Title: Installing and Operating a System
1Installing and Operating a System
- System connections
- Signal delay calculation
- Programming the Transmitter
- Testing the reception quality
IO Manual
2Connecting the DCN Next Generation system
- The transmitter can be directly connected to the
optical network of the DCN Next Generation
conference system by means of an optical network
cable - Network mode must be enabled
3Connecting the DCN system
- The transmitter requires the DCN Interface Module
- The connections between DCN units and the
transmitter are made in a loop-through
configuration.
4DCN interface module
- For interfacing with DCN
- Allows simultaneous interpretation generated by
DCN - LBB3423/20
5Connecting the CCS800 and Interpreter desks
- The transmitter requires the Symmetrical Audio
Input and Interpreters Module. - Up to 12 6-Channels interpreter desks can be
loop-through connected to the module. - The floor signal for the interpreters desk is
connected to the Aux-Left input of the
transmitter. - The floor signal from a CCS 800 discussion system
line output or from an external audio source,
such as an audio mixer.
6Symmetrical Audio Input Module
- For use with analogue audio systems with 8
symmetrical Inputs - Up to 12 6-Channels interpreter desks LBB3222/04
- Automatic floor selection for unused
interpretation channels - LBB3422/20
7Symmetrical Audio Input Module
8Settings on the Audio Input Module
- Floor audio connection from CPSU line output to
Aux. input of infra-red transmitter
9Maximum cable length to interpreters desks
- Maximum Up to 12 6-Channels interpreter desks
can be loop-through connected to the module.
10Interface connection to Recording System
LBB3422/20 Symmetrical Audio Input Module
LBB3222/04 6-Channel Interpreters Desk
To be made locally
To recording system
11Connecting other external audio sources
- The audio signals (stereo or mono) are connected
to the audio input cinch connectors. - When the cinch audio inputs are used in
combination with inputs via one of the
interface modules, the signals on
corresponding channels are mixed.
12Connecting an emergency signal switch
- To use the emergency signal function, a switch
(normally-open) must be connected to the
emergency switch connector. - When the switch is closed, the audio signal on
the Aux-right input is distributed to all output
channels, overriding all other audio inputs. - The Aux. Input mode of the transmitter must be
set to Mono Emergency
13Connecting to another transmitter
- The transmitter can operated in slave mode to
loop-through the IR radiator signals from a
master transmitter. - One of the six radiator outputsof the master
transmitter is connected with an RG59 cable to
the radiator signal loop-through input of the
slave transmitter. - The Transmission mode of the slave transmitter
must be set to Slave
14Connecting radiators to transmitter
- The transmitter has six BNC connectors on the
rear panel. They can each drive up to 30
radiators in a loop-through configuration. - The radiators are connected with RG59 cables (75
Ohm). - The maximum cable length per output is 900 m.
- Automatically cable termination by a built-in
detection circuit.
15Connecting radiators to transmitter
- Notes
- Never leave an open-ended cable connected to the
last radiator in a loop-through chain. - When connecting infra-red radiators, do not split
the cable, else the system will not function
correctly.
16Signal delay calculation
- Setting the radiator delay compensation switches
- Differences in cable length between the
transmitter and the radiators can cause black
spots as a result of the multipath effect. - The IR signal from a radiator with a long cable
is delayed with respect to the signal from a
radiator with a shorter cable. - To compensate these cable length differences, the
delay of a radiator can be increased to make it
equal to the signal delay of the other radiators. - This signal delay can be set with delay switches
at the back of the radiator.
17Signal delay calculation
- Two ways for determining delay compensation
switch positions of the radiator. - By measuring the cable lengths
- 1.1 Manual
- 1.2 delay switch calculation tool (recommended)
- By using a delay measuring tool
- 2.1 Manual
- 2.2 delay switch calculation tool (recommended)
18Signal delay calculation 1.1
- To determine the delay switch position based on
cable lengths and calculating manually follow the
next steps - Measure the lengths of the cables between the
transmitter and each radiator. - Multiply these cable length differences with the
cable signal delay per meter (the manufacturer
specified factor). This is the cable signal delay
difference for that radiator. - Determine the maximum signal delay.
- Calculate for each radiator the signal delay
difference with the maximum signal delay. - Divide the signal delay difference by 33. The
rounded off figure is the signal delay switch
position for that radiator. - Set the delay switches to the calculated switch
positions.
Cable Measuring
19Signal delay calculation 1
20Signal delay calculation 1.2
- To determine the delay switch position based on
cable lengths and the delay switch calculation
tool follow the next steps - Start the calculation tool
- Select system type
- Fill-in the cable signal delay per meter of the
used cable. (specified by the cable
manufacturer). - Fill-in the number of radiator(s) on each output
- Fill-in the measured cable lengths of the cables
between the transmitter and each radiator. - Set the delay switches on the radiator(s) to the
automatically calculated switch positions.
Calculation tool
21Signal delay calculation 2.1
- To determine the delay switch position by delay
measuring tool and calculating manually follow
the next steps - Disconnect the cable from a radiator output of
the transmitter and connect this to a delay
measurement tool. - Disconnect the cable from the first radiator in
that trunk. - Measure the impulse response time (in ns) of the
cable(s) between that transmitter and the
radiator. - Reconnect the cable to the radiator and repeat
steps 2 to 4 for the other radiators (started by
the next radiator in that trunk). - Reconnect the cable to the transmitter and repeat
step 2 to 5 for the other radiator outputs of the
transmitter. - Divide the impulse response times for each
radiator by two. These are the cable signal
delays for each radiator.
22Signal delay calculation 2.1
- Determine the maximum signal delay.
- Calculate for each radiator the signal delay
difference with the maximum signal delay. - Divide the signal delay difference by 33. The
rounded off figure is the delay switch position
for that radiator. - Set the delay switches to the calculated switch
positions.
Delay Measuring
23Signal delay calculation 2.2
24Signal delay calculation 2.2
- To determine the delay switch position by delay
measuring tool and the delay switch calculation
tool the follow the next steps - Start the calculation tool, Select system type,
Fill-in the number of radiator(s) on each output - Disconnect the cable from a radiator output of
the transmitter and connect this to a delay
measurement tool. - Disconnect the cable from the first radiator in
that trunk. - Measure the impulse response time (in ns) of the
cable(s) between that transmitter and the
radiator. - Enter this impulse response time in the
calculation tool. - Reconnect the cable to the radiator and repeat
steps 2 to 4 for the other radiators (started by
the next radiator in that trunk).
Calculation tool
25Signal delay calculation 2.2
- Reconnect the cable to the transmitter and repeat
step 2 to 5 for the other radiator outputs of the
transmitter. - When the cable signal delays are known, the delay
switch calculation tool will calculate the delay
switch positions automatically.
Calculation tool
26Signal delay calculation with more transmitters
- When radiators in one multi purpose room are
connected to two transmitters, an extra signal
delay is added by - Transmission from master transmitter to slave
transmitter (cable signal delay). - Transmission through the slave transmitter.
Calculation tool
27Signal delay calculation with more transmitters
- For calculating the delay switch positions for a
system with a master-slave configuration, use the
following procedure - Calculate the cable signal delay for each
radiator, using the procedures for a system with
one transmitter. - Calculate the signal delay of the cable between
the master and the slave transmitter in the same
way as for cables between a transmitter and a
radiator. - Add to the cable signal delay of the cable
between the master and the slave, the delay of
the slave transmitter itself 33 ns. This gives
the master-to-slave signal delay. - Add the master-to-slave signal delay to each
radiator connected to the slave transmitter. - Determine the maximum signal delay.
Calculation tool
28Signal delay calculation with more transmitters
- Calculate for each radiator the signal delay
difference with the maximum signal delay. - Divide the signal delay difference by 33. The
rounded off figure is the signal delay switch
position for that radiator. - Set the delay switches to the calculated delay
switch positions.
Calculation tool
29Signal delay calculation with more transmitters
50m
Tx Slave
Tx Master
30Signal delay calculation with more transmitters
31Radiation signal delay
- A situation in which a radiation signal delay
occurs. - For systems with more than four carriers, add one
delay switch position per 10 meter difference in
signal path length to the radiators which are
closest to the overlapping coverage area. - In this Figure the signal path length difference
is 12 meter. Add one delay switch position to the
calculated switch position(s) for the radiator(s)
under the balcony.
Calculation tool
32Transmitter menu structure
IO Manual
33Transmitter menu structure
IO Manual
34Transmitter menu structure
IO Manual
35Transmitter menu structure
IO Manual
36Testing the reception quality
- An extensive reception quality test must be done
to make sure that the whole area is covered with
IR radiation of adequate strength. Such a test
can be done during installation and during the
meeting - Test during installation
- Check that all radiators are connected and
powered up and that no loose cables are connected
to a radiator. Switch the transmitter off and on.
(needed for the auto signal equalisation) - Set the transmitter in the Test-mode. For each
channel a different frequency test tone will be
transmitted. - Set a receiver on the highest available channel
and listen via the headphones to the transmitted
test tone. - For testing all positions follow the instruction
of chapter 1.6 of the Integrus Installation and
Operating Instructions
37Testing the reception quality
- Testing during the meeting
- Set a receiver in the Test-mode and select the
highest available carrier. The quality of the
received carrier signal is indicated on the
display of the receiver. - The quality indication should be between 00 and
39 (good reception). - For testing all positions follow the instruction
of chapter 1.6 of the Integrus Installation and
Operating Instructions
38Installing and Operating a System
Integrus menu