Postal Responsibility/Contractor responsibility - PowerPoint PPT Presentation

1 / 3
About This Presentation
Title:

Postal Responsibility/Contractor responsibility

Description:

SAFETY COMPENDIUM FIRE EXTINGUISHERS PS Form 4705 Completion Requirements 1 2 3 7 4 5 6 Postal Responsibility/Contractor responsibility Serial number of fire ... – PowerPoint PPT presentation

Number of Views:24
Avg rating:3.0/5.0
Slides: 4
Provided by: Willi545
Category:

less

Transcript and Presenter's Notes

Title: Postal Responsibility/Contractor responsibility


1
SAFETY COMPENDIUM FIRE EXTINGUISHERS
PS Form 4705 Completion Requirements
  • Postal Responsibility/Contractor responsibility
  • Serial number of fire extinguisher
  • Number found on fire extinguisher and panel
  • Date extinguisher was installed at this location
  • Completed by contractor conducting annual
    inspection
  • Completed by contractor when extinguisher is
    recharged
  • Completed by contractor when hydrostatic test is
    conducted
  • Completed by postal employee assigned to monthly
    PM route
  • Retention 5 years
  • Source MS-56, 444

2
SAFETY COMPENDIUM FIRE EXTINGUISHERS
Monthly Portable Fire Extinguisher Check
  • Postal Responsibility
  • The following elements constitute the monthly
    fire extinguisher check (monthly check to include
    fire extinguishers in vehicles)
  • Verify the fire extinguisher is not blocked by
    equipment or other objects that could interfere
    with access in an emergency.
  • Inspect the shell for corrosion, mechanical
    damage (denting or abrasion), paint condition,
    presence of repairs (welding, soldering, brazing,
    etc.), and broken hanger attachment concealing
    surface damage (nicks or corrosion).
  • Inspect the nameplate for illegible wording,
    corrosion, and loose plate. Verify extinguisher
    has pictographic type label.
  • Inspect the nozzle for damage, deformation,
    cracks, blocked openings, damaged threads
    (corroded, cross-threaded, or worn), and aging
    (brittleness).
  • Inspect hose assembly for damaged hose (cut,
    cracked, worn, or plugged), damaged couplings or
    swivel joint (cracked or corroded), damaged
    threads (corroded, cross threaded or worn), and
    inner tube cut at couplings.
  • Ensure the valve-locking device is in place and
    inspect for damage (bent, corroded, or binding).
  • Check extinguisher pressure gauge, tap gauge
    lightly to determine if pointer is stuck or
    jammed. Inspect for missing pointer missing,
    deformed, or broken crystal illegible or faded
    dial corrosion, dented case, and damaged crystal
    retainer. Read gauge. If not in operating range,
    remove, replace, and submit extinguisher for
    recharging or hydrostatic test.
  • Ensure that seal or tamper indicator is not
    missing or broken. Replace extinguisher if seal
    or tamper indicator is missing or broken.
  • Complete the applicable portions of Form 4705,
    Fire Inspection Tag.
  • Inspection Record Retention 5 years

3
SAFETY COMPENDIUM FIRE EXTINGUISHERS
Fire Extinguisher Mounting
  • Extinguishers must be available when needed and
    employees must not be subjected to injury when
    obtaining an extinguisher.
  • The locations of extinguishers must be
    immediately visible from several different
    directions.
  • Access to extinguishers must be maintained at all
    times.
  • Floor areas below the extinguisher and their
    approaches must be kept free of materials, and
    red lines must be applied to the floor.
  • Location numbers must be applied to all
    extinguishers and the red background where the
    extinguisher is mounted to ensure accurate
    service and adequate inventory records. In
    multi-floor structures, the extinguisher number
    may be prefixed by the floor designation.
  • Fire extinguishers having a gross weight not
    exceeding 40 pounds must be installed so that the
    top of the fire extinguisher is not more than 5
    feet above the floor. The clearance between the
    bottom of the fire extinguisher and the floor
    must be at least 4 inches.
  • Portable fire extinguishers must be installed
    securely on the hanger, or in the bracket
    supplied by the extinguisher manufacturer, or in
    a bracket approved for such purpose, or placed in
    cabinets or wall recesses.
  • If the possibility of damage to an extinguisher
    exists from rolling equipment, hampers, trucks,
    etc., suitable guards must be provided.
  • A solid red rectangle must be applied to the wall
    behind the extinguisher, extending at least six
    inches beyond each side of the extinguisher. If
    the extinguisher is not readily visible from
    several directions, an additional rectangle at
    least 12 inches wider than the extinguisher must
    be painted on the wall above the extinguisher at
    least 12 feet from the floor.
  • In USPS workrooms the location of column mounted
    extinguishers is indicated by a solid red band
    extending six inches above and below the
    extinguisher, encircling the column. If the
    location of the extinguisher cannot be
    immediately determined, or is not readily visible
    from several directions, a red band at least 6
    inches wide must be applied to the column at
    least 12 feet from the floor, encircling the
    column.
  • Use additional directional signs or triangular
    sign, where necessary.
  • Distribute portable fire extinguishers,
    regardless of size or class, so that the maximum
    travel distance to any extinguisher does not
    exceed 50 feet. This includes elevated work
    platforms, conveyor walkways, and catwalks.
  • Selected locations should have the following
    characteristics
  • (1) Provide uniform distribution
  • (2) Provide easy accessibility
  • (3) Be relatively free from blocking by storage
    and equipment, or both
  • (4) Be near normal paths of travel
  • (5) Be near entrance and exit doors

Signage or panel above extinguisher
Solid red rectangle, 6 inches beyond each side of
extinguisher.
Write a Comment
User Comments (0)
About PowerShow.com