Title: Variable Frequency Drives
1 ASHRAE NB PEI Chapter May 12, 2009
Variable Frequency Drives Motors
in the HVAC Industry
2HVAC Variable Frequency Drives
Pumps Fans Towers
3(No Transcript)
4Control HP Save Energy
Used to be the main topic
Centrifugal Loads
- Flow µ Speed
- HP µ Speed3
- At 50 Speed, HP 12.5
5Affinity Laws
- Flow vs Speed
- Q1/Q2 S1/S2
- Head vs Speed
- H1/H2 S12/S22
- HP vs Speed
- bhp1/bhp2 S13/S23
6Typical HVAC VFD Applications
- Fans
- AHU (Supply Air Fans)
- Return Air
- Exhaust
- Cooling Towers
- Evaporative Condensers
- Pumps
- Chilled Water
- Condenser
7(No Transcript)
8(No Transcript)
9Energy Savings
Speed 1
Head
Head
Power
Speed 2
Power
Throttling (riding the curve)
VFD (varying the speed)
10Variable Frequency Drives
- Over 25 years of HVAC applications
- Fundamental principal remains unchanged
- Convert line voltage frequency to controllable
values and apply to induction motors - For a 4 pole motor
- 60Hz 1800 rpm
- 30Hz 900 rpm
The preferred choice to achieve variable flow
control
11Variable Frequency Drives
- Numerous advancements over the 25 yrs
- Power devices evolved
- Thyristor (SCR) GTO Bipolar Transistor
to present day IGBT devices - IGBT (Insulated Gate Bipolar Transistor)
- Faster Switching / Higher performance
- Lower losses / Higher efficiency
- Smaller packaging
- Robust / Increased reliability
12Variable Frequency Drives
- Numerous advancements over the 25 yrs
- Microprocessor power
- Better control and accuracy
- Enhanced firmware
- High speed current limit Tripless
- Regen Avoidance
- Built-in PLC Function
- PID control loop
- Network communications
- BACnet MSTP, BACnet IP, FLN, N2, LonWorks,
- Modbus RTU, Modbus TCP/IP
- Today VFDs are rated for 100kA interrupt capacity
13- Keypad
- Store Multiple Parameter Sets
- Upload / Download Parameters
- Download Parameters without powering up the VFD
14High Speed USB port to capture oscilloscope
type data traces
15(No Transcript)
16Typical PWM VFD
DC Bus
Speed µ Hz
Torque µ V/Hz
Input Line
Filter Capacitor
AC Motor
PWM Output
Inverter
Rectifier
575/3/60
0 - 575V 0 - 60Hz
AC to DC
DC to AC
17Motors
- Manufactured to Nema MG1 standard
- Part 30
- General Purpose not generally associated with
VFD applications - Insulation rated for 1000V / 2 msec rise time
(majority of quality motors rated for withstand
voltage of 1200V to 1400V)
Note that specs such as Class B or F relate to
temperature classes not voltage withstand rating.
Similarly efficiency ratings also do not relate
to voltage withstand ratings.
18Motors
- Manufactured to Nema MG1 standard
- Part 31
- Definite Purpose Inverter Duty
- Insulation rated for 1600V / 0.1 msec rise time
Note that specs such as Class B or F relate to
temperature classes not voltage withstand rating.
Similarly efficiency ratings also do not relate
to voltage withstand ratings.
19Motors
- Manufactured to Nema MG1 standard
- Part 31
- Definite Purpose Inverter Duty
- Insulation rated for 1600V / 0.1 msec rise time
- Newer motor designs rated for 2000V
- Speed Turndown range
- CT 101
- VT 1001
- 5 Year Warranty
20Motors
- Comments and Recommendations
- The voltage withstand rating relates to the
voltage waveform applied to the motor windings - When connected to the line a normal sine wave has
a peak voltage of approx 800V - PWM output with voltage reflection due to fast
rise time (0.1 msec) and long cable can approach
two times the peak voltage (1600V). - Recommend using a Nema MG1 Part 31 motor for new
installations - For retrofit installations use an output LRC
dv/dt filter - Some installations with short cables can use a
load reactor.
21Component VFD vs Packaged System
- Stand Alone Component VFD
- VFD mounted and individually connected to
external components (in their own enclosures)
such as - Disconnects or Circuit Breakers
- Fuses
- Reactors and/or filters
- Bypass components
- Packaged System
- VFD and components mounted and wired in a Nema 1
wall or floor mount enclosure
22Component VFD vs Packaged System
- A Packaged System provides the following
benefits - More cost effective vs Field mounting and
interconnecting - Less space required
- Avoids finger pointing re warranty issues
- Reduces material management on site
23System Components
Fused Disconnect
Bypass
Load Reactor or LRC filter
VFD
O/L
Line Reactor or Harmonic Filter
24Harmonics
- Many devices are defined as non-linear and
draw current from the line in such a manner as
to induce current harmonics. Examples are - Adjustable Speed Drives (AC DC)
- UPS
- Switch-mode power supplies (computers)
- Electronic ballasts
- Phase converters
25What Are Harmonics
- Basic power source is 575/3/60
- Base or fundamental frequency is 60Hz -
Sinusoidal - We will see that VFD line current is a
distorted waveform - A repeating, distorted waveform can be expressed
as the Fundamental multiples of the fundamental -
26Loads Without Harmonics
- Most common loads do not cause harmonics e.g.
- Incandescent light bulbs
- Baseboard heaters
- Motors
- These are known as Linear Loads
- The current they draw follows the voltage
27Loads With Harmonics
- These are known as Non-Linear Loads
- The current they draw does not follow the
voltage
28Harmonics
Voltage
Current
Non-Linear Load Fund. Current Harmonics
Linear Load Fund. Current
29Harmonics
Non-Linear Load Reduced Harmonic Content
Non-Linear Load High Harmonic Content
30What are Harmonics?
Fundamental (60Hz)
3rd Harmonic (180Hz)
2nd Harmonic (120Hz)
31Harmonics
- Fundamental 5th Harmonic 7th Harmonic
Fundamental
5th Harmonic
7th Harmonic
Note Lowest harmonic in 6 pulse VFDs is the 5th
32Effects of Harmonics
- Previous slides referred to Current Distortion
- Current Distortion results in Voltage Distortion
- Potential for overheating of Transformers, Motors
- Harmonic resonance
- High neutral currents (1 ph - 3rd harm.)
33IEEE 519
- Originally introduced in 1981 to place limits of
Voltage Distortion on the power utility at a
point of common coupling between users at the
Utility level. - The 1992 revision added limits of Current
Distortion relative to the system in which
non-linear loads are utilized.
346 12 Pulse Configuration
-
-
6 Pulse
12 Pulse
35IEEE 519
- A simplified summary of the 1992 revision can be
expressed as - A small non-linear load installed in a
large or
stiff system will not result in excessive
harmonic distortion. - As the ratio of non-linear loads vs system
capacity increases, mitigation of harmonic levels
may be necessary.
36IEEE 519 - 1992
- current (fundamental frequency component) at PCC.
- Current distortions that result in a dc offset,
e.g., half-wave converters, are not allowed.
37IEEE 519 PCC
Xfmr 1
xxMVA 69kV / 13.8kV
PCC-1
xxkVA 13.8kV / 480V
Xfmr 2
PCC-2
X
VFD
M
M
M
M
38IEEE 519 - PCC
- From the previous slide
- The intent of IEEE 519 is not to define the
PCC as point X but rather as points PCC 1 or 2
depending on the Utility metering point. (TDD
applied here) - If Xfmr 1 has a large MVA value the ISC will be
large as well leading to a greater ISC/IL value
thus a higher allowable TDD.
39IEEE 519 - PCC
- From the previous slide
- The practice suggested is to reduce the harmonic
distortion at point X but measure the results
at the PCC which is the intent of IEEE 519 - Specifying that TDD be met at point X can lead
to expensive solutions and may not be possible.
40IEEE 519 - PCC
- From the previous slide
- If calculated levels of both Current and Voltage
distortion are required at the quotation stage
the following must be made available - A single line diagram
- Transformer details to calculate Isc
- Load details to calculate IL
- A specified PCC
-
41Harmonic Solutions
- If the IEEE 519 levels at the PCC cannot be met,
then harmonic mitigation must be employed.
- Reduce Harmonic Levels by
- Adding Line Reactors
- 12 , 18 .Pulse Configuration
- Add Tuned Filter Traps
- Add Passive Broadband Filters
- Add Active Filters
- Add Active Front End
42Harmonic Solutions
- The various solutions will reduce current
distortion values in varying degrees
- A 6 pulse VFD without any filtering will
typically have a current distortion level of
approximately 75 - Adding line reactors will reduce this to 35-40
at a low cost - Mid level filtering or 12 pulse systems can
achieve levels of 9-15 at increased cost
43Harmonic Solutions
- High level filtering or 18 pulse systems can
reduce the current distortion level down to
approximately 5 at a further increase in cost
44Summary
- The solutions have limitations
- Tolerance of Voltage unbalance
- Leading power factors at light load
- Compare efficiency
- Compare size
-
45(No Transcript)
46Note physical size of Harmonic Filters relative
to Drive Panels beside them
47Bypass Packagewith Input andOutputReactors
48Summary
-
- There are various solutions
- Specify performance not the method
-