PROFIBUS Classic IO Modules - PowerPoint PPT Presentation

1 / 17
About This Presentation
Title:

PROFIBUS Classic IO Modules

Description:

PROFIBUS Classic IO Modules. 60mm Classic IO Module Housing ... Baud rate: Auto baud (supports 9.6K to 12 Mbaud) Profibus Classic IO Module Diagnostic LEDs ... – PowerPoint PPT presentation

Number of Views:51
Avg rating:3.0/5.0
Slides: 18
Provided by: bobh58
Category:

less

Transcript and Presenter's Notes

Title: PROFIBUS Classic IO Modules


1
PROFIBUS Classic IO Modules
2
60mm Classic IO Module Housing
  • Industrial IP rating
  • IP67
  • Classic size
  • 60mm x 220mm x 20mm
  • User settings
  • Via clear window
  • Hardware
  • 8 IO ports of M12 connection
  • Mounting
  • 37.5mm x 210mm centers

3
Profibus DP Classic IO Module
  • Four configurations
  • 16 In
  • 14 In / 2 Out
  • 12 In / 4 Out
  • 8 In / 8 Out
  • Choice of input compatibility
  • NPN sensors or dry contact
  • PNP sensors or dry contact
  • Current sourcing outputs
  • Autobaud rates up to 12M
  • Addressing range of 1-126
  • Diagnostic data over Profibus

4
Profibus DP Classic IO Bus Connections
  • Bus In
  • Male Reverse-Key M12
  • B-code
  • Bus Out
  • Female Reverse-Key M12
  • B-code
  • Integrated T wiring
  • Separate Molded Bus Terminator

5
Profibus DP Classic IO Power Connection
  • Tee Connection
  • Power In
  • Male Mini 5-Pole
  • Power Out
  • Female Mini 5-Pole
  • 24 VDC Output Power
  • 24 VDC Module Input Power

6
Profibus DP Classic IO I/O Connection M12
  • Female M12 single-key micro A-code
  • BradConnectivity Ultra-Lock connection system
  • Twin wired
  • A channel on pin 4
  • B channel on pin 2
  • Ports 1 through 8

7
Twin Wired I/O Connection M12
  • Input
  • Factory configured to PNP or NPN
  • 3 ms input filter
  • 140 mA sensor supply
  • Short circuit protected
  • Output
  • current sourcing
  • 2.0 Amps per channel
  • 8 Amps per module
  • Overload protected
  • 200 Hz switching frequency

8
Complementary Wired I/O Connection M12
  • Classic Profibus 14 input and 2 output models
    only
  • Input
  • Factory configured to PNP or NPN
  • 3 ms input filter
  • 140 mA sensor supply
  • Short circuit protected
  • Output
  • Current sourcing
  • 2.0 Amps per channel
  • 8 Amps per module
  • Overload protected
  • 200 Hz switching frequency

9
Profibus Classic IO Module IO Selection
10
Profibus Classic IO Module Settings
  • Address
  • 1-99 by rotary switch
  • 1-126 by software
  • Baud rate
  • Auto baud(supports 9.6K to 12 Mbaud)

11
Profibus Classic IO Module Diagnostic LEDs
12
Profibus Classic IO Module Range
13
Profibus Classic IO Module Printing Labeling
  • Direct printing (common to all)
  • BradControl, NET, MOD, PWR I O, Port A,B channel
  • White label inserts (common to all)
  • pre-assembled
  • user markable
  • Module identification label
  • Individual for each module, example shown

14
Profibus Classic IO Module Part Numbers
15
Profibus Classic IO Module References
  • Website
  • e-Catalog
  • Data Sheet
  • User Manuals
  • GSD Files

16
Summary
  • BradConnectivity Ultra-Lock connection technology
  • Extended addressing
  • NPN sensor compatible
  • Wide dedicated range
  • Output current capacity
  • T bus power connection
  • Mini power connection
  • Pricing
  • Availability
  • E-catalog documentation

17
PROFIBUS Classic IO Modules
Write a Comment
User Comments (0)
About PowerShow.com