Title: Overcurrent Protection: Fuses and Circuit Breakers
1Chapter 17
- Overcurrent ProtectionFuses and Circuit Breakers
2Objectives
- List and identify the types, classes, and ratings
of fuses and circuit breakers - Describe the operation of fuses and circuit
breakers - Develop an understanding of switch sizes,
ratings, and requirements
3Objectives (cont'd.)
- Define interrupting rating, short-circuit
currents, I2t, Ip, RMS, and current limitation - Apply the National Electrical Code to the
selection and installation of overcurrent
protective devices - Use the time-current characteristics curves and
peak let-through charts
4Overcurrent Protection
- NEC Article 240 states the requirements for
overcurrent protection - NEC 240.1 (FPN) use if the current reaches a
value that will cause excessive temperature in
conductors or conductor insulation - Two types of overcurrent protective devices are
commonly used - Fuses and circuit breakers
5Overcurrent Protection (cont'd.)
- Underwriters Laboratories, Inc. (UL) and National
Electrical Manufacturers Association (NEMA)
establish standards for ratings, types,
classifications, and testing procedures for fuses
and circuit breakers
6Disconnect Switches
- Fused switches are available in ratings of
several amperes in both 250 and 600 volts - Used with copper conductors unless marked to
indicate suitability for use with aluminum - Rating, unless otherwise marked, is based on
- 140F (60C) wire (14 AWG through 1 AWG) and
167F (75C) for wires 1/0 AWG and larger - May be equipped with ground-fault sensing and
labels that indicate their intended use
7Disconnect Switches (cont'd.)
- Accessibility of overcurrent devices
- Occupants of must have access to overcurrent
devices for their circuits, NEC 240.24(B) - How high should disconnect switches be mounted?
- NEC 240.24(A) requires that overcurrent devices
be readily accessible - Same rule applies to a circuit breaker
8Fuses and Circuit Breakers
- Voltage rating
- Equal to or greater than the voltage of the
circuit in which they are to be used - Continuous current rating
- Amperes that the device can continuously carry
- Rating is usually based on the ampacity of
circuit conductors
9Fuses and Circuit Breakers (cont'd.)
- Protection of conductors
- When overcurrent device is rated at 800 amperes
or less - The Code permits the use of next higher standard
ampere-rated fuse or circuit breaker
10Fuses and Circuit Breakers (cont'd.)
- When overcurrent device is rated above 800-ampere
- Conductor ampacity must be equal to or greater
than the rating of the fuse or circuit breaker - Interrupting rating
- Highest current where a device is intended to
interrupt under standard test conditions
11Fuses and Circuit Breakers (cont'd.)
- Short-circuit current rating
- Ability to withstand fault current equal to or
less than the short-circuit rating for the length
of time it takes the overcurrent device to react - Speed of response
- Time required for a fuse to open varies inversely
with current that flows through fuse - Circuit breaker also has this characteristic
12Types of Fuses
- Dual-element, time-delay fuse
- Provides a time delay in low-overload range to
eliminate unnecessary opening of the circuit
because of harmless overloads - Using fuses for motor overload protection
- Sizing dual-element fuses slightly larger than
the overload relay provides backup protection - If overload relays fail to operate, dual-element
fuses will provide backup overload protection
13Types of Fuses (cont'd.)
- Applying fuses and breakers on motor circuits
- High starting currents of motors can cause
nuisance opening of fuses and nuisance tripping
of circuit breakers - Check time-current curves of fuses and breakers
to make sure that they will handle the momentary
motor starting inrush currents without nuisance
opening or tripping
14Types of Fuses (cont'd.)
- Using fuses for motor branch-circuit,
short-circuit, and ground-fault protection - NEC Table 430.52 maximum size permitted for
dual-element fuses is based on a maximum of 175
percent of full-load current of the motor - Dual-element, time-delay, current-limiting fuses
- Can handle currents five times their ampere
rating for at least 10 seconds
15Types of Fuses (cont'd.)
- Fast-acting, current-limiting fuses
(nontime-delay) - Extremely fast response in both low-overload and
short-circuit ranges - Has the lowest energy let-through values
- Provides better protection to mains, feeders and
subfeeders, circuit breakers, bus duct,
switchboards, and other circuit components
16Types of Fuses (cont'd.)
- Types of cartridge fuses
- According to the Code, all cartridge fuses must
be marked to show - Ampere rating
- Voltage rating
- Interrupting rating when greater than 10,000
amperes - Current-limiting type, if applicable
- Trade name or name of manufacturer
17Types of Fuses (cont'd.)
- Plug fuses
- Requirements in NEC Article 240, Part V
- Opening characteristics available in three types
- Standard link type does not have much time delay
- Loaded link type has a metal bead element that
gives it time delay to hold motor inrush starting
currents - Dual-element, time-delay has a spring-loaded
short-circuit element plus an overload element
connected in series with short-circuit element
18Testing Fuses
- OSHA electrical equipment must not be worked on
when it is energized - When power is turned on
- Exercise extreme caution when checking fuses
- Using a voltmeter, first step is to set the scale
to its highest voltage setting and then change to
a lower scale after you are within the range of
the voltmeter
19Testing Fuses (cont'd.)
- Reading from line-to-load side of a good fuse
should show zero to small voltage - When power is turned off
- Remove fuse from switch, then use an ohmmeter to
take a resistance reading - Good fuse zero or a very minimal resistance
open (blown) fuse will show a high reading
20Testing Fuses (cont'd.)
- Cable limiters
- Used where parallel cables are used on service
entrances and feeders - Devices that can isolate a faulted cable rather
than having the fault open the entire phase - Selected on the basis of conductor size
- Are available for cable-to-cable or cable-to-bus
installation for either aluminum or copper hot
phase conductors
21Figure 17-18 Use of cable limiters in a service
entrance
22Delta, 3-Phase, Corner-Grounded B Phase System
- Fuses shall be installed in series with
un-grounded conductors for overcurrent
protection, NEC 240.15(A) - Sometimes called a corner ground
- There are certain instances where a 3-pole,
3-phase switch may be installed, where it is
permitted to install fuses in two poles only
23Figure 17-20 Three-phase, 3-wire delta system
with grounded B phase
24Delta, 3-Phase, Corner-Grounded B Phase System
(cont'd.)
- Solid neutrals
- Made of copper bar that has exactly the same
dimensions as a fuse for a given ampere rating
and voltage rating - Generally used in retrofit situations
25Time-Current Characteristic Curves and Peak
Let-Through Charts
- Fuse manufacturers furnish information for
- Time-current characteristic curves, including
total clearing and minimum melting curves - Peak let-through charts
- Time-current characteristic curves can be used to
answer questions about fuse capabilities
26Peak Let-Through Charts (cont'd.)
- The use of peak let-through charts
- Properly matches short-circuit current rating of
electrical equipment with let-through current
values of overcurrent protective devices - Peak let-through charts give a good indication of
current-limiting effects of a current-limiting
fuse or circuit breaker under bolted fault
conditions
27Circuit Breakers
- NEC Article 100 definition
- Device designed to open and close a circuit by
nonautomatic means and to open the circuit
automatically on a predetermined overcurrent - Types of circuit breakers
- Molded-case circuit breakers
- Power circuit breakers
- Insulated-case circuit breakers
28Figure 17-28 Molded-case circuit breakers
29Circuit Breakers (cont'd.)
- NEC 240.80 through 240.86 state the basic
requirements for circuit breakers - Thermal-magnetic circuit breakers
- Contain a bimetallic element that, on continuous
overload, moves until it unlatches the inner
tripping mechanism of the breaker - Time required for the breaker to open the circuit
depends upon the fault current and mechanical
condition of circuit breaker
30Circuit Breakers (cont'd.)
- Ambient-compensated circuit breakers
- Some circuit breakers are ambient (surrounding
temperature) compensated - If installing thermal circuit breakers in
extremely hot or extremely cold temperatures,
consult manufacturers literature - Ambient factors can affect proper operation of a
circuit breaker, such as dust, fumes, etc.
31Circuit Breakers (cont'd.)
- Common misapplication
- Common violation of NEC 110.9 and 110.10
- Installation of a main circuit breaker that has a
high interrupting rating while making the
assumption that branch-circuit breakers are
protected adequately against short circuit - Standard molded case circuit breakers with high
interrupting ratings cannot protect standard
end-use equipment having lower interrupting
rating
32Series-Rated Applications
- Series-rated equipment
- Main overcurrent device and branch-circuit
overcurrent devices are connected in series - Series-rated systems
- Less costly than fully-rated systems
- Available fault current does not exceed
interrupting rating of the line-side overcurrent
device but does exceed interrupting rating of the
load-side overcurrent device
33Figure 17-33 Series-rated circuit breakers. In
this example, both the 20-ampere breaker and the
100-ampere main breaker trip off under high-level
fault conditions
34Series-Rated Applications (cont'd.)
- Where high available fault currents indicate the
need for high interrupting breakers or fuses,
fully rated system is generally used - Another less costly way to safely match main
circuit breaker or main fuses ahead of
branch-circuit breakers is to use listed
series-rated equipment
35Series-Rated Systems Where Electric Motors are
Connected
- NEC 240.86(C) sets forth two requirements
- Do not connect electric motors between load side
of higher rated overcurrent device and line side
of lower rated overcurrent device - Sum of connected motor full-load currents shall
not exceed one percent of the interrupting rating
of lower rated circuit breaker
36Current-Limiting Breakers
- Current-limiting circuit breaker limits the
let-through energy (I2t) to something less than
the I2t of a one-half cycle symmetrical wave - When installing circuit breakers, it is important
to ensure that - Circuit breakers have the proper rating
- All circuit components can withstand the
let-through current of the breaker
37Cost Considerations
- There are a number of different types of circuit
breakers to choose from - Selection of the type to use depends upon a
number of factors, including interrupting rating,
selectivity, space, and cost
38Motor Circuits
- NEC Table 430.52
- Shows that maximum setting of a conventional
inverse-time circuit breaker must not exceed 250
percent of full-load current of the motor - For instantaneous-trip circuit breaker, maximum
setting is 800 percent of motors full-load
current - Design B motors, the maximum setting is 1100
percent
39Motor Circuits (cont'd.)
- If an engineering evaluation can demonstrate
the need to exceed percentages shown in NEC
Table 430.52, then - 800 percent setting may be increased to a maximum
of 1300 percent - 1100 percent setting may be increased to a
maximum of 1700 percent
40Heating, Air-Conditioning, and Refrigeration
Overcurrent Protection
- Check the nameplate carefullyand do what it says
- Nameplate on HVAC equipment might indicate
maximum size fuse, maximum size fuse or
circuit breaker, or maximum size fuse or HACR
circuit breaker
41Summary
- NEC Article 240 sets the requirements for
overcurrent protection - Two types of overcurrent protective devices
commonly used fuses and circuit breakers - Factors that must be considered when selecting
proper fuses and circuit breakers - Voltage rating, continuous current rating,
interrupting rating, and speed of response