Title: STATE ESTIMATOR QUALITY TRACKING IN BC Hydro EMS IMPLEMENTATION
1STATE ESTIMATOR QUALITY TRACKING IN BC Hydro EMS
IMPLEMENTATION
- Dr. DJORDJE ATANACKOVIC, P.Eng.
- Engineering Team Leader, Power system
Applications, Grid Operations Support
2STATE ESTIMATOR GENERAL PERFORMANCE REQUIREMENTS
- CONVERGENCE SUCCESS RATE OF 98
- COST FUNCTION IN THE RANGE OF 8000 11000
(2500 BUSES, 4000 ANALOG MEASUREMENTS) - TOTAL GENERATION ERROR lt 40 MW
- TOTAL INTERCHANGE ERROR lt 10MW
- MAX. MW BUS MISMATCH lt 50MW
- TOTAL LOAD ALLOCATION ERROR lt 400MW
3STATE ESTIMATOR QUALITY MONITORING NEW INDICES
- TOTAL LOAD ALLOCATION ERROR
- TOTAL MW, MVAR LINE FLOW RESIDUAL PER MEASUREMENT
- TOTAL MW, MVAR INJECTION RESIDUAL PER MEASUREMENT
- TOTAL VOLTAGE AND CURRENT RESIDUAL PER
MEASUREMENT
4STATE ESTIMATOR QUALITY MONITORING TOTAL LOAD
ALLOCATION ERROR
- CALCULATED AS A SUM OF LOAD RESIDUALS FOR ALL
LOADS IN BC HYDRO AREA - LOAD RESIDUAL IS A DIFFERENCE BETWEEN ESTIMATED
LOAD AND ALLOCATED LOAD - BC HYDRO PERFORMANCE CRITERIA
- TOTAL LOAD ALLOCATION ERROR SHOULD NOT EXCEED 600
MW MAXIMUM - AVERAGE LOAD ALLOCATION ERROR OVER A PERIOD OF
ONE YEAR SHOULD NOT EXCEED 400 MW
5STATE ESTIMATOR QUALITY MONITORING TOTAL MW,MVAR
LINE FLOW RESIDUAL PER MEASUREMENT
- CALCULATED AS A SUM OF MW/MVAR LINE FLOW
RESIDUALS FOR ALL MEASUREMENTS IN THE CONSIDERED
ZONE DIVIDED BY NUMBER OF MEASUREMENTS - THREE ZONES ARE USED FOR THIS TRACKING
- TRANSMISSION (230 KV AND ABOVE)
- SUBTRANSMISSION (60 138KV)
- DISTRIBUTION (BELOW 60 KV)
- BCTC PERFORMANCE CRITERIA FOR A PERIOD OF ONE
YEAR - TRANSMISSION - BELOW 7 MW
- SUBTRANSMISSION - BELOW 15 MW
- DISTRIBUTION - BELOW 20 MW
-
6STATE ESTIMATOR QUALITY MONITORING TOTAL MW,MVAR
INJECTION RESIDUAL PER MEASUREMENT
- CALCULATED AS A SUM OF ALL INJECTION RESIDUALS IN
A CONSIDERED ZONE DIVIDED BY NUMBER OF
MEASUREMENTS IN THE ZONE - BCH PERFORMANCE CRITERIA FOR A PERIOD OF ONE
YEAR - TRANSMISSION BELOW 3 MW
- SUBTRANSMISSION - BELOW 7 MW
- DISTRIBUTION - BELOW 10 MW
7STATE ESTIMATOR QUALITY MONITORINGNORMALIZED
RESIDUALS
- ENABLES RANKING OF MEASUREMENTS OF DIFFERENT
TYPES (MW, MVAR, AMPS, KV) BASED ON A NORMALIZED
INDEX - BCH PERFORMANCE CRITERION
- NORMALIZED RESIDUAL GREATER THAN 10 UNITS
INDICATES A MEASUREMENT OF A LOWER QUALITY - NEEDS IMPROVEMENT DOES NOT REFLECT ERRORS OF
GENERATOR UNIT MEASUREMENT AND OTHER INJECTION
MEASUREMENTS
8STATE ESTIMATOR QUALITY MONITORINGCONSISTENCY OF
VOLTAGE STABILITY REGION
9STATE ESTIMATOR PERFORMANCE TRACKING
- TRACK SOLUTION QUALITY INDICES IN PI
- IMPROVE ONLINE SEQUENCE DISPLAY TO INCLUDE ALERT
SIGNALS (FLASHING APPLICATION STATUS BOXES) - MONITOR IMPACT ON OTHER APPLICATIONS E.G. VSA
- PERFORM REGULAR REAL TIME TELEMETRY QUALITY
ANALYSIS AND PRODUCE TELEMETRY QUALITY REPORTS - ISSUE TELEMETRY CALIBRATION REQUESTS
- RTNET SOLUTION INVALIDATED IF QUALITY MEASURES
OUTSIDE PERFORMANCE LIMITS
10BASIC QUALITY INDICES
11AVERAGE MEASUREMENT RESIDUALS
12(No Transcript)
13(No Transcript)
14(No Transcript)
15(No Transcript)
16(No Transcript)
17QUESTIONS?