1
LAC Epics (Windows) IOC
  • SLS Controls Pikett Training

2
What is the LAC (Windows) IOC used for?
  • The SLS Local Access Control system (SLS LAC)
    controls the person admission to the optics and
    experimentation areas of the SLS Beamlines.
  • The SLS LAC system based on a PhoenixContact.Inter
    bus OPC server (located at WSLA.7.0.56)
  • The SLS LAC system is maintained from the Section
    9310 Steuerungssysteme, (Stefan Staudenmann
    tel. 3737)
  • The Epics implementation was done to view the SLS
    LAC status on the Alarm handler and other Epics
    clients.

3
How the SLS LAC is implemented in Epics
  • All SLS LAC information is Read Only from
    Epics.
  • A windows XP (PC5150) run a IOC with OPC device
    support.
  • The IOC device support is based on Bessy GmbHs
    code.
  • The OPC toolkit used at SLS is version 4.01 from
    Softing.com
  • The current used epics version is 3.14.6
  • The LAC IOC is currently running on the PSI
    office network!
  • CVS location is X/LAC

4
Testing the LAC IOC
  • If all LAC PVs are neither disconnected, nor
    invalid, nor not avaiblethe problem does not
    have to do with the LAC IOC. Section 9310 must be
    informed.
  • Some existing PVs to test are
  • X00GA-GE-LAC99_01 Alive bit and valid between
    06, if a value more then 60, reboote the LAC
    IOC.
  • X00GA-GE-LAC01_10 X06SA-OP-LAC01_01 _02
    ..._03
  • caget from the office network and if valid from
    the machine network. If they are only visible on
    the office network, the problem may be the
    Channel Access Gateway
  • If this PVs have problems on the office network,
    the Windows LAC IOC must be rebooted.

5
Reboot LAC IOC (PC5150)
  • Create a VNC connection to PC5150
  • On the office network open browser Adress
    http//pc5150.psi.ch5800/
  • only the VNC password must be
    entered.
  • On the terminal start-Interbus-local type exit
    to close the IOC.
  • Click the start button (button left corner of
    Windows screen) and then select "Shut Down".
  • Make shure "Restart" is selectedon "What do you
    want the com-puter to do?"

6
Re-Login PC5150 (LAC IOC)
  • It takes about 2 minutes until the PC is
    rebooted.
  • Then VNC login to PC5150 (see prev. Page)
  • The Welcome to Windowsscreen apears.
  • Because of using VNC,Press Shift-Ctrl-Alt-Del
    to login

7
Known unsolved LAC IOC problems
  • The IOC should be moved from the office network
    to the machine network.
  • The LAC IOC should be started as a Windows
    service. - This would prevent the need of login
    after rebooting the PC.