Title: Wind Speed Interference From Callaway


1
Wind Speed InterferenceFrom Callaways Aviation
Beacon
  • Tim Waldron, Met Associates
  • Kip Barbour, Callaway Plant
  • October 9, 2003

2
Wind Speed Interference at Night
  • In early April 2002 while validating Callaway
    Plant's meteorological data for the Annual
    Effluent Release Report, Tim Waldron of Met
    Associates, Inc. performed differential analysis
    of the Primary Tower 10M WS data compared to the
    Secondary 10M WS data. This analysis identified
    an approximate 3 m/s bias on the Primary Tower
    data, but only at night.

3
Illustrations of Differential Analysis
  • The following slides provide some examples of the
    differential analysis used by Met Associates to
    identify the intermittent bias found in the
    Callaway Plant wind speed data.

4
Wind Speed Interference at Night
  • Tim speculated that the data was being affected
    by some kind of dusk-to-dawn circuitry at the
    Primary Tower shelter.
  • The only circuit controlled by a photocell at the
    Primary Tower was the single aviation beacon
    located at the top of the tower.

5
Single Strobe Aviation Beacon
A Flash Technology FTB 310-4 strobe beacon was
installed in September 1997.
6
Flash Technology Power Converter
Cable to beacon
Conduit to Photocell
7
Initial Troubleshooting
  • The IC FIN team verified the beacon was the
    source of the interference by removing the 10
    meter level cups and manually placing the beacon
    controls in night mode.
  • The strip chart recorder immediately jumped to 3
    m/s when the beacon was placed in night mode, and
    pulsed to 5 m/s with each flash of the strobe.

8
Immediate Actions Taken
  • Manually placed the beacon controls in day mode.
    The strobe intensity is about 20,000 candles vs.
    2,000 for night mode.
  • Wrote operability evaluation for WS with the
    beacon controls kept in day mode.
  • Contacted the nearest flight service station
    concerning strobe in day mode.
  • Wrote a Night Order for Operations.

9
Other Actions Taken
  • Submitted Special Report 2002-002 to the NRC.
  • Submitted an Operating Experience report through
    INPO.

10
Obstruction Marking and Lighting
  • Federal Aviation Administration Advisory
    Circular, AC 70/7460-1K
  • 23. Light Failure Notification
  • b. Any failure or malfunction that lasts longer
    than thirty (30) minutes and affects a top light
    or flashing obstruction light, regardless of its
    position, should be reported immediately to the
    nearest flight service station (FSS) so a Notice
    to Airmen (NOTAM) can be issued.
  • FAAs website www.faa.gov/ats/ata/ata400

11
Obstruction Marking and Lighting
  • This report should contain the following
    information
  • Name of persons or organizations
  • The type of structure
  • Location of structure
  • Height of structure above ground level
  • A return to service date.
  • FCC Antenna Registration Number, if app.

12
Obstruction Marking and Lighting
  • 24. Notification of Restoration
  • As soon as normal operation is restored, notify
    the same AFSS/FSS that received the notification
    of failure. The FCC advises that noncompliance
    with notification procedures could subject its
    sponsor to penalties or monetary forfeitures.

13
Investigation of Interference
  • I contacted the following sources
  • Innovative Flash, the contractor for Callaways
    cooling tower lights
  • Flash Technology, the beacon vendor
  • NUMUG e-mail list server

14
Innovative Flash
  • Richard Schawba of Innovative Flash stated that
    he was only aware of one case where the flash
    head itself was creating an RFI field on a
    communications tower. They finally corrected the
    affect by installing a wire mesh around the flash
    head.

15
Flash Technology
  • The Flash Technology representative stated that
    they do not endorse installing a mesh over their
    flash head. He recommended moving the beacon
    cable away from the sensor cables. He stated
    that they had had similar problems on
    communications towers when the beacon cable was
    installed too close to the communications lines.
  • However, he also gave me the name and phone
    number of a competitor that sells a wire mesh
    made to fit their flash head

16
Some NUMUG Feedback
  • One, ensure that your signal cable and strobe
    cable are not co-located they should especially
    not be tied to the same junction box. Two, make
    sure that your power source for the met system
    and for the strobe are separate. Both the met
    system and strobe should be grounded to your
    tower grounding network.
  • Matt Parker, W Savannah River Company

17
Some NUMUG Feedback
  • If the Wind Speed data is only being biased from
    dusk until dawn, it may not be RFI. We had a
    problem years ago that required us to jumper out
    the surge suppression on the ground return from
    the tower sensors into the Climatronics computer.
    we were getting errors on our wind direction
    sensors causing them to read lower than
    expected.
  • Tom Payne, Waterford 3

18
Some NUMUG Feedback
  • I would imagine that if the cause of your
    problem is, indeed, RFI related proper grounding
    and shielding techniques for both the sensor and
    lamp cable as well as re-routing of the lamp
    power cable should mitigate it.
  • Bob Pickwoad, Palo Verde

19
Some NUMUG Feedback
  • If I can add a note here, the shields need to be
    used. Send each of them through the cable run
    separately, and terminate them at the tower grid
    in the shelter (floating the sensors is
    important). Keep in mind that the analog
    translator circuits with the F460 system can pick
    up the RF, as well as the cable run.
  • Ralph Heistand, Turkey Point

20
Summary of Possible Causes
  • RFI from the beacon flash head.
  • EMI from the high voltage cable.
  • 60 Hz noise on tower ground.
  • Inadequate instrument cable shield grounding.
  • Shared a/c power source.

21
Cables at the Base of the Tower
Beacon cable.
Retired cables and waveguides.
Instrument cables.
110 VAC power.
Tower ground cable.
22
Conduit Supports to the Shelter
23
Possible Source of Interference
110 VAC in flex conduit
Beacon cable
Instrument cables
24
Review of Callaway TB Drawings
  • The drawings for the rack TBs showed the sensor
    shields grounded at the rack TBs.
  • The drawings for the tower TBs showed a jumper
    between the sensor shields and the tower ground.
    Possible ground loop?
  • The Climatronics vendor manual drawings showed
    them ONLY grounded at the rack.

25
Extra Jumper from Shields
26
Corrective Actions
  • FIN Electricians removed the jumper in the tower
    TBs to float the sensor shields. This did not
    fix the interference problems.
  • Planned work documents to move the beacon cable.
    Put on 12-week schedule!
  • An Unexpected Discovery
  • The sensor cable shields were cut off at the rack
    TB,
  • and were not grounded as shown on the rack
    drawings.

27
Corrective Actions
  • IC FIN team re-lugged the sensor cables and
    grounded their shields at the rack. Grounding
    the sensor cable shields at the rack corrected
    the interference.
  • The work document to move the beacon cable was
    cancelled.
  • Health Physics and Met Associates had to resubmit
    several Effluent Release Reports