Title: Noti-Fire-NetTM
1Noti-Fire-NetTM
2(No Transcript)
3Network Components
4Noti-Fire-NetTM
- A series of modules and products which allow a
group of Fire Alarm Control Panels and other
control equipment to connect forming a true
peer-to-peer network. - Page 4
5Noti-Fire-NetTM
- Equipment that connects to NOTI-FIRE-NET and
communicates with other equipment using the
network may be referred to as a network node.
NOTI-FIRE-NET supports up to 103 nodes with a
total capacity of 201,960 points. A node may be - AM2020 Fire Alarm Control Panel
- AFP1010 Fire Alarm Control Panel
- NRT Network Reporting Terminal
- AFP-200 with NAM-232 Module
- INA Intelligent Network Annunciator
- Page 4
6Media Interface Board
- The Media Interface Board (MIB) provides the
physical interface to the following medium which
connects node together forming a network - MIB-W - Two twisted pair wire ports
- MIB-F - Two fiber optic cable ports
- MIB-WF - One twisted pair port and one fiber
optic cable port - Page 4
7Network Adapter Module
- NAM-232 Provides a physical interface from the
AFP-200 or AM2020/AFP1010 Analog Fire Panel
through the EIA-232 data port to the Network - NAM-232W - Two twisted pair wire ports
- NAM-232F - Two fiber optic cable ports
- Page 5
8The Serial Interface Board
- The Serial Interface Board (SIB-NET) connects an
AM2020 or AFP1010 to the network through an MIB. - Each AM2020/AFP1010 requires a network node
address and the SIB-NET permits communication
between the AM2020/AFP1010 and other nodes on the
network. - The SIB-NET also provides an EIA-232 and EIA-485
output circuits for other external devices. - Page 5
9The NRT-NET Board
- The NRT-NET interface card and a MIB allow the
Network Reporting Terminal (NRT) to communicate
with the network. - The NRT-NET interface card plugs directly into a
computer expansion slot located on the NRT mother
board. - The MIB plugs onto the NRT-NET card to complete
the network interface. - Each NRT requires a network node address.
- Page 5
10The Repeaters (RPTs)
- The Repeaters (RPT) boost data signals between
network nodes extending communication distances. - RPT-W supports twisted pair wire
- RPT-F supports fiber optic cable
- RPT-WF supports twisted pair wire and fiber optic
cable. - Page 5
11Related Documents
- AM2020/AFP1010 Fire Alarm Control Panel
50119/15088 - Liquid Crystal Display (LCD-80) 15037
- Network Reporting Terminal (NRT) 15090
- Intelligent Network Annunciator (INA) 15092
- Universal Zone Coder Installation
(UZC-256) 15216 - Product Installation Document (CCM-1) 15328
- Product Installation Document (MPS-TR) 15331
- AM2020/AFP1010 Operator Instructions 15337
- Notifier Device Compatibility Document 15378
- Analog Fire Panel (AFP-200) 15511
- Canadian Requirements for the AM2020/AFP1010 1563
1 - Network Interface Board (NIB-96) 15666
- Smoke Control Manual 15712
- NR45-24 Charger 15760
- Page 6
12Related Documents
- Annunciator Control System 15842
- Lamp Driver Modules (LDM) 15886
- The XP Transponder Series 15888
- Voice Alarm Multiplex 15889
- Network Adapter Module (NAM-232) 50038
- The UDACT Universal. Dig. Alarm
Comm/Transmitter 50050 - FCPS-24/FCPS-24E Field Charger Power
Supply 50059 - Video Graphics Annunciator System (VGAS) Inst.
Manual 50251 - Media Interface Board (MIB) 50255
- Repeater (RPT) 50256
- Telephone/Panel Interface (TPI-232) 50372
- Media Evaluation Tool (MET-1) 50480
- MMX-2 Installation Instructions M500-03-00
- Page 6
13NOTI-FIRE-NET Specifications
- When designing the wiring layout of a
NOTI-FIRE-NET system, the following distance
limitations must be considered - 1.The length of each individual twisted pair or
fiber optic segment is limited. A segment is
either point-to-point of two nodes/repeaters or
bus connection (wire only) containing three or
mode nodes. - Page 7
14NOTI-FIRE-NET Specifications Wire
15NOTI-FIRE-NET Specifications
- NOTI-FIRE-NET distance limitations
- Twisted Pair circuits
- The length of cable for each segment in the
system must be within the range specified in
Table 1.5-1. If the distance required is greater
than permitted, a RPT must be inserted into the
circuit. - Cable type should be selected to satisfy the code
requirement specific to a particular application. - Note This table has been expanded to include
more wire sizes and styles since original
preparation. See the table in the manual for more
information. - Page 7
16Twisted Pair LengthsTable 1.5-1
17Twisted Pair LengthsTable 1.5-1
18Twisted Pair LengthsTable 1.5-1
19Twisted Pair LengthsTable 1.5-1
20NOTI-FIRE-NET Specifications
- NOTI-FIRE-NET distance limitations
- Fiber Optic circuits
- Cable attenuation between two nodes must not
exceed a 10 dB limit. Distances greater than
permitted require a repeater module inserted at
intervals less than or equal to 10 dB. - To determine loss, find the rated dB loss per
foot and multiply by the distance required, and
add the dB loss for each connector and splice - Loss ((loss/ft) X (length in feet)) conn.
loss. - Page 10
21NOTI-FIRE-NET Specifications
- NOTI-FIRE-NET distance limitations
- 2. System path length is limited and determined
by using Table 1.5-2. The path is defined as the
distance of travel from one end of the network to
the other, and is influenced by the number of
MIB, NAM and RPT devices, and medium of the
circuit path. - Page 10
22System Path Length
System Path Length Sum of the length of
Segments 1, 2, 3, 4, and 5.
23Node versus Medium Distance Table 1.5-2
24Minimum Requirements
- An NRT or INA and a fire panel with initiating
devices and notification appliances define the
minimum system requirements for a NOTI-FIRE-NET. - For each AM2020/AFP1010 panel configured for NFPA
72-1993 Local Fire Alarm System a CMX module set
at Loop 1, address 96 with Type ID EVGA is also
required. - Page 11
25NFPA Style 4 Configuration
- Noti-Fire-Net is capable of communicating using
NFPA Style 4 SLC. - Under this style of operation, a single open,
wire-to-wire short, wire-to-wire short and open,
wire-to-wire short and ground, or open and ground
results in fragmentation of the network. - A single ground does not affect communication,
but is detected. - Each fragment of the network reconfigures to
permit communications among nodes within the
fragment. - Page 12
26NFPA Style 4 Configuration
NFPA Style 4 SLC Without Regeneration (Bus
Connection)
NOTE A wire-to-wire short
here results in loss of commu- nication between
all four nodes/repeaters on this bus connection
as well as fragmentation of the net- work. Bus
connections should be no longer than 100 within
conduit or the same enclosure.
27NFPA Style 4 Configuration
- In an NFPA Style 4 fiber-optic system, a single
break will result in loss of communication
between network nodes within the fragment of the
network that can only receive signals from the
other fragment. - Page 13
28NFPA Style 7 Configuration
- Noti-Fire-Net is capable of communicating using
NFPA Style 7 SLC. - Under this style of operation, a single open,
wire-to-wire short, wire-to-wire short and open,
wire-to-wire short and ground, or open and ground
will not result in fragmentation of the network. - A single ground does not affect communication,
but is detected. - Style 7 operation may be achieved using fiber
optic cable or mixed media (wire and fiber) - Page 12
29NFPA Style 7 Configuration
30Configuration Definitions
- Point-to-Point wiring configuration is defined as
a twisted-pair segment with only two nodes/
repeaters attached to it. Terminating resistors
are required at each end of every segment, and
are built into each MIB, NAM-232, and RPT. - Page 14
31Configuration Definitions
- Characteristic Impedance in a Point-to-Point
Configuration - Wire segment of each connection is a transmission
line. - Physical construction of the cable used
determines the characteristic impedance of that
segment. - To minimize unwanted data reflections, never mix
more than one brand name, gauge or type of wire
within a segment. - Page 14
32Configuration Definitions
NFPA Style 4 or Style 7 System Point-to-Point
Configuration
Add this segment for a Style 7 System
33 Bus Configuration
- A bus wiring configuration is defined as a
twisted pair network with more than two nodes.
Terminating resistors are only needed on the
first and last node of the bus pair, all other
resistor must be removed. - Page 16
34 Bus Configuration
- In a bus configuration, more than one node
/repeater shares the same circuit. - A fault anywhere along the bus will affect the
rest of the nodes/ repeaters on the bus. - Because of their inherent weakness, bus
configurations are best employed for wiring
between nodes/repeaters local to each other
(within the same cabinet or room). - Page 16
35 Bus Configuration
- Wiring Distances Between Nodes on a Bus
- In a bus configuration, data is shared between
all ports on the twisted pair, thereby reducing
the allowable transmission distance to a maximum
of 100 ft. - Page 16
36 Bus Configuration
- Characteristic Impedance in a Bus Configuration
- The wire segment for each bus connection is a
transmission line. - The physical construction of the twisted-pair
cable used for a segment determines the
characteristic impedance of that segment. - To minimize unwanted data reflections, never mix
more than one brand name, gauge, or type of wire
within a bus segment. - Always make bus connections at the module
terminals provided. - Do not make branch connections at other points.
- Page 16
37Combination Configuration
- A Combination configuration can be used to
distribute the network circuit from a central
facility, saving on wiring run lengths. - A repeater is bus-wired to two existing nodes in
each central facility (located in the same room)
to support point-to-point connections in the
remaining buildings in the system. - Page 17
38Terminating Point-to-Point and Bus Configurations
- Both point-to-point and bus twisted wire pair
configurations require end-of-line termination at
each end of the respective circuit. - Whereas a point-to-point circuit has a
terminating resistor at each node/repeater port,
a bus circuit spans multiple nodes/repeaters,
with termination only at the outer edges of the
circuit. - Page 18
39Terminating Point-to-Point and Bus Configurations
- Terminating resistors are present on all MIBs,
NAMs, and repeaters. The terminating resistor on
the first and last nodes/repeaters of a wire
segment must remain intact. The terminating
resistors on all the other nodes/repeaters
connected to the same bus segment must be cut and
removed from each board. - Page 18
40On-Board Terminating ResistorsTable 1.10-1
41On-Board Terminating Resistors
Point-to-Point Termination
These point-to-point segments are terminated at
each node/repeater.
42On-Board Terminating Resistors
43On-Board Terminating Resistors
44Network Wiring Ground Fault Detection
- Twisted pair communications links between nodes
can be isolated through the MIB/ NAM transformer
coupling, so a single ground fault has no effect
on circuit operation. - Ground fault of the isolated link is not
necessary unless required by LAHJ. - Ground fault detection from a node power supply
may be fed-through or disabled at the MIB/NAM. - Page 20
45Network Wiring Ground Fault Detection
- Media Interface Board (MIB)
- SW1 corresponds to Channel A
- SW2 corresponds to Channel B
- Network Adapter Module (NAM-232)
- JP1 corresponds to Channel A
- JP2 corresponds to Channel B
- Page 20
Switch set ON to enable ground fault
feed-through. Switch set OFF to disable ground
fault feed through
Jumper set ON to enable ground fault
feed-through. Jumper set OFF to disable ground
fault feed through
3 2 1
3 2 1
46Network Wiring Ground Fault Detection
- Ground fault circuit operation
- Ground fault detection may be provided by a FACP
node which is powered by a MPS-24A or by an
AFP-200 connected with a NAM-232. - INA and NRT cannot provide ground fault
detection. Switches SW1 and SW2 on the INA or NRT
must always be off. - Page 20
47Network Wiring Ground Fault Detection
- Point-to-Point Configuration
- In point-to-point without repeaters, enable
ground fault in only one of two nodes. - Page 20
48Network Wiring Ground Fault Detection
- Point-to-Point Configuration
- If an RPT-W is used, two ground fault detection
schemes are possible. One or both nodes may
provide detection depending on the RPT pass
through switch (SW3) Setting. - Page 21
49Network Wiring Ground Fault Detection
- Point-to-point
- Left side node provides detection. Port B SW2 is
ON. - RPT passes through detection. SW3 is ON.
- Right node blocks detection. Port A SW1 is OFF.
- Page 21
50Network Wiring Ground Fault Detection
- Point-to-Point
- Left side node provides detection. Port B SW2 is
ON. - RPT blocks detection. SW3 is OFF.
- Right node provides detection. Port A SW1 is ON.
- Page 21
Ports
Network Node
Network Node
51Network Wiring Ground Fault Detection
- Ground fault detection feed-through is effective
for a maximum of two point-to-point repeaters. - A maximum of 5 repeaters can be serially
connected for proper ground fault operation. - Page 21
ON NODE
ON RPT
ON RPT
OFF RPT
ON NODE
ON RPT
ON RPT
52Network Wiring Ground Fault Detection
- Bus Configuration
- In a bus configuration, as in point-to-point,
only one node can provide ground fault detection
along the bus. - The primary difference is that one node can
provide ground fault detection for multiple nodes
along the bus. - Page 22
53Network Wiring Ground Fault Detection
- Bus Configuration
- 2nd node from right provides ground fault
detection. - All other nodes have ground fault disabled.
- Note Termination resistors removed from
pass-through bus ports. - Page 22
54Network Wiring Ground Fault Detection
- Bus Configuration
- Node on the left and 2nd node from right provide
ground fault detection, and RPT SW3 is off to
prevent pass through. - This creates two separate ground fault circuits.
- All other nodes have ground fault disabled.
- Page 22
55FCC Considerations
- In order to comply with FCC regulations regarding
radio frequency emissions, a ferrite cylinder
(Notifier p/n 29087) must be installed on every
twisted pair circuit connected to a MIB-W (two
cylinders included) and MIB-WF (one cylinder
included). - Page 20
56FCC Considerations
- NRT Installation
- Thread the twisted pair(s) through the ferrite
cylinder. - Slide the cylinder along the pair(s) toward the
MIB on the back of the NRT so that the closest
edge of the cylinder is no more than 3 inches
away from the terminal connection block. - Secure the ferrite cylinder to the wiring with
the supplied toe wrap at each end of the
cylinder. - Page 23
57FCC Considerations
- INA SIB-NET Installation
- Thread the twisted pair(s) through the ferrite
cylinder. - Slide the cylinder along the pairs toward the
entrance point on the cabinet (not toward the
MIB) so that the edge of the cylinder and the
cabinet are separated by no more than three
inches. - Secure the ferrite cylinder to the wiring with
the supplied tie wrap at each end of the
cylinder. - Repeat for the second MIB-W port.
- Page 23
58 Tips and Techniques
- How to recognize and fix ground loops
- Its important to realize that a ground loop is
not the same as a surge. A ground loop is a
consistent electrical state, causing a steady
high voltage with high current capability. A
voltage surge, although it may be higher and more
powerful, is typically an induced voltage with a
very fast rise time.
59Noti-Fire-Net Data Pulse
- The two thresholds available are HIGH (1.4 Volts)
and LOW (800mV). If the pulse width 2.1 at the
HIGH(TH, 1.4V) and 2.4 at the LOW(TL, .8V), the
threshold should be set to HIGH. The main
criteria is to look for is a pulse width gt 1.1
uSec at each threshold.
60(No Transcript)