Title: One Machine
1One Machine Infinite Bus
- EE341 Energy Conversion
- Ali Keyhani
- Synchronous Machines
- lecture 3
2Infinite Bus
- Define of Infinite Bus infinite bus has the
following properties - Bus voltage will remain constant under any
loading - It has infinite capacity
- By definition, and infinite bus voltage is an
ideal voltage source.
3Infinite Bus
Problem 1
Power System
345/132 kV 10 100MVA T1
132/13.2 kV 10 50MVA T2
13.2kV/220V 5 10MVA T3
PL 500W lighting load rated at 220 volts
- For the load of 500W, which bus should be
considered as an infinite bus? - Assume load voltage is to be maintained at its
rated value, which bus should be considered as
infinite bus? - Problem 2 Assume the load is equal to 500W at
unity PF. Compute p.u equivalent circuit. - Assume Sb100 MVA, Vb 345 kV at high side of T1
4Infinite Bus
Assume Sb100 MVA, Vb 345 kV at high side of T1
345kV
j.10
j.20
j.50
220V
132kV
13.2kV
Sb 100 MVA
5A Generator Power Flow
Assume Sb100 MVA, Vb 345 kV at high side of T1
1-? Eq. CKT
Assume
6A Generator Power Flow
The complex power generated is
Note
7Synchronous Machine On An Infinite Bus
- Synchronous Motor
- Electrical power supplied
- Tem produced to support
- mechanical load (Tmech)
- b) Synchronous Generator
- Mechanical power supplied
- to the shaft
- Electrical power supplied to
- The network
Assume
Note
8Synchronous Machine On An Infinite Bus
- Synchronization Connecting
- A synchronous generator
- To a power system for
- synchronous operation. For
- synchronous operation, we
- Need to provide the following conditions
Circuit Breaker
- Electrical speed of synchronous generator should
be equal to the electrical speed of power system
generators - The terminal voltage of generator should be equal
to the V? bus and they must be in the same abc
sequence
With above conditions satisfied, the C.B.
(circuit breaker) can be closed. Synchronous
operation means parallel operation of synchronous
generators.
9?
Relationship Between and E
Consider a synchronous generator Assume
Pmech prime mover power
constant
Xs, E is determined by manufacturers
Adjust
(by changing Rf)
?
(this is called the excitation voltage)
10?
Relationship Between and E
In general
when
is reduced
decrease
If
Keep Pmech constant
increase
therefore
Keep Pmech constant, and reduce If till ?
reaches 90o
This is called pull-out power
If we reduce If further, Pelec will decrease and
? will increase. The machine will lose
synchronization when ?gt90o It means power
cannot be injected, and the external power will
drive the machine
11Operation of one machine - infinite bus
3
2
1
4
Pmech
5
6
Pelec
Computer control of generation is called
Automatic Generation Control (AGC)
12Operation of one machine - infinite bus
Consider a generator supplying power at a lagging
power factor to an infinite bus
(Inductive load)
Pmech
Assume
(ie ?mconst, Ifconst)
Overexcited generator is
operating with lagging power factor
13Operation of one machine - infinite bus
Overexcited Generator
Keep
?mconst
Reduce If to If, then EA will reduce to EA
That is the ? has to increase to ?
14Operation of one machine - infinite bus
Note also
That is IL will reduce to IL , and ? will
reduce to ?
However,
Conclusions By reducing If, the reactive power
generated by synchronous generator will be
reduced. However, the active power generated by
the generator will remain the same (
). However, the balance of generations and
loads will be maintained
15Operation of one machine - infinite bus
Suppose we reduce If such that ?0 (i.e. the
angle between V and I). That is,
dec
dec
dec
dec
Generator operation with unity power factor
Conclusions By reducing If, we can operate the
machine with unity power factor while generating
the same active power. However reactive power
generated by the machine will reduce to
zero. Note Computer control of generation will
control all generators such that
16Operation of one machine - infinite bus
Underexcited Generator Operation Suppose we
reduce If such that ?gt0 (i.e. IL would lead V?)
dec
dec
inc
inc
Underexcited generator
Conclusions By reducing Ifsuch that ?gt0 leading,
we can operate the generator with leading power
factor while generating the same active power.
Note Computer control of generation will
control all generators such that
17Problems
- Problem 1 A 13.8-kV 10-MVA 0.8-PF-lagging 60 Hz
two-pole Y-connected steam turbine generator has
a synchronous reactance of 18 ? per phase and an
armature resistance of 2 ? per phase. This
generator is operating in parallel with a large
power system (infinite bus). Answer the following
questions about this generator. - What is the magnitude of EA at rated conditions?
- What is the torque angle of the generator at
rated conditions? - If the field current is constant, what is the
maximum power possible out of this generator? How
much reserve power or torque does this generator
have at full load? - At the absolute maximum power possible, how much
reactive power will this generator be supplying
or consuming? Sketch the corresponding phasor
diagram. (Assume IF is still unchanged).
18Problems
2j18
2j18
13.8-kV 10-MVA 0.8-PF-lagging P2
a)
b)
19Problems
c) Ignoring RA, the maximum output power of the
generator is given by
d) The resulting reactive power produced by the
generator is
20Problems
- Problem 2 A 100-MVA 11.8-kV 50-Hz two-pole
Y-connected synchronous generator has a per-unit
synchronous reactance of 0.8 and a per0unit
armature resistance of 0.012. (pf0.85 lagging.) - What is its synchronous reactance and armature
resistance in ohms? - What is the magnitude of the internal generated
voltage EA at the rated conditions? What is its
torque angle ? at these conditions? - Ignoring losses in this generator, what torque
must be applied to its shaft be the prime mover
at full load?
21Problems
a)
.012j.8
S1 pu pf .85 lagging
b)
In pu
or
22Problems
c)
23Problems
- Problem 3 A three-phase Y-connected synchronous
generator is rated 120 MVA, 13.2 kV, 0.8 PF
lagging, and 60 Hz. Its synchronous reactance is
0.7 ?, and its resistance may be ignored. - What is its voltage regulation?
- What would the voltage and apparent power rating
of this generator be if it were operated at 50 Hz
with the same armature and field losses as it had
at 60 Hz? - What would the voltage regulation of the
generator be at 50 Hz?
24Problems
a)
j.7
pf.8 lagging
25Problems
b) Since the voltage produced by a generator is
directly proportional to speed, the voltage (and
hence the apparent power) rating of the generator
will be reduced by a factor of 5/6
c) At 50 Hz rated conditions, Note that the
synchronous reactance is also reduced by a factor
of 5/6, since reactance is a function of
frequency. The voltage regulation is