Title: Building Energy Codes Program Commercial Program Review
1Commercial Energy Code Compliance IECC 2000/
2001/2003 Compliance Lighting Requirements Chapter
8 IECC
U.S. Department of Energy Building Energy Codes
Program
2Overview of Code ComplianceStructure of the IECC
- Chapter 1 Administrative Enforcement
- Chapter 2 Definitions
- Chapter 3 Design Conditions
- Chapter 4 Residential - Systems Analysis
- Chapter 5 Residential - Component Performance
- Chapter 6 Simplified Prescriptive Requirements
- Chapter 7 ASHRAE 90.1 Energy Code Reference
- Chapter 8 Design by Acceptable Practice for
Commercial Buildings - Chapter 9 Referenced Standards
Commercial Chapters
3Outline
- Overview of Commercial Energy Codes
- Code Requirements
- Building Envelope
- Mandatory Requirements
- Prescriptive Requirements
- Mechanical Systems
- Simple Systems
- Complex Systems
- Service Water Heating
- Lighting Systems
-
Requirements for Chapter 7 (ASHRAE 90.1) are
covered in a separate presentation
For additional training materials see
www.energycodes.gov/training/presentations.stm
4IECC Chapters 7 and 8
5IECC Chapter 8Design by Acceptable Practice
Building System
Compliance Options
Prescriptive Option
Envelope
Energy Code Compliance
Trade Off Option
Lighting
Mechanical
Performance Option
HVAC
SWH
This presentation covers the Mandatory and
Prescriptive requirements, see COMcheck-EZ
materials for information on the Trade-off and
Performance Options. For additional training
materials see www.energycodes.gov/training/presen
tations.stm
6Presentation Reference
Code year covered in current presentation.
Building System covered by material
IECC Chapter Reference (7 or 8)
Mechanical
Lighting
Envelope
2000/2001/2003 IECC
Section
Mandatory Requirements
Power Requirements
Includes section
Type of requirement covered by material
This presentation covers 2000/200/2003 IECC
Lighting Requirements 2001/2003 requirements
are listed in red.
7Scope
- Applies to the design of the
- first installed lighting systems
- altered system that increases the lighting load
if change of occupancy - Lighting systems used for specialized commercial,
display and emergency use purposes are exempt
(Section 805.4.1)
8Interior Lighting Compliance
Mandatory Requirements
Interior Lighting Power Requirements
and
Controls
The building complies if its total connected
power is no greater than the interior lighting
power.
Switching
Total Connected Power (805.4.1)
Interior Lighting Power (805.4.2)
lt
Entire Building
Partial Building
9Interior Lighting Controls
- Lighting controls required for each area enclosed
by ceiling height partitions - Switch locations
- In view of lights
- On or off indication from remote location
- Occupancy sensor
Section 805.2.1
10Interior Lighting Controls
- Exceptions
- Emergency/security lighting
- Stairway or corridor lighting for egress
Section 805.2.1
11Additional Controls
- Each area with mandatory controls must have
- Light reduction controls (805.2.2.1) included in
2003 - Automatic lighting shutoff (805.2.2.2) 2001
Supplement - Guestrooms (805.2.2.3) included in 2003
- Exceptions
- Areas with only 1 luminaire
- Areas with an occupant-sensing device
- Corridors, storerooms, restrooms, or public
lobbies
Section 805.2.2
12Bi-Level SwitchingLight Reduction Controls
- Areas that are required to have manual control
shall also - Reduce connected lighting load uniformly by 50
for each space - Exceptions
- Area has one luminaire
- Occupancy sensor controls area
- Area is corridor, storeroom, restroom, or public
lobby - Guest rooms
- Spaces that use less than 0.6 Watts per square
foot - (in 2001 IECC requirement applied to areas lt 250
ft.2)
Section 805.2.2.1
13Bi-Level Switching
14Bi-Level Switching
Example Alternate Lamps (a/b)
Example Dimmer Control Option
15Automatic Lighting Shutoff
- In buildings gt 5000 ft2
- must have automatic control devices to function
either on - Scheduled basis using time-of-day
- Unscheduled basis by occupant intervention
- In 2001 IECC requirement for spaces gt250 ft2 in
buildings larger than 5,000 ft2
Section 805.2.2.2
16Occupant Override
- Where automatic time switch control devices are
installed to comply with Automatic Lighting
Shutoff, device shall be equipped with an
override switching device that - Readily accessbile
- Located so that person using the device can see
the lights or area controlled by the switch - Manually operated
- Allows lighting to remain on for no more than 2
hours when an override is initiated - Controls an area lt5,000 square feet
- Some Exceptions
Section 805.2.2.2.1
17Holiday scheduling
- If automatic time switch is installed
- Automatic holiday scheduling feature that turns
off all loads for at least 24 hours and then
resumes to normally scheduled operation - Exceptions
- Retail stores and associated malls, restaurants,
grocery stores, churches and theaters
18Guest Rooms
- Master switch required at entry
Standard Room
Suite
Section 805.2.2.2
19Exterior Lighting Controls
- Automatic switching or photocell controls shall
be provided for all exterior lighting not
intended for 24 hour operation. - Automatic time switches shall have a combination
- Seven-day and seasonal daylight program schedule
adjustment - A minimum 4-hour power backup
20Tandem Wiring
Center to Center
- Exceptions
- Luminaires with electronic high-frequency
ballasts - Luminaires not on same switch controls or not in
the same area
Section 805.3
21Exit Signs
- Internally illuminated exit signs shall not
exceed 5 Watts per side
Section 805.4
22Interior Lighting Power Requirements
Mandatory Requirements
Interior Lighting Power Requirements
and
Controls
The building complies if its total connected
power is no greater than the interior lighting
power.
Switching
Total Connected Power
Interior Lighting Power
lt
Entire Building
Partial Building
Section 805.4/805.5
23Total Connected Power
- Total connected lighting wattage includes
- Lamp wattage
- Ballast wattage
- Sources of bulb/ballast wattages
- Manufacturers literature
- Industry default tables
- Exceptions
- Specialized medical, dental, and research
lighting - Professional sports arena playing field lighting
- Display lighting for gallery exhibits, museums,
and monuments - Guest room lighting in hotels, motels, boarding
houses, or similar buildings - Emergency lighting automatically off during
normal building operation
24Interior Lighting Power
Mandatory Requirements
Interior Lighting Power Requirements
and
Controls
The building complies if its total connected
power is no greater than the interior lighting
power.
Switching
Total Connected Power
Interior Lighting Power
lt
Entire Building
- Entire building
- Building is all one occupancy or a majority
occupancy exists (Section 101.4.3) - Tenant area or partial building
- Use for tenant spaces in larger building or
divide whole building into area types - Table 805.4.2/Table 805.5.2
Partial Building
25What is the Interior Lighting Power Budget for
this Building?
26Does the Building Comply?
- Determine the total connected power in watts for
the proposed lighting - Determine the interior lighting power budget for
the entire building or space - Building complies if
- Interior lighting power budget - total connected
power ?0
27Exterior Lighting
- Criteria
- Lighting power supplied through building
electrical service - Must use energy-efficient lighting sources to
highlight paths, walkways and parking areas - ? 45 Lumens/Watt
- Fluorescent
- Compact Fluorescent
- Metal Halide
- High Pressure Sodium
- Exceptions
- Where approved because of the following
considerations - Historical
- Safety
- Signage
- Emergency
Section 805.5/805.6
28Energy-Efficient Lighting Sources
29Electrical Energy Consumption
- In buildings having individual dwelling units,
provisions shall be made to determine the
electrical energy consumed by each tenant by
separately metering individual dwelling units
Section 805.7
30 More Information
- For additional training materials see
- www.energycodes.gov/training/presentations.stm
- Code Books
- www.iccsafe.org