are available in ratings of
    several amperes in both 250 and 600 volts
  • Used with copper conductors unless marked to
    indicate suitability for use with aluminum
  • Rating, unless otherwise marked, is based on
  • 140F (60C) wire (14 AWG through 1 AWG) and
    167F (75C) for wires 1/0 AWG and larger
  • May be equipped with ground-fault sensing and
    labels that indicate their intended use

7
Disconnect Switches (cont'd.)
  • Accessibility of overcurrent devices
  • Occupants of must have access to overcurrent
    devices for their circuits, NEC 240.24(B)
  • How high should disconnect switches be mounted?
  • NEC 240.24(A) requires that overcurrent devices
    be readily accessible
  • Same rule applies to a circuit breaker

8
Fuses and Circuit Breakers
  • Voltage rating
  • Equal to or greater than the voltage of the
    circuit in which they are to be used
  • Continuous current rating
  • Amperes that the device can continuously carry
  • Rating is usually based on the ampacity of
    circuit conductors

9
Fuses and Circuit Breakers (cont'd.)
  • Protection of conductors
  • When overcurrent device is rated at 800 amperes
    or less
  • The Code permits the use of next higher standard
    ampere-rated fuse or circuit breaker

10
Fuses and Circuit Breakers (cont'd.)
  • When overcurrent device is rated above 800-ampere
  • Conductor ampacity must be equal to or greater
    than the rating of the fuse or circuit breaker
  • Interrupting rating
  • Highest current where a device is intended to
    interrupt under standard test conditions

11
Fuses and Circuit Breakers (cont'd.)
  • Short-circuit current rating
  • Ability to withstand fault current equal to or
    less than the short-circuit rating for the length
    of time it takes the overcurrent device to react
  • Speed of response
  • Time required for a fuse to open varies inversely
    with current that flows through fuse
  • Circuit breaker also has this characteristic

12
Types of Fuses
  • Dual-element, time-delay fuse
  • Provides a time delay in low-overload range to
    eliminate unnecessary opening of the circuit
    because of harmless overloads
  • Using fuses for motor overload protection
  • Sizing dual-element fuses slightly larger than
    the overload relay provides backup protection
  • If overload relays fail to operate, dual-element
    fuses will provide backup overload protection

13
Types of Fuses (cont'd.)
  • Applying fuses and breakers on motor circuits
  • High starting currents of motors can cause
    nuisance opening of fuses and nuisance tripping
    of circuit breakers
  • Check time-current curves of fuses and breakers
    to make sure that they will handle the momentary
    motor starting inrush currents without nuisance
    opening or tripping

14
Types of Fuses (cont'd.)
  • Using fuses for motor branch-circuit,
    short-circuit, and ground-fault protection
  • NEC Table 430.52 maximum size permitted for
    dual-element fuses is based on a maximum of 175
    percent of full-load current of the motor
  • Dual-element, time-delay, current-limiting fuses
  • Can handle currents five times their ampere
    rating for at least 10 seconds

15
Types of Fuses (cont'd.)
  • Fast-acting, current-limiting fuses
    (nontime-delay)
  • Extremely fast response in both low-overload and
    short-circuit ranges
  • Has the lowest energy let-through values
  • Provides better protection to mains, feeders and
    subfeeders, circuit breakers, bus duct,
    switchboards, and other circuit components

16
Types of Fuses (cont'd.)
  • Types of cartridge fuses
  • According to the Code, all cartridge fuses must
    be marked to show
  • Ampere rating
  • Voltage rating
  • Interrupting rating when greater than 10,000
    amperes
  • Current-limiting type, if applicable
  • Trade name or name of manufacturer

17
Types of Fuses (cont'd.)
  • Plug fuses
  • Requirements in NEC Article 240, Part V
  • Opening characteristics available in three types
  • Standard link type does not have much time delay
  • Loaded link type has a metal bead element that
    gives it time delay to hold motor inrush starting
    currents
  • Dual-element, time-delay has a spring-loaded
    short-circuit element plus an overload element
    connected in series with short-circuit element

18
Testing Fuses
  • OSHA electrical equipment must not be worked on
    when it is energized
  • When power is turned on
  • Exercise extreme caution when checking fuses
  • Using a voltmeter, first step is to set the scale
    to its highest voltage setting and then change to
    a lower scale after you are within the range of
    the voltmeter

19
Testing Fuses (cont'd.)
  • Reading from line-to-load side of a good fuse
    should show zero to small voltage
  • When power is turned off
  • Remove fuse from switch, then use an ohmmeter to
    take a resistance reading
  • Good fuse zero or a very minimal resistance
    open (blown) fuse will show a high reading

20
Testing Fuses (cont'd.)
  • Cable limiters
  • Used where parallel cables are used on service
    entrances and feeders
  • Devices that can isolate a faulted cable rather
    than having the fault open the entire phase
  • Selected on the basis of conductor size
  • Are available for cable-to-cable or cable-to-bus
    installation for either aluminum or copper hot
    phase conductors

21
Figure 17-18 Use of cable limiters in a service
entrance
22
Delta, 3-Phase, Corner-Grounded B Phase System
  • Fuses shall be installed in series with
    un-grounded conductors for overcurrent
    protection, NEC 240.15(A)
  • Sometimes called a corner ground
  • There are certain instances where a 3-pole,
    3-phase switch may be installed, where it is
    permitted to install fuses in two poles only

23
Figure 17-20 Three-phase, 3-wire delta system
with grounded B phase
24
Delta, 3-Phase, Corner-Grounded B Phase System
(cont'd.)
  • Solid neutrals
  • Made of copper bar that has exactly the same
    dimensions as a fuse for a given ampere rating
    and voltage rating
  • Generally used in retrofit situations

25
Time-Current Characteristic Curves and Peak
Let-Through Charts
  • Fuse manufacturers furnish information for
  • Time-current characteristic curves, including
    total clearing and minimum melting curves
  • Peak let-through charts
  • Time-current characteristic curves can be used to
    answer questions about fuse capabilities

26
Peak Let-Through Charts (cont'd.)
  • The use of peak let-through charts
  • Properly matches short-circuit current rating of
    electrical equipment with let-through current
    values of overcurrent protective devices
  • Peak let-through charts give a good indication of
    current-limiting effects of a current-limiting
    fuse or circuit breaker under bolted fault
    conditions

27
Circuit Breakers
  • NEC Article 100 definition
  • Device designed to open and close a circuit by
    nonautomatic means and to open the circuit
    automatically on a predetermined overcurrent
  • Types of circuit breakers
  • Molded-case circuit breakers
  • Power circuit breakers
  • Insulated-case circuit breakers

28
Figure 17-28 Molded-case circuit breakers
29
Circuit Breakers (cont'd.)
  • NEC 240.80 through 240.86 state the basic
    requirements for circuit breakers
  • Thermal-magnetic circuit breakers
  • Contain a bimetallic element that, on continuous
    overload, moves until it unlatches the inner
    tripping mechanism of the breaker
  • Time required for the breaker to open the circuit
    depends upon the fault current and mechanical
    condition of circuit breaker

30
Circuit Breakers (cont'd.)
  • Ambient-compensated circuit breakers
  • Some circuit breakers are ambient (surrounding
    temperature) compensated
  • If installing thermal circuit breakers in
    extremely hot or extremely cold temperatures,
    consult manufacturers literature
  • Ambient factors can affect proper operation of a
    circuit breaker, such as dust, fumes, etc.

31
Circuit Breakers (cont'd.)
  • Common misapplication
  • Common violation of NEC 110.9 and 110.10
  • Installation of a main circuit breaker that has a
    high interrupting rating while making the
    assumption that branch-circuit breakers are
    protected adequately against short circuit
  • Standard molded case circuit breakers with high
    interrupting ratings cannot protect standard
    end-use equipment having lower interrupting
    rating

32
Series-Rated Applications
  • Series-rated equipment
  • Main overcurrent device and branch-circuit
    overcurrent devices are connected in series
  • Series-rated systems
  • Less costly than fully-rated systems
  • Available fault current does not exceed
    interrupting rating of the line-side overcurrent
    device but does exceed interrupting rating of the
    load-side overcurrent device

33
Figure 17-33 Series-rated circuit breakers. In
this example, both the 20-ampere breaker and the
100-ampere main breaker trip off under high-level
fault conditions
34
Series-Rated Applications (cont'd.)
  • Where high available fault currents indicate the
    need for high interrupting breakers or fuses,
    fully rated system is generally used
  • Another less costly way to safely match main
    circuit breaker or main fuses ahead of
    branch-circuit breakers is to use listed
    series-rated equipment

35
Series-Rated Systems Where Electric Motors are
Connected
  • NEC 240.86(C) sets forth two requirements
  • Do not connect electric motors between load side
    of higher rated overcurrent device and line side
    of lower rated overcurrent device
  • Sum of connected motor full-load currents shall
    not exceed one percent of the interrupting rating
    of lower rated circuit breaker

36
Current-Limiting Breakers
  • Current-limiting circuit breaker limits the
    let-through energy (I2t) to something less than
    the I2t of a one-half cycle symmetrical wave
  • When installing circuit breakers, it is important
    to ensure that
  • Circuit breakers have the proper rating
  • All circuit components can withstand the
    let-through current of the breaker

37
Cost Considerations
  • There are a number of different types of circuit
    breakers to choose from
  • Selection of the type to use depends upon a
    number of factors, including interrupting rating,
    selectivity, space, and cost

38
Motor Circuits
  • NEC Table 430.52
  • Shows that maximum setting of a conventional
    inverse-time circuit breaker must not exceed 250
    percent of full-load current of the motor
  • For instantaneous-trip circuit breaker, maximum
    setting is 800 percent of motors full-load
    current
  • Design B motors, the maximum setting is 1100
    percent

39
Motor Circuits (cont'd.)
  • If an engineering evaluation can demonstrate
    the need to exceed percentages shown in NEC
    Table 430.52, then
  • 800 percent setting may be increased to a maximum
    of 1300 percent
  • 1100 percent setting may be increased to a
    maximum of 1700 percent

40
Heating, Air-Conditioning, and Refrigeration
Overcurrent Protection
  • Check the nameplate carefullyand do what it says
  • Nameplate on HVAC equipment might indicate
    maximum size fuse, maximum size fuse or
    circuit breaker, or maximum size fuse or HACR
    circuit breaker

41
Summary
  • NEC Article 240 sets the requirements for
    overcurrent protection
  • Two types of overcurrent protective devices
    commonly used fuses and circuit breakers
  • Factors that must be considered when selecting
    proper fuses and circuit breakers
  • Voltage rating, continuous current rating,
    interrupting rating, and speed of response
Write a Comment
User Comments (0)
About PowerShow.com