College and University Fire Prevention - PowerPoint PPT Presentation

1 / 66
About This Presentation
Title:

College and University Fire Prevention

Description:

... rooms, gift or retail shops. Bulk laundries, guest laundries ... Approved covers are to be provided for all switch and electrical outlet boxes. BOCA F-310.6 ... – PowerPoint PPT presentation

Number of Views:153
Avg rating:3.0/5.0
Slides: 67
Provided by: statefirem
Category:

less

Transcript and Presenter's Notes

Title: College and University Fire Prevention


1
College and UniversityFire Prevention
  • Oklahoma State Fire Marshals Office

2
State Adopted Codes
  • 1999 BOCA Building Code
  • 1999 BOCA Fire Prevention Code
  • 1997 NFPA 101 Life Safety Code

3
Occupancy Classification
  • The use group is determined by the subject being
    taught
  • Most instructional areas are Business Use Group
  • Areas with more than 50 occupants are Assembly
  • Laboratories with chemicals have special
    requirements
  • Dormitories are R-2 Residential Use Group

4
Business Use Occupancies
  • Means of Egress Components
  • Doors NFPA 101 5-2.1
  • Delayed egress to comply with NFPA 101
    5-2.1.6.1
  • Access-controlled egress to comply with NFPA 101
    5-2.1.6.2

5
Business Use Occupancies
  • Stairs comply with NFPA 5-2.2
  • Number of EXITS
  • Two separate exits
  • Provided on every story
  • Accessible from every part of every story and
    mezzanine
  • With exceptions 1 through 4 permitted
  • NFPA 101 27-2.4.1

6
Business Use Occupancies
  • No dead-end corridor may exceed 50 feet
  • NFPA 101 27-2.5.2

7
Business Use Occupancies
  • Arrangement of means of egress
  • No common path of travel may exceed 75 feet
  • NFPA 101 27-2.5.3
  • Travel distance to Exit may not exceed 200 feet
  • NFPA 101 27-2.6

8
Business Use Occupancies
  • Emergency Lighting is required when
  • The building is two or more stories in height
  • The occupancy is subject to 100 or more occupants
    above or below the level of discharge
  • The occupancy is subject to 1,000 occupants
  • Windowless or underground

9
Business Use Occupancies
  • Means of egress are required to have signs
  • NFPA 101 27-2.10
  • Vertical Openings
  • Every stairway, elevator shaft, escalator
    opening, and other vertical opening shall b e
    enclosed or protected in accordance with 6-2.4.5
    with exceptions 1 through 5
  • NFPA 10127-3.1

10
Business Use Occupancies
  • Interior wall and ceiling finish is required to
    be Class A or Class B in exits and enclosed
    corridors
  • Interior wall and ceiling finish is required to
    be Class A, Class B, or Class C in other areas
  • NFPA 10127-3.4

11
Business Use Occupancies
  • Fire Alarm systems are required when
  • The building is two or more stories in height
    above the level of exit discharge
  • The occupancy is subject to 100 or more occupants
    above or below the level of discharge
  • The occupancy is subject to 1,000 or more total
    occupants
  • NFPA 101 27-3.4.1

12
Residential Occupancies - Dormitories
  • Definition Dormitories
  • Buildings or spaces in buildings where group
    sleeping accommodations are provided for more
    than 16 persons who are not members of the same
    family in one room or a series of closely
    associated rooms under joint occupancy and single
    management, with or without meals, but without
    individual cooking facilities

13
Dormitories
  • Doors
  • No door in any means of egress shall be locked
    against egress when the building is occupied with
    exception of delayed egress locks complying with
    NFPA 101 5-2.1.6.1 and access-controlled egress
    doors complying with NFPA 101 5-2-1.6.2
  • NFPA 101 17-2.2.2

14
Delayed Egress Doors
  • Approved, listed, delayed egress locks are
    permitted in buildings protected throughout by an
    approved, supervised automatic fire detection
    system, or an approved, supervised automatic fire
    sprinkler system provide that

15
Delayed Egress Doors
  • The doors unlock upon actuation of an approved,
    supervised automatic sprinkler system or upon
    actuation of any heat detector or not more than
    two smoke detectors of an approved, supervised
    automatic fire detection system

16
Delayed Egress Doors
  • The doors unlock upon loss of power controlling
    the lock or locking mechanism

17
Delayed Egress Doors
  • The doors unlock upon disablement of the
    automatic fire detection system, sprinkler
    system, or the means of sprinkler system
    supervision

18
Delayed Egress Doors
  • An irreversible process releases the lock within
    15 seconds upon application to the release device
    required for not more than 3 seconds
  • The initiation shall activate a signal near the
    door

19
Delayed Egress Doors
  • On the door adjacent to the release device, there
    is a readily visible, durable sign in letters at
    least 1 inch height and at least 1/8 inch stroke
    that reads
  • PUSH DOOR UNTIL ALARM SOUNDS
  • DOOR CAN BE OPENED IN 15 SECONDS

20
(No Transcript)
21
(No Transcript)
22
Access Controlled Doors
  • Access-controlled egress doors are permitted to
    be equipped with an approved entrance and egress
    system provide that
  • A sensor is provided on the egress side arranged
    to detect an occupant approaching the doors and
    the doors are arranged to unlock upon detection
    of approaching occupant or loss of power

23
Access Controlled Doors
  • Loss of power to that part of the access control
    system that locks the doors automatically unlocks
    the doors
  • The doors are arranged to unlock from a manual
    release device located 40 inches to 48 inches
    vertically above the floor within 5 feet of the
    secured doors. The manual release device shall
    be readily accessible and read
  • PUSH TO EXIT

24
Doors Access Controlled Doors
  • When operated, the manual release device shall
    result in direct interruption of power to the
    lock -- independent of the access control system
    electronics -- and the doors shall remain
    unlocked for at least 30 seconds

25
Access Controlled Doors
  • Activation of the building automatic sprinkler or
    fire detection system automatically unlocks the
    doors
  • The doors remain unlocked until the
    fire-protective signaling system has been
    manually reset

26
Dormitory Egress
  • Not less than two exits shall be accessible from
    every floor, including floors below the level of
    exit discharge and occupied for public purposes
  • NFPA 101 17-2.3.1

27
Dormitory Egress
  • No common path of travel shall exceed 35 feet
  • NFPA 101 17-2.5.2
  • No dead-end corridor shall exceed 50 feet
  • NFPA 101 17-2.5.3

28
Dormitory Egress
  • Means of egress shall be illuminated
  • NFPA 101 17-2.8
  • Emergency lighting is required in all buildings
    with more than 25 rooms
  • NFPA 101 17-2.9
  • Means of egress is required to have signs
  • NFPA 101 17-2.10

29
Dormitories - Protection of Vertical Openings
  • Every stairway, elevator shaft, and other
    vertical opening shall be enclosed or protected
  • Exceptions 1 through 5

30
Get Out and Stay Alive
  • United States Fire Administration 16825 South
    Seton Avenue Emmitsburg, MD 21727
    (301) 447-1189
    Internet htt//www.usfa.fema.gov

31
Dormitory - Protection from Hazards
  • The following areas are deemed hazardous and
    require 1-hour separation or sprinklers
  • Boiler and fuel-fired heater rooms serving more
    than a single guest room
  • Employee locker rooms, gift or retail shops
  • Bulk laundries, guest laundries over 100 sq ft
  • Maintenance shops, trash rooms, storage rooms
  • NFPA 101 17-3.2.2

32
Dormitory - Interior Finish
  • Interior wall and ceiling finish material are
    required to comply with 6-5.5
  • Exit enclosures Class A or Class B
  • Other spaces Class A, Class B, or Class C
  • NFPA 101 17-3.3.3

33
Dormitory - Interior Finish
  • Curtains, draperies, and other similar loosely
    hanging furnishings and decorations are required
    to be flame resistant
  • NFPA 101 17-3-3.4

34
Dormitory Detection Alarm
  • A fire alarm system is required in all dormitory
    buildings, except where each room has an exterior
    exit door
  • NFPA 101 17-3.4.1

35
Dormitory Detection Alarm
  • Initiation
  • Manual means
  • At any control station or desk
  • By the sprinkler system or fire detection system
  • NFPA 101 17-3.4.2
  • Sleeping room smoke detectors are not required to
    initiate the building fire alarm system

36
Dormitory Detection Alarm
  • Occupant notification shall be provided
    automatically
  • NFPA 101 17-3.4.3.1
  • Immediate notification of the public fire
    department by telephone or other means
  • NFPA 17-4.3.2

37
Dormitory Detection Alarm
  • An approved, single-station smoke alarm is
    required to be installed in every guest room and
    every living area and sleeping room within a
    guest suite
  • The alarms are not required to be interconnected
  • Single-station smoke alarms without secondary
    power source are permitted
  • NFPA 10117-3.4.4.2

38
Dormitory Extinguishing Requirements
  • In buildings up to and including 4 stories NFPA
    13R sprinkler systems are permitted
  • NFPA 101 17-3.5.1
  • All high-rise (more than75 ft in height)
    buildings shall be protected throughout by an
    approved, supervised automatic sprinkler system
    installed in accordance with NFPA 13
  • NFPA 101 17-3.5.2

39
Dormitory Extinguishing Requirements
  • Portable fire extinguishers shall be provided in
    hazardous areas and throughout the building to
    NFPA 10
  • NFPA 101 17-3.5.3

40
Dormitory Corridors
  • Exit access corridor walls shall consist of fire
    barriers having a minimum of
  • ½-hour fire resistance rating
  • NFPA 101 17-3.6.1

41
Dormitory Corridor Doors
  • Doors that open onto exit access corridors shall
    have a minimum 20-min fire protection rating in
    accordance with 6-2.3
  • NFPA 101 17-3.6.2
  • Doors that open onto exit access corridors shall
    be self-closing and self-latching
  • NFPA 101 17-3.6.3

42
Dormitory Corridor Doors
  • Unprotected openings shall be prohibited in exit
    access corridor walls and doors
  • NFPA 101 17-3.6.4

43
Dormitory Corridor Doors
  • Transoms, louvers, or transfer grilles shall be
    prohibited in walls or doors of exit access
    corridors (see exceptions in code)
  • NFPA 101 17-3.6.5

44
Precautions Against Fire
  • Required fire doors and smoke barrier doors shall
    be maintained in good working order, including
    the hardware necessary for the proper operation
    thereof
  • Fire door assemblies shall not be modified
  • BOCA Fire Prevention Code - 303.4

45
Precautions Against Fire
  • Door stops, wedges and other unapproved hold-open
    devices are prohibited on fire doors
  • BOCA F-303.4.1
  • Swinging fire doors shall close from the
    full-open position and shall latch automatically
  • BOCA F-303.4.2

46
Precautions Against Fire
  • Horizontal or vertical sliding and rolling fire
    doors shall be inspected and tested at least
    annually by the owner or legal building
    representative

47
(No Transcript)
48
Precautions Against Fire
  • Swinging fire doors shall have a maximum undercut
    of ¾ inch
  • BOCA F-303.4.4
  • Glazing installed in fire doors is required to
    comply with the building code
  • BOCA F-303.4.5

49
(No Transcript)
50
Precautions Against Fire
  • All identified electrical hazards are required to
    be abated
  • BOCA F-310.1
  • Illumination is required for all service
    equipment areas, motor control centers and
    electrical panel boards
  • BOCA F-310.2

51
(No Transcript)
52
Precautions Against Fire
  • Clearance of not less than 30 inches shall be
    provide between all electrical service equipment
    and storage
  • BOCA 310.3
  • Multiplug adaptors, such as cube adaptors,
    unfused plug strips or any other device not
    complying with NFPA 70 is prohibited
  • BOCA 310.4

53
Precautions Against Fire
  • Extension cords and flexible cords shall not be a
    substitute for permanent wiring

54
Precautions Against Fire
  • Extension cords and flexible cords shall not be
    affixed to structures, extended through walls,
    ceilings or floors, or under doors or floor
    coverings, nor shall such cords be subject to
    environmental damage or physical impact
  • BOCA F-310.5

55
Precautions Against Fire
  • Open junction boxes and open-wiring splices are
    prohibited
  • Approved covers are to be provided for all switch
    and electrical outlet boxes
  • BOCA F-310.6

56
Precautions Against Fire
  • Electrical appliances and fixtures shall be
    tested and listed in published reports or
    inspected electrical equipment by an approved
    agency
  • BOCA F-310.7

57
(No Transcript)
58
Precautions Against Fire
  • All fire protection systems that were installed
    in compliance with any law, ordinance or order,
    shall be maintained in an operative condition at
    all times
  • BOCA F-504.1
  • All water sprinkler and water-spray extinguishing
    systems and standpipe systems shall be
    periodically inspected, tested, and maintained in
    accordance with the requirements of NFPA 25
  • BOCA F-506.1

59
Precautions Against Fire
  • A structure is not permitted to be altered in any
    manner that will reduce the number of means of
    egress or the capacity of the means of egress
    below that which was required for the structure
    when constructed
  • BOCA F-604.1

60
Precautions Against Fire
  • Structures shall not be occupied during repairs
    or alterations unless the required means of
    egress is maintained
  • BOCA F-604.2

61
Precautions Against Fire
  • The means of egress is required to be maintained
    in a safe condition and available for immediate
    utilization and free of obstructions at all times
  • BOCA F-605.1
  • Security devices affecting means of egress shall
    be subject to approval
  • BOCA F-605.1

62
Precautions Against Fire
  • An exit shall not be utilized for any purpose
    that interferes with its function as a means of
    egress
  • BOCA F-606.1
  • Combustible or flammable material is not to be
    placed, stored or kept in any portion of an exit,
    elevator car or hoistway, or at the bottom of a
    stairway
  • BOCA F-606.1.1

63
Precautions Against Fire
  • All means of egress doors shall be readily
    openable from the side from which egress is to be
    made without a key, special knowledge, or effort
  • BOCA F-608.1
  • All doors that could mistaken as a means of
    egress are to be identified as to use or
    identified as Not an Exit

64
Precautions Against Fire
  • A fire safety plan and evacuation procedure is
    required to be submitted and approved for every
    high-rise building
  • BOCA F-701.1

65
Precautions Against Fire
  • Decorations, furnishings and equipment impairing
    the visibility of egress sign are not permitted
  • BOCA F-610.5

66
Oklahoma State Fire Marshal 2401 N.W. 23rd
StreetSuite 4Oklahoma City, OK
73107405/522-5005
Write a Comment
User Comments (0)
About PowerShow.com