1Line differential relay 7SD52
Line differential relay for HV and UHV
lines/cables with a serial communication
interface 7SD52
2Protection and communication join togetherThree
benefits of the 7SD52
- Differential protection for the universal
use with easy to handle settings Two up
to six line ends , for serial and parallel
compensated lines, handles transformers and
compensation coils within the protection zone,
tripping time approx. 15 ms with fast high
set element - Additional functions for very long overhead
lines and cables Considation of local CT
errors, charge current compensation (step
2), increased setpoint during switching-on
conditions - Direct and modular connection to fibre optic
and digital communication networks
3Application for a three terminal configuration
Monomode fibre optic cable up to 35 km with 1300
nm interface
Monomode fibre optic cable up to 10 km (1300 nm
modul)
Distance relay 7SA52
X21 G703.1
SDH comms-network
o
e
820 nm max. 3 km
e
o
OptionI-REGB
Comms- converter G703.1 64 kBitX21 N64
kBit (1?N?8)
time synchronisation
4Scope of functions / Hardware options
Options for the Protection Interface
Scope of functions - Fast high set element
with charge comparision- Sensitive normal trip
stage with vector summation principle -
Autoreclosure 1/3 pole - Communication features -
Commissioning aid - Overload protection -
Backup-/emergency overcurrent - Multiterminal
extention- Switch on to fault protection- 4
remote commands 24 remote signals
Relay Hardware
820 nm1,5 / 3 km multimode
ST- connector
3Iph, and IE 4 U 8 binary inputs 16 contacts
1 - 2 protection interfaces System
interface PC-interface Time synchronisation
internal
1300 nm10 kmmonomode
ST- connector
internal
½19
16 binary inputs 24 contacts 24 binary inputs 32
contacts Option 5 fast trip contacts
O
1300 nm35 kmmonomode
FC- connector
internal
ElectricalX21 G703.1interface
820 nm1,5 kmST-connectors
119
External converter
5Hardware option of the comms interfaces
Remote line end 2
Plug in modules
Remote line end 1
Protection interface 1Port D
Synchronous N x 64kB/sec
Subst. control interface
Substation control
communication modules
Interfacemodul 2
FO (Fibre optic) or RS485or RS232 Available
ProtocolsIEC - standard
RS485 or FO
6Main board of the relay with its Communication
- Interfaces
Main processor board of the relay Sockets for
the communicationmodules
7Main protection functionFeatures of the
differential function
- Phase selective multiend differential
protection(2 - 6 ends). Tripping time 15 ms with
fast charge comparison protection. - Fundamental vector comparison for the sensitive
trip stage. - Dynamic increase of differential setpoint during
switch-on of long lines / cables (settable time) - CT saturation detector (only 5 ms saturation free
time due to external faults necessary) - Phase selective intertrip within 15 ms
- Settable delay time for single phasefaults
(feature for inductive compensated networks) - Option Inrush 2nd harmonic restraint with
vector group adaption. Undelayed trip for high
fault currents - Optional Lockout function
8Adaptive differential relayingConsideration of
CT- errors and comms-errors
I1
I2
IDiffIN
Tripping area
I2
I3
I3
Restraint area
I1
IDiffgt
I1
I IN
IDiff I1 I2 I3
Phasor summation Error summation
I IDiffgt Linear CT-error (
Syncronization error
IK)
Trip, if diff.current exceeds the max.
permissible error
9To complete the 7SD52Additional functions
- 3 stage backup- or emergency O/C protection(Can
be activated automatically if the communication
with the remote end is gt50 ms interrupted) - Overload function (Thermal replica with
IOperation) - User definable logic and control functions(AND,
OR, NOT, Timer, Flip-Flop) - 4 remote commands via binary input or logic
inputs (destination is adressable), 24 remote
signals - Operational values currents, voltages,
power,delay time, differential current - remote
end refresh 2 s - Fault recorder with voltages, currents, binary
traces and differential and restraint current per
phase - Fast monitoring functions(Fast broken wire
supervision, Current symmetry) - Switch On to Fault protection
- Option Three pole and single pole AR (Single
pole AR during 2pole fault without earth
possible, adaptive AR)
10Familiar with digital communication networks
Features of the relay to relay communication
- Synchronous data transmission by HDLC- protocol
- Permanent supervision of the data transmission
- Measurement and compensation of signal
transmission time (max. 20 ms) - Counts number of invalid telegrams
Blocking the diff.protection if transmission
failure rate is too high - Settings for the data transmission (N64
kBit/s, N settable from 1 - 8, synchronous
HDLC-protocol) - Communication device addresses (Protection
devices are clearly assigned to a defined
protection section) - Detection of reflected data in the loops in
comms- network - Step 2 Microsecond exact time synchronisation
via satellite (civil - IRIG-B) (If
signal transmission time depends on the
transmission direction, Online high
resolution fault recorder)
11Ring and Chain topologie
Automatic change fromclosed ring to chain, if
one connection is lost or not available
side 2
side 3
I2
Connection to other diff. relays
I3
I3I1
I2
I1I2
I3
I1
I3I1
I1I2
side 1
Closed ring
Partial current summation
12Topologies Chain topology for max. 6 line ends
1
3
2
PI1
PI1
PI2
PI1
PI2
PI - Protection Interface
PI1
4
6
5
PI2
PI1
PI2
PI1
13Topologies Ring topology, 6 line ends
3
1
2
PI1
PI2
PI1
PI2
PI2
PI1
PI1
PI2
4
6
5
PI2
PI1
PI2
PI1
PI - Protection Interface
14Plug and Protect Commissiong helps and test
features
- Signal transmission timeMean value of transmit
and receive direction - Generation of signals for switching test
loopsSending of defined telegram patterns looped
back to the receive input of the transmitting
relay - Absolute value and phase measurement of
currentsLocal measurement of angle between IL1,
IL2, IL3,Angle between currents of each phase
from remote - CB test trip
- Counting of faulty telegrams in per minute and
hour - Activation of binary inputs and outputs by
operating software DIGSI 4. - Display of the status of binary inputs
- Test telegrams to the substation control system
- Automatic Switchover from 3 line to 2 line end
configuration (while commissioning 3rd line end) - Complete commissioning support with DIGSI 4
andbrowser based PC-software
IL1_2
Phi1-gt2
IL1_1
IL2_1
IL2_2
IL3_2
IL3_1
15Browser based commissioning aid
16Comprehensive fault analysis with DIGRA 4
17Prefault and fault conditions in the vector
diagram