Title: General Guidelines
1INTERFACE TRANSFORMER WINDING CONFIGURATION
Pankaj Sharma, P. Eng. Sustainment Manager (PC
Planning) May 13th, 2009
1
2Topics to be Covered
- Importance
- Types
- DG Contribution to Utility System fault
- Temporary Over-voltage
- Summary
2
3Importance of DGIT Winding Connection
- Impacts Power Quality and Reliability
- Impacts Distribution System grounding
- Impacts total ground fault levels and
distribution of ground fault in-feeds - Impacts Protection System design
4Types of Winding Connections
- Star ground / star ground
- Star ground / star ungrounded
- Delta / star ground
- Star ground / delta
- Delta / delta
- Note
- All connections are in System / generator order
- System side Neutral must be effectively or low
impedance grounded
4
5STAR GROUND / star ground
- Advantages
- Standard utility transformer replacements
available - No voltage phase shift simple relaying and
fault detection - Ferro-resonance less probable
- Low TOV on distribution system (Dx) if Gen is
solidly gnd
- Disadvantages
- DG can feed any type of Dx faults
- May pass zero-sequence currents
- High TOV if Gen neutral is grounded thru high
impedance
Most common transformer (typically up to 500kVA)
connection in North America for load
distribution If Gen is solidly grounded ? IG
issues Generally Gen are grounded thru impedance
? TOV issue
5
6STARGROUND / starunground
- Advantages
- -- Inverters may require an ungrounded
connection on LV side - -- No passage for IG and also no IG source
- -- No voltage phase shift less vulnerable to
Ferro resonance
- Disadvantages
- -- High TOV on Dx
Not a common transformer connection
6
7DELTA / star ground
- Advantages
- Low DG contribution to Dx ground faults (via
ve and ve seq networks) - Does not pass zero sequence I, harmonics from
the DG are blocked - Primary SLG faults do not have severe impact
on the secondary voltages
- Disadvantages
- More difficult for generator protection to
detect SLG faults on Dx - Triplen harmonics from DG circulate in Delta
and low-impedance secondary neutral - Possible ferro-resonance and the need for 3Ø
switches on the primary side of transformer - High TOV on Dx
Second most common Xmer connection in North
America Most common transformer connection in
Europe High TOV on Dx can be mitigated by
connecting Grounding Xmer on HV side of the
DGIT For 3-Ø, 3-W Dx this connection is suitable
and preferred
7
8STAR GROUND / delta
- Advantages
- Primary Dx faults are easily detected by the
generators interconnection protection system - Blocks triplen harmonics from Gen
- Protection scheme is standardized based on
utility-owned generator protection systems - -- No TOV on Dx system if Xmer neutral is solid
or grounded through appropriately sized
reactor/resistor
- Disadvantages
- Source for ground fault current
- May cause sympathetic tripping of other
feeders during ground faults - Interferes with existing protection systems
and makes fuse saving impossible or extremely
difficult (if solidly grounded) - Transformer may overheat due to zero-sequence
currents
- Usual connection for generator transformers
- IG contribution has to be optimized by inserting
impedance in the neutral connection. - Low enough to reduce TOV to acceptable levels
- High enough to maintain feasible protection
schemes. - For 3-Ø, 4-W Dx system this connection is
preferred
8
9DELTA / delta
- Advantages
- Primary SLG faults not affected
- Low DG contribution to Dx ground faults (via
ve and ve seq networks) - Some inverters may require an ungrounded
connection - Could center-tap one-leg of delta secondary to
provide single- and three-phase service
- Disadvantages
- Ferro-resonance issues may require 3Ø switches
and protection on primary side - Detection of primary SLG faults is difficult
- Non-standard equipment for most utilities
- High TOV on Dx system
Uncommon connections but used in some industrial
facilities to reduce impact from SLG faults of
the system
9
10 TRANSFORMER CONNECTIONS AND ZERO SEQUENCE
CURRENTS
Xmer can pass I0 only if I0 circulates in
primary loop on the source side Secondary loop
(between Xmer and fault) is driven by this
loop Open loop results in Xmer unable to pass
I0
10
11(No Transcript)
12How to Restrict Ground Fault Contribution at HV
side
- By inserting Neutral Grounding Reactor (NGR)
between neutral of star connected HV winding and
ground - NGR needs to be carefully sized higher values
will reduce the ground current contribution but
increase the TOV - Optimize NGR such that TOV remains under 130
13Temporary Over-voltage (TOV)
- TOV is a fundamental frequency O/V associated
with - switching (for example load rejection)
nonlinearities (ferro-resonance effects,
harmonics) - ground faults (SLG faults)
- If the ratio of X0 / X1 is positive 1 System
is solidly grounded - 3 System is effectively grounded (TOV lt 130
of L-N voltage) - gt 3 System is no more suitable for 4-W
multi-grounded Dx
TOV vs. X0/X1 ratio
14How to Restrict TOV at HV side
- TOV at 3-Ø, 3-W Dx are not an issue (L-L rated
insulation) - TOV must be restricted to lt 130 in 3-Ø, 4-W Dx
to keep the system effectively grounded as surge
arrestors, 1-Ø Xmers rated for L-N volts and L-N
connected customers are all vulnerable to TOV - By connecting Grounding Xmers (GT) at HV side of
DGIT the TOV can be restricted to safe levels - GT must be sized for a) continuous current
rating and b) fault current rating (10 sec)
15SUMMARY
- There is no best winding connection which is
commonly suitable for all types sizes of DG - There is always a trade off in selection of
winding connection - IG contribution and TOV at PCC are two critical
aspects to be sincerely considered in selection - - ? on HV ?TOV issues ? mitigation ? Gnd
Xmer - - Star-gnd on HV ? IG constraint ? mitigation
NGR - Balance between IG TOV can be achieved by
appropriately sizing of Grounding Xmer
or Neutral Grounding Reactor (NGR)
T H A N K S ??? QUESTIONS ???