Title: GRPE ISO GROUP MEETING, MUNICH, JANUARY 22th, 2003
1- GRPE ISO GROUP MEETING, MUNICH, JANUARY 22th, 2003
GAS CYLINDERS USE OF PRESSURE RELIEF DEVICES
Hervé BARTHELEMY AIR LIQUIDE PARIS
2PRD FIRE PROTECTION
- ISO/CD/15869-1 REQUIRES USE OF THERMALLY
- ACTIVATED PRD
- This type of PRD is the only one which allows
gas pressure - release in case of fire even at low pressure
- Some fully wrapped cylinders behave very badly
during - standard bonfire tests if not protected with PRD
3CYLINDER CARBON FIBER - PLASTIC LINER
SERVICE PRESSURE 3 000 PSI
4CYLINDER CARBON FIBER - PLASTIC LINER
SERVICE PRESSURE 3 000 PSI
- FRAGMENTATION
- AFTER 100 s
- EXPOSURE TO
- STANDARD
- BONFIRE TEST
5PRD FIRE PROTECTION
- SITUATION WITH INDUSTRIAL CYLINDERS
- (SINGLE, BUNDLE/PACK OR ON TRAILER)
- Several millions are in used
- In Europe PRD not required by regulation and
not used
- In North America PRD required by regulation.
For H2, - the industry decides to use bursting disk back
up with a - fusible plug (to avoid unexpected release of
gas)
6RISK ANALYSIS
TWO RISKS SHALL BE CONSIDERED
- IN CASE OF FIRE / RISK OF CYLINDERS BURST
- SHORTLY AFTER THE FIRE
- RISK OF GAS RELEASE H2 IS EXTREMELY
- FLAMMABLE
The flammability range of H2 in air is much
bigger than CH4
H2 70,5 (LFL 4 UFL 74,5 )
CH4 10 (LFL 5 UFL 15 )
The minimum energy for igniting H2 in air is 10
times lower than CH4
7ACCIDENT WITH AN HYDROGEN BUNDLE (1985)
LEAK DUE TO FAILURE OF A NUT
8ACCIDENT WITH AN HYDROGEN BUNDLE (1985)
VUE OF THE FIRE DAMAGE
THE FILLING CENTER WAS SEVERELY BURNED
9ACCIDENT IN STOCKHOLM (1983) HYDROGEN LEAK
THE EXPLOSION CONSECUTIVE TO THE HYDROGEN LEAK
LEADS TO SEVERE DESTRUCTION IN A BIG AVENUE
10ACCIDENT IN STOCKHOLM (1983) HYDROGEN LEAK
BUNDLES 18 CYLINDERS 50 L/200 bar (about 180
m3 H2)
11GENERAL CONSIDERATIONS
AVOIDANCE OF GAS RELEASE
It is better to contain the gas in cylinder as
much and as long as possible. Consequently, the
use of PRD shall be limited.
12INCIDENTS FIRE RESULTING FROM GAS LEAKAGES
13INCIDENTS FIRE RESULTING FROM GAS LEAKAGES
14INCIDENTS FIRE DUE TO INDUE FAILURE OF PRD
15INCIDENTS CYLINDERS INVOLVED IN A FIRE
16GENERAL CONSIDERATIONS
- Many severe fires result from unexpected gas
release.
- Several severe fires result from undue failure
of C2H2 fusible plugs.
- Cylinders involved in fire none of the
reported incidents led to facilities or
injuries.
17PROPOSAL
- Fully Wrapped cylinders
- Thermally activated device is required, if
cylinders cannot - resist 5 min. in a Standard fire (Note ISO
11119 requires - only 2 min.).
- For every type, the car manufacturer will decide
the use - (or not) and the type of PRD to protect the full
system.