Title: VM1: innovation in power technology
1VM1 innovation in power technology
2VM1 Innovation in medium voltage
technology Vacuum circuit-breaker with magnetic
actuator
- Die Summe von Vorteilen
- Keine Wartung
- Wenige Einzelteile
- Einfache mechanische Abläufe
- Sehr hohe Zuverlässigkeit
- Hoher Qualitätsstandard
- Sehr hohe Lebensdauer
- Main Characteristics
- Maintenance-free
- Extremely high number of operating cycles
- Electronic controller with sensor technology
- Vacuum interrupters embedded in epoxy resin
- High quality standard
- Compatible with conventional circuit-breakers
- For universal applications worldwide
3VM1 Rated voltage kV 12 17.5 24 Rated
current A ...2500 ...2500 ...2500 Rated
short-circuit kA ...31.5 ...31.5 ...25 breaking
current
4- Common look and feel
- the same common look and feel according to PT
Guidelines for Product Design
new look VM1
new VD4
5- new VD4 and new look VM1 have common frame
suitable for interchangeable plug-in actuators
new look VM1
new VD4
6Emergency manual breaking mechanism Electronic
controller Magnetic actuator Electrical energy
store Sensors for switching position detection
7(No Transcript)
8- Main characteristics
- Electronic maintenance-free
- Controller with sensor technology
- Magnetic actuator with extremely high number of
operating cycles - up to 100,000 operating cycles for breaking
capacity up to 25 kA and rated current up to 1250
A - up to 50,000 operating cycles with rated current
gt 1600 A and/or breaking capacity gt 31.5 kA - Embedding technology to protect vacuum
interrupters - High quality standard
- External dimensions compatible with VD4
- Developed for universal applications worldwide
9Single-line diagram of electronic controller
10-SO4 Undervoltage opening (only with ED2.0 Full
Option) -SL1 Contact locking the CB closing -SO3
Auxiliary and safety open (2 open command from
remote) -SO2 Open command from remote -SC2 Close
command from remote
DO7 CB Remote Open DO6 Unit Not Ready DO5 Unit
Ready DO2 CB closed DO1 CB open
24 .. 48V AC / 24 .. 60 V DC100 .. 240V AC / 110
.. 250 V DC
Auxiliary voltage supply
11 Electronic controller
Sensors
Capacitor
12 Magnetic actuator
13Representation of magnetic flux density
distribution
Magnetic latching in end-of-run
position Armature position 0 mmAmpere-turns 0
A
Moving armature in opposing position and magnetic
end-of-run latching Armature position 20 mmAmper
e-turns 5000 A
Magnetic latching and action of the magnetic
field of a coil Armature position 0 mmAmpere-tu
rns 12500 A
14 y
Reduction of the magnetic flux density of Koerdym
280 as a function of the lifetime t at an ambient
temperature of 120 C
15- Basic version
- Closing pushbutton (SC1)
- Opening pushbutton (SO1)
- Mechanical operation counter
- Mechanical signalling device for circuit-breaker
open/closed - Emergency manual opening device
- Lever for manual emergency opening
- Lamp signalling READY for the operation (PRDY)
- Capacitors for storing energy for the operation
- Mobile connector for direct connection to the
sockets of the electronic module, to cable the
auxiliary circuits - ED2.0 standard version control module
16- ED2.0 control module standard version
- Signalling contacts without potential, fitted
with relay, with the following functions - N 1 contact signalling circuit-breaker open
(DO1) - N 1 contact signalling circuit-breaker closed
(DC1) - N 1 contact signalling circuit-breaker ready for
the operation (capacitors charged and check of
circuit-breaker state) (DR) - N 1 contact signalling circuit-breaker not ready
for the operation (DN, normally closed) - N 1 transient contact with momentary closing
during the opening operation (DOR) - Remark with the circuit-breaker not supplied
(without auxiliary power supply) these contacts
are open, except the contact signalling
circuit-breaker not ready for the operation (DN). - Not available in withdrawable version
17- ED2.0 control module standard version
- 2 feeder power supply
- Type 1 24 ... 48 V AC / 24 ... 60 V DC
- Type 2 100 ... 240 V AC / 110 ... 250 V DC
- Binary inputs (logical inputs) for remote
control - N 1 input for closing control (-SC2)
- N 1 input for opening control (-SO2)
- N 1 input for additional opening control (-SO3)
- N 1 input for circuit-breaker opening on direct
command from the protection release PR512 (-SO5) - N 1 input for lock on closing control (the same
function of the locking electromagnet in the
mechanical actuator of the VD4 circuit-breaker)
(-SL1) - Binary inputs
- 24 ... 240 V AC ( 15 ... 10)
- 24 ... 250 V DC ( 30 ... 10)
- (minimum duration of the impulse is 20 ms)
18- ED2.0 control module standard version
- Functions
- Self-opening following determination of incorrect
state of circuit-breaker - Self-opening following load threshold of the
capacitors lower than the minimum value required
for the opening and closing operation - Anti-pumping relay function
- Trip-free function
- Monitoring of capacitor load with feeder turning
itself off in the case of exceeding the maximum
load level - (these functions can be disabled by means of
dip-switches)
19- ED2.0 control module full option version (on
request) - Signalling contacts without potential, fitted
with relay, with the following functions - N 2 contacts signalling circuit-breaker open
(DO1, DO2) - N 2 contacts signalling circuit-breaker closed
(DC1, DC2) - N 1 contact signalling circuit-breaker ready
for the operation (capacitors charged and check
of circuit-breaker state) (DR) - N 1 contact signalling circuit-breaker not
ready for the operation (DN, normally closed) - N 1 transient contact with momentary closing
during the opening operation (DOR) - Remark difference respect to ED2.0 control
module basic version
20- ED2.0 control module full option version (on
request) - Binary inputs (logical inputs) for remote
control - N 1 input for closing control (-SC2)
- N 1 input for opening control (-SO2)
- N 1input for additional opening control (-SO3)
- N 1 input for circuit-breaker opening on direct
command from the protection release PR512 (-SO5) - N 1 input for lock on closing control (the same
function of the locking electromagnet in the
mechanical actuator of the VD4 circuit-breaker)
(-SL1) - N 1 input as undervoltage control for (-S04)
- Remark difference respect to ED2.0 control
module basic version
21- ED2.0 control module full option version (on
request) - Functions
- Self-opening following determination of incorrect
state of circuit-breaker - Self-opening following load threshold of the
capacitors lower than the minimum value required
for the opening and closing operation - Anti-pumping relay function
- Trip-free function
- Monitoring of capacitor load with feeder turning
itself off in the case of exceeding the maximum
load level - Undervoltage function with selection of the
reference rated voltage and with possibility of
delaying the opening from 0 to 5 s (-SO4) - Watchdog of the electronic power circuit with
feeder turning itself off in the case of
overtemperature and/or overcurrent - Slow capacitor charging function (the power load
passes from 100 watt to 40 watt, doubling the
charging time) - Monitoring continuity of the opening and closing
coils - Watchdog (DN)
- Additional safety opening command function
- Remark difference respect to ED2.0 control
module basic version
22- Accessories available (on request)
- Signalling auxiliary contacts circuit-breaker
open/closed - Fixed circuit-breaker (-BB1 -BB2 -BB3 -BB8)
- Set of 5 make contacts plus 5 break contacts
- Set of 10 make contacts plus 10 break contacts
(alternatively) - Withdrawable circuit-breaker (-BB1 -BB2)
- Set of 5 break contacts plus 5 make contacts
- Transmitted contacts of the withdrawable
circuit-breaker installed in the truck (-BT1
-BT2) - These contacts are either in addition or as an
alternative to the position contacts (for
signalling circuit-breaker racked out) located in
the unit they also carry out the function of the
position contact (-BT3) - Position contact of the withdrawable
circuit-breaker (-BT3) - With binary input SL1 prevents remote CB closing
during translation of the truck it is supplied
when the transmitted contacts -BT1 -BT2 are not
required - Motorised truck (-MT) (only for VM1 for UniGear
panel)
23- Features of the control module ED2.0 (standard
version) - The closing coil can only be activated when VM1
is open - The opening coil can only be activated when VM1
is closed - Closing is disabled when an opening command is
active at the same time - De-activation of the opening or closing coil
takes place when the relative limit position has
been reached - WRONG POSITION (auto trip) function if the final
CLOSED (or OPEN) position is not reached within
70 ms during a closing (or opening) operation, an
opening operation is immediately started to
guarantee reaching a defined safe position in any
case. - Anti-pumping function ensures that only one
closing-opening cycle is carried out when a
closing command followed by an opening command is
active active closing command must be cancelled
and reset for the next closing operation. - Activation of the input for the closing command
can be locked by means of an external locking
signal. - Input for the lock on closing command must be
energised to be able to close the circuit-breaker
(without power it inhibits closing).
24- Features of the control module ED2.0 full version
- Undervoltage function
- controls VM1 opening if the voltage applied drops
below the limit of tolerance (established by the
Standards) - rated voltage value to be monitored is set in the
factory in conformity with the order
specifications but it can be changed by
dip-switches - to prevent UVR intervention, when the voltage
drops below the specified level (e.g. in the case
of motor starting), it is possible to set a trip
time - UVR function can be disabled
- Monitoring function of the actuator closing and
opening coil if a fault is detected, the
luminous READY signal on front of the
circuit-breaker turns off and the READY/NOT
READY signalling contacts are activated. - Additional safety opening command function the
second input of the control module for the
opening function is designed so that an opening
command is carried out directly even in the case
of a fault in the microprocessor.
25- Features of the capacitor
- The energy stored is suitable for an O-C-O
operating cycle without recharging - The energy stored is constantly monitored by
measuring the voltage of the capacitor - READY indication signals
- application of the power supply voltage
- ready status of VM1 for the next operation
- READY signal switched on means
- (VM1 in the open position) energy sufficient for
one C-O operating cycle - (VM1 in the closed position) energy sufficient
for one opening operation energy available is
sufficient for one opening operation within 60 s
from interruption of the auxiliary power supply
(up to 120 s with 2 capacitors)
26y
Lifetime t of aluminium electrolytic capacitors
as a function of the ambient temperature T
27Characteristic data
Switching energy for CO VM1 150 J VD4 115
J Capacitor voltage 80 V Closing cycleVM1 max.
100 Jwithout capacitor max. 2.3 kW for 54
ms Making current max. 29 A for 44 ms Breaking
capacitywith capacitor max. 50 Jwithout
capacitor max. 2.1 kW for 27 ms Breaking
current max. 27 A for 30 ms Opening time 35 ...
45 ms Arcing time 10 ...15 ms Total interruption
time 45 ... 60 ms Closing time 50 ... 60 ms
28(No Transcript)