GENERAL - PowerPoint PPT Presentation

1 / 1
About This Presentation
Title:

GENERAL

Description:

GENERAL DIMENSION(unit : mm) FND Display Power LED Standby LED Trouble LED Alarm 3 LED Bar graph LED Alarm 2 LED Test switch Alarm 1 LED Buzzer stop switch – PowerPoint PPT presentation

Number of Views:40
Avg rating:3.0/5.0
Slides: 2
Provided by: cize
Category:
Tags: general | modbus

less

Transcript and Presenter's Notes

Title: GENERAL


1
GENERAL
DIMENSION(unit mm)
FND Display
Power LED
Standby LED
Trouble LED
Alarm 3 LED
Bar graph LED
Alarm 2 LED
Test switch
Alarm 1 LED
Buzzer stop switch
Buzzer
Mount Hole
Rest switch
ACCESORIES
RS-485 Communication Module
GTC-520A
SPECIFICATION
SINGLE-CHANNEL TYPE GAS DETECTOR RECEIVER GTC-520A SERIES
Model GTC-520A
Operation display 6-LED (Power, 3-stage alarm, Trouble, Stand-by for maintenance)
Measuring display 4-Digit FND Bar-Graph(32 Segment, 3-color LED)
Measuring range 19999 (programmable) / LEL, ppm, Vol
Alarm display Visual 3-stage alarm, Trouble LEDs Audible buzzer
Alarm output signal 3-Stage Alarm, Trouble / AC250V 5A relay contact (SPDT) Shut-off Valve control signal (DC 12V)
Alarm level set Programmable with in detection range
Input signal 4-20mA DC (2-wire or 3-wire)
Output signal 4-20mA DC Isolated RS-485 Communication Modbus(option)
Reset signal Reset switch and remote control
Program set mode -Alarm value (1, 2, 3 alarm) -Alarm time (instant delay) 130min -Alarm dead band -Relay output on / off
Operating temperature -20? 60?
Operating humidity 5 99 RH (non-condensing)
Operating power AC 90V250V / 63W Max 24V DC
Dimensions 135x180x81 (WxHxD)mm
Weight 0.6kg
?Specifications are subject to be changed without
prior notice.