Title: 4100 Presentation


1
PReasy 4100
A New Beginning
2
4100 Series
  • A Universal, Front programmable and
    Cost-effective series of products for Signal
    Conditioning and Still High Quality (Namur NE-21,
    PR-Precision and 5 year Warranty)
  • Thus Dedicated for Installers, Panel builders,
    machine Builders and of course all types of End
    Users.

3
4100 Series
  • The Interface
  • Input
  • Output
  • Relay Function
  • Error Handling and Diagnostics
  • Advanced Features

4
4100 Universal transmitters / trip amplifier
  • Universal Input
  • Analogue Output Voltage and Current
  • Universal supply 21,6-253 VAC / 19,2 300 VDC
  • 2 relays with programmable functions
  • Sensor error indication via Display Front or LED
  • And Programmable via display front 4501
  • No Manual Needed Menu Structure PR Guided!
  • Approvals CE, LVD, UL-508 (Autumn 2005)
  • Safety Fulfilling the requirements for SIL-2

INPUT OUTPUT
X
5
4100 The Programming Interface
  • Run Mode
  • Display of Input value in eng. Units
  • Display Output Value or TAG
  • Programming Mode
  • Change value with Arrows
  • Validate with OK
  • The Menu Guides you to the Next Item gt Thats
    PReasy
  • Error Mode
  • All error indications will be shown in the 2nd
    line together with a Flashing Backlight. The
    Flashing backlight can be turned off by pressing
    OK.

249.0
VOLT
SE.BR
Both Arrows TAG / Ana.Out Toogle
Flashing BacklightWith Errors
C
INTYPE
Error TEXT
15.2 mA
HELP TEXT
Prog-Mode
Error-Mode
Run-Mode
6
4100 The Programming Interface Status Line
  • The Status Line has 4 symbols
  • 1 Indicates the status of the Relay 1 Contact
    Open or Closed
  • The 1 can be flashing, if the relay is in the
    Delay period
  • 2 Indicates the status of the Relay 2 Contact
    Open or Closed
  • The 2 can be flashing, if the relay is in the
    Delay period
  • The arrow shows the tendancy of the Input Signal
  • The Com-symbol indicates if the 4501 is running
    correctly

249.0
C
15.2 mA
Run-Mode
7
4100 The Display Engineering Units
  • C in/s bar kV F ft/s mbar
  • mV K in/min kJ Ohm m ft/min
  • Wh S cm in/h MWh uS mm
  • ft/h kWh ft rpm W m3/min
  • in Hz GW m3/h yd t MWL/s
  • m3 kg kW L/minL g hp L/h
  • s N A gal/min min Pa kA
  • gal/h m/s MPa mA t/h m/min kPa
  • uA mol m/h hPa V pH

Run-Mode
8
4100 The Programming Interface - The PR Guided
Menu
PR GUIDED Menu Structure 4100 3 Lines 5714 1
Line
Traditional Menu Structure Often 1 Line
Short Cut to fastset Short Cut to Advanced
Features
Start
Start
Type
Range
Input
Type
Range
Input
Relays
Setp
Hyst
Relays
Value
Output
Thats PReasy!
Output
  • User Problems
  • Where am I?
  • Whats Next?
  • What do I need to do now? What do I miss?
  • User Advantages
  • No need to Know where You are!
  • Only 1 way Through (Fwd or Bwd)
  • PR Guided makes sure You will get through all
    Necessary Items!

9
4100 Universal Input
  • Current 0-20 mA 4-20 mA
  • Voltage 0-1V 0,2-1V 0-5V 1-5V 0-10V 2-10V
  • Lin.R. 0-10.000 Ohm (2,3 and 4 wire )
  • Potentiometer 10 O 100 kO (3 wire)
  • Loop Supply 16V for 2-wire Transmitter

INPUT OUTPUT
X
10
4100 Universal Input - Temperature
  • Pt x and Ni X
  • 2,3 and 4 wire connections
  • Pt 10, 20, 50, 100, 200, 400, 500, 1000
  • Ni 50, 100, 120, 1000
  • TC
  • 13 Types, including Russian L (LR)
  • Internal CJC (Always Mounted)

INPUT OUTPUT
X
11
4100 TC- Input Cold Junction Compensation
  • Internal CJC Always Mounted
  • Precision
  • Max lt/-1,0 C (-20 C - 60 C)
  • Max Error (0,0053 C x Amb.Temp)0,68 C
  • Safety
  • The unit will make max. comp. of -20 C and 80
    C respectively, even though the CJC sensor
    element should indicate a higher or lower
    temperature.

INPUT OUTPUT
X
12
4100 Analogue Output
  • Current
  • 0-20 mA 20-0 mA
  • 4-20 mA 20-4 mA
  • Max Charge 800 O
  • Over/Under Range Limits 3,8 mA / 20,5 mA
  • Sensor Error Indication 0/3,5mA or 23mA
  • Voltage (calibrated with Internal Shunt)
  • 0/0,2-1V 1-0,2/0V 0/1-5V 5-1/0V 0/2-10V 10-2/0V
  • Sensor Error Indication No

INPUT OUTPUT
X
13
4100 Two Independant Relay Outputs
  • Relay Functions (The 2 relays can have different
    functions)
  • Setpoint (SETP) (Fastset Possibility)
  • Window (WIND)
  • Input Error (ERR)
  • Power (POW)
  • OFF

INPUT OUTPUT
X
14
4100 Relay Units
  • For all Functions
  • For Temp Inputs the unit is C or F
  • For other inputs, you can choose between
  • DISP Display Units
  • PERC Percentage

INPUT OUTPUT
X
15
4100 Relay Output SETP function
  • FUNCTION SETP Setpoint
  • Function N.O. / N.C.
  • Setpoint
  • Action Increase or Decrease
  • Hysteresis 0,1 to 25 of span or 1 count to 3000
    counts (max 25)
  • On-Delay in Seconds (0- 3600s)
  • Off-Delay in Seconds (0- 3600s)
  • Error action Hold,Open,Close, None

INPUT OUTPUT
X
16
4100 Relay Output WIND function
  • FUNCTION WIND Window
  • Contact
  • O.I.W. Open In Window
  • C.I.W Closed in Window
  • Setpoint Low
  • Setpoint High
  • Hysteresis 0,1 to 25 of span or 1 count to 3000
    counts (max 25)

INPUT OUTPUT
X
17
4100 Relay Output ERR function
  • FUNCTION ERR Error
  • Action in case of Error
  • Hold,Open,Close, None

INPUT OUTPUT
X
18
4100 Relay Output POW function
  • Function POW Power
  • The Relay will be CLOSED when the module is
    powered.
  • The Relay will be OPEN when the module is NOT
    powered

INPUT OUTPUT
X
19
4100 Relay Output OFF function
  • Function OFF
  • The Relay will be deactivated!

INPUT OUTPUT
X
20
4100 Series
  • Error Indication, Detection
  • Auto Diagnostics

21
4100 Error Detection Out of A/D converter range
  • Indicated by IN.LO or IN.HI
  • Voltage Input1 lt-25 mV or gt1,2V
  • Voltage Input2 lt-25 mV or gt12V
  • Current Input lt-1,05mA or gt25,05mA
  • POTM Input lt-0,5 or gt100,5
  • LIN.R input1 lt-10O or gt1075O
  • LIN.R input2 lt-10O or gt110kO
  • TEMP ltPoly-2 C or gtPoly2 C

22
4100 Error Detection Sensor Error
  • Indicated by SE.BR (break) or SE.SH (shortage)
  • Voltage None
  • 4-20mA SE.BR - Input lt3,6mA or gt 21mA
  • POTM SE.BR - Input gt126k O (Each Wire)
  • LIN.R1 SE.BR gt 875 O
  • LIN.R2 SE.BR gt 11 kO
  • TC SE.BR gt 750 kO
  • Pt and Ni SE.BR gt 15 kO
  • SE.SH lt 15 O (Not for
    Pt10, Pt20 and Pt50)

23
4100 Error Detection Display Over/Under Range
  • Display over/under range, indicated by -1.9.9.9
    or 9.9.9.9
  • NB the minimum/maximum values on the Display is
    -1999, 9999 respectively.

24
4100 Error Indication Resumed With 4501
  • Out of A/D converters Range
  • Flashing IN.LO or IN.HI
  • Display Over/Und range indication
  • Flashing -1.9.9.9 or 9.9.9.9
  • Sensor Break
  • Flashing SE.BR
  • Sensor Shortage
  • Flashing SE.SH

25
4100 Error Indication With LED
  • The unit is continuously verifying its own State
    of Health, thus Increasing Safety.
  • Error Indication with 1 Green/Red LED on Front
  • Green Flashing 13 Hz Normal
  • Green Flashing 1 Hz Sensor Error
  • Green On not Flashing Internal Error
  • Red On not Flashing Fatal Error
  • Return Product to PR

26
4100 Auto Diagnostics With 4501 Display
  • The unit is continuously verifying its own State
    of Health, thus Increasing Safety.
  • Error Indication with Display Mounted
  • HW.ER Permanent error in uC/AD converter
  • CJ.ER CJC sensor Failure
  • RA.ER error in RAM (Memory)
  • FL.ER Error in Flash Memory
  • AO.ER Error in analogue Measurement
  • TY.ER Trying to Load a configuration from for
    example a 4114 to a 4116.
  • CO.ER Com Error between 4501 and 41xx
  • PW.ER Error in Internal Power

27
4100 Series
  • Advanced Features

28
4100 Advanced Features
  • It is possible to enter Advanced Setting in
    Beginning of the Menu structure
  • Memory
  • Display
  • Calibration
  • Simulation
  • Password
  • Language

29
4100 Advanced Features MEMORY (MEM)
  • With this feature you can easily copy a
    configuration from one module to another.
  • Memory (MEM)
  • SAVE or LOAD
  • Save, saves the Product Configuration in the
    Front
  • Load, uploads the configuration in the front to
    the next Product
  • NB Process Calibrations are not copied.

30
4100 Advanced Features DISPLAY (DISP)
  • Contrast (CONTRA)
  • 0 to 9
  • Light (LIGHT)
  • 0 to 9
  • TAG (Exception 1st and 2nd line swithced)
  • 6 characters Alpha Numerique
  • LINE 3 (Selection of Indication in 3rd Line)
  • TAG or A.OUT

31
4100 Advanced Features CALIBRATION (CAL)
  • 2 Point Process Calibration for ALL input Types
  • CAL.LO (not necessarily 0)
  • Yes or No, if Yes then
  • Affect the LOW value you want to calibrate to the
    Input of the Product.
  • Preset the Correct Value in Display Units.
  • CAL.HI (not necessarily 100)
  • Yes or No, if Yes then
  • Affect the HIGH value you want to calibrate to
    the Input of the Product.
  • Preset the Correct HIGH Value in Display Units.
  • NB A new Process Calibration will not consider
    an eventual previous process calibration.

32
4100 Advanced Features SIMULATION (SIM)
  • Simulate the Input value in Display Units
  • Enable Simulation (EN.SIM)
  • Yes or No
  • If Yes, then Simulate the Input value in Display
    Units
  • And see what happens to the Output and the Relays
  • Relay Simulation (REL.SIM)
  • Use the arrows to toggle the two relays
    independently

33
4100 Advanced Features PASSWORD (PASS)
  • Enable Password (EN.PASS)
  • Yes or No
  • If Yes, then enter Password
  • Enable Fastset (EN.FAST)
  • Yes or No

34
4100 Advanced Features LANGUAGE (LANG)
  • Select the Language of the Help Texts
  • Language (LANGUA)
  • DE,DK,ES,FR,IT,SE,UK

35
4100 Compared to 5000 and 2200 Series Whats New?
  • Same As 2202, 2204, 2231, 2237, 2238, 2241,
    2271, 2284
  • But which Functionality can be found in he 4000
    but not in the 2200 series?
  • Pt100 with 2 Relays
  • TC transmitter
  • TC transmitter with 2 Relays
  • Relay with Loop Supply
  • ReadOut of Input and Output Values (in
    Engineering Units)
  • 2-Point Process Calibration (w.Buttons not
    Potentiometers)
  • And Much more

36
Preasy 4100
Profit - Advantages - Features
37
Preasy 4100
38
Preasy 4100
39
Preasy 4100