Title: ELECTRICAL HAZARDS
1ELECTRICAL HAZARDS
2ELECTRICAL HAZARDS
- SHOCK. Electric shock occurs when the human body
becomes part of the path through which current
flows. - The direct result can be electrocution.
- The indirect result can be injury resulting from
a fall or movement into machinery because of a
shock
3ELECTRICAL HAZARDS
- BURNS. Burns can result when a person touches
electrical wiring or equipment that is energized. - ARC-BLAST. Arc-blasts occur from high- amperage
currents arcing through the air. This can be
caused by accidental contact with energized
components or equipment failure.
4ELECTRICAL HAZARDS
- ARC-BLAST. The three primary hazards associated
with an arc-blast are - Thermal radiation.
- Pressure Wave.
- Projectiles.
5ELECTRICAL HAZARDS
- EXPLOSIONS. Explosions occur when electricity
provides a source of ignition for an explosive
mixture in the atmosphere.
6ELECTRICAL HAZARDS
- FIRES. Electricity is one of the most common
causes of fires both in the home and in the
workplace. Defective or misused electrical
equipment is a major cause.
7EFFECTS ON THE HUMAN BODY
- Depends on
- Current and Voltage
- Resistance
- Path through body
- Duration of shock
8Effects of AC Electricity
- More than 3 mA- Painful shock- cause indirect
accident - More than 10 mA- Muscle contraction No Let Go
danger - More than 30 mA- Lung paralysis, usually
temporary
9Effects of AC Electricity
- More than 50 mA- Ventricular fibrillation,
usually fatal - 100 mA to 4 A- Certain ventricular fibrillation,
fatal - Over 4 A- Heart paralysis, severe burns
101910.303(b)Examination of equipment
- Electrical equipment must be free of recognized
hazards that are likely to cause death or serious
physical harm to employees.
111910.303(b)Examination of equipment
- Safety of equipment must be determined using the
following considerations - Suitability for installation and use
- Mechanical strength and durability
- Electrical insulation
- Heating effects under conditions of use
121910.303(b)Examination of equipment
- Safety of equipment must be determined using the
following considerations - Arcing effects
- Classification by type, size, voltage, current
capacity and specific use - Other factors
131910.303(c)Splices
- Conductors must be spliced with
- Splicing devices suitable for the use
- Brazing, welding or soldering (with a
mechanically and electrically secure joint before
soldering then soldered)
141910.303(c)Splices
- All splices and joints and the free ends of
conductors must be covered with an insulation
equivalent to that of the conductors or with an
insulating device suitable for the purpose.
151910.303(e)Marking
- Electrical equipment may not be used unless the
manufacturers name, trademark or other
identification is on the equipment.
161910.303(e)Marking
- Other markings must be provided giving voltage,
current, wattage, or other ratings as necessary. - Markings must be durable enough to withstand the
environment.
171910.303(f)Identification
- Each disconnecting means must be legibly marked
to indicate its purpose, unless located and
arranged so that its purpose is evident.
181910.303(f)Identification
- These markings must be durable enough to
withstand their environment.
191910.303(g)(1)600 volts, nominal, or less
- Working space about electrical equipment.
- This section refers to a person qualified to work
on electrical equipment, usually an electrician.
201910.303(g)(1)(i)Working clearances
- Except as required or permitted, the dimension of
the working space in front of live parts
(operating at 600 volts or less) and likely to
require examination, adjustment, servicing, or
maintenance must be at least three feet.(See
table S-1).
211910.303(g)(1)(i)Working clearances
- The workspace in front of electrical equipment
must not be less than 30 inches wide.
221910.303(g)(1)(ii)Working clearances
- Working spaces required for this standard may not
be used for storage.
231910.303(g)(2)600 Volts or less
- Guarding of live parts operating at 50 Volts or
more. - The purpose of this requirement is to protect
any person who is in the vicinity of electrical
equipment against accidental contact, not just
electricians.
241910.303(g)(2)600 Volts or less
- Guarding of live parts.
- Guard against accidental contact by
- Location accessible only to qualified persons
- Permanent, substantial partitions or screens
251910.303(g)(2)600 Volts or less
- Guarding of live parts.
- Guard against accidental contact by
- (C) Location on a suitable elevated balcony or
platform - (D) Elevation of 8 feet or more above the floor
or other working surface
261910.303(g)(2)600 Volts or less
- Guardian of live parts.
- In locations where electrical equipment would be
exposed to physical damage, enclosures or
guardians must be so arranged and of such
strength as to prevent such damage.
271910.303(h)(3)Over 600 Volts
- Workspace around equipment.
- Sufficient space must be provided and maintained
around electrical equipment to permit ready and
safe operation and maintenance.
281910.303(h)(3)(ii)Illumination (Over 600 Volts)
- Adequate illumination must be provided for all
working spaces around electrical equipment. - The lights and switches must be arranged so that
persons making repairs or turning on lights wont
contact live ports.
291910.303(h)(3)(iii)Elevation of unguarded live
parts
- Unguarded live parts above working space must be
maintained at elevations not less than specified
in Table S-3. - The minimum is 8 feet.
301910.304(a) Grounded and grounding conductors
- Identification of conductors.
- The grounded conductor is an energized circuit
conductor that is connected to earth through the
system ground. It is commonly referred to as the
neutral.
311910.304(a) Grounded and grounding conductors
- Identification of conductors.
- The equipment grounding conductor is not an
energized conductor under normal conditions. It
is energized only if there is a leak or fault in
the normal current path and directs current back
to the source.
321910.304(a) Grounded and grounding conductors
- Identification of conductors.
- The National Electric Code requires that
- The grounded conductor (neutral) be continuous
white or natural gray. - The equipment grounding conductor be green, green
with yellow stripes or bare.
33 1910.304(a)(2)Polarity of connections
- No grounded conductor may be attached to any
terminal or lead so as to reverse designated
polarity.
34 1910.304(a)(2)Polarity of connections
- Reversed polarity is a condition when neutral
conductor is incorrectly connected to the hot
terminal of a plug, receptacle or other connector.
35 1910.304(e)Overcurrent protection
- 600 volts or less.
- (i) Conductors and equipment must be protected
from overcurrent.
361910.304(e)Overcurrent protection
- 600 volts or less.
- Fuses and circuit breakers are designed to
disconnect a circuit from its supply source when
a maximum allowable heat is reached.
371910.304(e)Overcurrent protection
- 600 volts or less
- (iv) Location. Overcurrent devices must be
readily accessible but not located where they
will be exposed to physical damage or in the
vicinity of easily ignitable material.
381910.304(f)Grounding
- (4) Grounding path.
- The path to ground from circuits, equipment, and
enclosures must be permanent and continuous
391910.304(f)Grounding
- (5)(v) Tools likely to be used in wet and
conductive locations need not be grounded if
supplied through an isolating transformer with an
ungrounded secondary of not over 50 volts.
401910.304(f)Grounding
- (5)(v) Listed or labeled portable tools and
appliances protected by an approved system of
double insulation, or its equivalent, need not be
grounded. However, they must be distinctively
marked.
41Electrical ToolsDouble Insulated
- They work with GFCIs
- Casing must be labeled
- Tool must be inspected
- Extension cord must be three-prong
421910.305(a)Wiring methods.
- General requirements.
- (ii) No wiring system of any type shall be in
ducts used to transport dust, loose stock or
flammable vapors, or used for vapor removal or
ventilation of commercial-type cooking equipment.
431910.305(a)Wiring methods.
- (2) Temporary wiring.
- Temporary electrical power and lighting wiring
may be of a class less than would be required for
a permanent installation.
441910.305(a)Wiring methods.
- (2) Temporary wiring.
- Uses permitted, 600 volts or less.
- (A) During and for remodeling, maintenance
repair, or demolition or similar activities.
451910.305(a)Wiring methods.
- Uses permitted, 600 volts or less.
- (B) For experimental or developmental work
- (C) For a period not to exceed 90 days for
Christmas decorative lighting, carnivals, and
similar purposes.
461910.305(a)Wiring methods.
- (2) Temporary wiring.
- Uses permitted, over 600 volts.
- Only during tests, experiments and emergencies.
471910.305(a)Wiring methods.
- (F) Lamps for general illumination must be
protected from accidental contact or breakage. - Protection can be provided by an elevation of 7
feet or by a suitable fixture with a guard.
481910.305(a)Wiring methods.
- (G) Flexible cords and cables must be protected
from accidental damage.Sharp corners or
projections must be avoided. - Protection must be provided when passing through
doorways or other pinch points.
491910.305(b)(1)Conductors entering boxes,
cabinets, or fittings.
- Conductors entering boxes, cabinets, or fittings
must be protected from abrasion. - Unused openings in cabinets, boxes, and fittings
must be effectively closed.
501910.305(b)(2)Electrical box covers
- All pull boxes, junction boxes, and fittings must
be provided with approved covers. - Metal covers must be grounded.
511910.305(b)(2)Electrical box covers
- Outlet boxes must have a cover or a faceplate.
- Outlet box covers with holes for flexible cords
must bushings or smooth, well- rounded surfaces.
521910.305(d)Switchboards and panelboards.
- Panelboards must be mounted in approved cabinets
or boxes and must be dead front. - Others are accessible only to qualified persons.
531910.305(g)(1)(i)Flexible cords and cables.
- Allowed uses
- Pendants
- Wiring fixtures
- Portable lamps or appliances
- Elevator cables
- Wiring cranes or hoists
541910.305(g)(1)(i)Flexible cords and cables.
- Allowed uses
- Connect stationary equipment to facilitate
frequent interchange - Prevent transmission of noise or vibration
- For removal for maintenance/repair
551910.305(g)(1)(iii)Flexible cords and cables.
- May not be used
- As a substitute for the fixed wiring of a
structure. - Where run through holes in walls, ceilings or
floors.
561910.305(g)(1)(iii)Flexible cords and cables.
- May not be used
- Where run through doorways, windows, or similar
openings - Where attached to building surfaces
- Where concealed behind building walls, ceilings,
or floors.
571910.305(g)(2)Flexible cords and cables.
- (ii) Flexible cords must be used only in
continuous lengths without splice or tap.
581910.305(g)(2)Flexible cords and cables.
- (ii) Hard service flex cords, No. 12 or larger,
may be repaired if spliced so that the splice
retains the insulation, outer sheath properties,
and usage characteristics of the original cord.
591910.305(g)(2)Flexible cords and cables.
- (iii) Flexible cords must be connected to devices
and fittings so that strain relief is provided
which will prevent pull off from being directly
transmitted to joints or terminal screws.
601910.305(j)Equipment for general use.
- (2)(ii) A receptacle installed in a wet or damp
location must be suitable for the location.
611910.307Hazardous (classified) locations.
- (b) Electrical installations.
- Equipment, wiring, and installations of equipment
in hazardous (classified) locations must be
intrinsically safe, approved for the location, or
safe for the location.
62Hazardous LocationsClass I locations
- Locations in which flammable gasses or vapors are
or may be present in the air in quantities
sufficient to produce explosive or ignitable
mixtures.
63Hazardous LocationsClass I, Division 1
- Location in which hazardous concentrations of
flammable gases or vapors may exist - Under normal operating conditions
- Because of repair or maintenance operations or
leakage - Because of breakdown or faulty operation
64Hazardous LocationsClass I, Division 2
- Location in which flammable gases or vapors are
- Normally confined within closed containers or
systems - Normally kept below hazardous concentrations by
ventilation - Normally kept below hazardous concentrations by
positive-pressure ventilation (adjacent to
Division 1)
65Hazardous LocationsClass II Locations
- Locations which are hazardous because of the
presence of combustible dust.
66Hazardous LocationsClass II, Division 1
- Location where combustible dust may be present
due to - Normal operations
- Mechanical failure or abnormal operation of
machinery or equipment - combustible dust of an electrically conductive
nature may be present.
67Hazardous LocationsClass II, Division 2
- Location where
- Combustible dust will not normally be in
suspension in ignitable quantities - Dusts may be in suspension as a result of an
infrequent malfunction of handling or processing
equipment.
68Hazardous LocationsClass III Locations
- Locations that are hazardous because of the
presence of easily ignitable fibers or flyings
but in which such fibers or flyings are not
likely to be in suspension in the air in
quantities sufficient to produce ignitable
mixtures.
69Hazardous LocationsClass III, Division 1
- Locations in which easily ignitable fibers or
materials producing combustible flyings are
handled, manufactured or used.
70Hazardous LocationsClass III, Division 2
- Location in which easily ignitable fibers are
stored or handled, except in the process of
manufacture.
711910.331 - .335Electrical Safe Work Practices
- Covers work practices rather than electrical
equipment and installations. - This should be a part of your Lockout/Tagout
program
72Electrical Protective Equipment29 CFR1910.137
(59 FR 4435)
- Design Requirements
- In-service Care and Use
73Electrical Protective Equipment29 CFR1910.137
(59 FR 4435)
- (a)Design Requirements
- Insulating blankets,matting, covers, line hose,
gloves, and sleeves made of rubber shall meet
specified requirements for manufacture, marking,
electrical properties, workmanship and finish.
74(b) In-service Care and Use
- Electrical protective equipment shall be
maintained in a safe, reliable condition. - Specific requirements for in-service care and use
are given for insulating blankets, covers, line
hose, gloves, and sleeves made of rubber.
75Qualified Employee(Qualified Person)
- One knowledgeable in the construction and
operation of the electric power generation,
transmission, and distribution equipment
involved, along with the associated hazards.
76Qualified Employee(Qualified Person)
- Must have the training required by
paragraph(a)(2)(ii). - Has undergone on-the-job training and has
demonstrated an ability to perform duties safely
under the direct supervision of a qualified
person.
77- One employee was climbing a metal ladder to
hand an electric drill to the journey installer
on a scaffold about five feet above him. When the
victim reached the third rung from the bottom of
the ladder he received an electric shock that
killed him.
78- The employee was attempting to correct an
electrical problem involving two non-operational
lamps. He proceeded to the area where he thought
the problem was. He had not shut off the power at
the circuit breaker panel nor had he tested the
wires to see if they were live. He was
electrocuted when he grabbed the two live wires
with his left hand and then fell from the ladder.