Title: Module 05: Industrial Valve
1Module 05 Industrial Valve
21.0 Introduction
- Fluid Any substance that flow from one area to
another area when it subjected to a normal and
shear stress. Gases and liquids are both
considered fluids - Valve A mechanical device that is used in
industrial piping to control the flow of fluids - On-Off Service Valve that only operate in the
fully open or fully closed positions are said to
provide on-off service
31.0 Introduction.
- Throttling Service Valves that control flow by
partially restricting the passage of the fluids
provide in what is called throttling service. - Pressure Drop The loss of energy that occurs
when a fluid encounters resistance passing
through a valve. The greater resistance, the
higher the pressure drop for a given flow rate. A
higher pressure drop means that more energy in
the form of pumping or compressing, must be used
to move the fluid through the piping.
42.0 Valve Functions And Applications
- Shut-off valves (block valves), whose purpose is
to close off the flow - Control valves, both manual and automatic, used
to regulate flow
5Selecting a Valve Type
- When speaking of valves, it's easy to get lost in
the terminology. Valve types are used to
describe the mechanical characteristics and
geometry (Ex/ gate, ball, globe valves). We'll
use valve control to refer to how the valve
travel or stroke (openness) relates to the flow - Equal Percentage equal increments of valve
travel produce an equal percentage in flow
change - Linear valve travel is directly proportional to
the valve stroke - Quick opening large increase in flow with a
small change in valve stroke
6Equal Percentage (most commonly used valve
control)
- Used in processes where large changes in pressure
drop are expected - Used in processes where a small percentage of the
total pressure drop is permitted by the valve - Used in temperature and pressure control loops
7Linear
- Used in liquid level or flow loops
- Used in systems where the pressure drop across
the valve is expected to remain fairly constant
(ie. steady state systems)
8Quick Opening
- Used for frequent on-off service
- Used for processes where "instantly" large flow
is needed (ie. safety systems or cooling water
systems)
9Typical Industrial Valve
10Gate Valve
11Gate Valve
- Best Suited Control Quick Opening
- Recommended Uses1. Fully open/closed,
non-throttling2. Infrequent operation3.
Minimal fluid trapping in line - Applications Oil, gas, air, slurries, heavy
liquids, steam, noncondensing gases, and
corrosive liquids
12Gate Valve
- Advantages
- High capacity
- Tight shutoff
- Low cost
- Little resistance to flow
- Disadvantages
- Poor control
- Cavitate at low pressure drops
- Cannot be used for throttling
13Globe Valve
14Globe Valve
- Best Suited Control Linear and Equal percentage
- Recommended Uses1. Throttling service/flow
regulation2. Frequent operation - Applications Liquids, vapors, gases, corrosive
substances, slurries
15Globe Valve
- Advantages
- Efficient throttling
- Accurate flow control
- Available in multiple ports
- Disadvantages
- High pressure drop
- More expensive than other valves
16Ball Valve
17Ball Valve
- Best Suited Control Quick opening, linear
- Recommended Uses1. Fully open/closed,
limited-throttling2. Higher temperature fluids - Applications Most liquids, high temperatures,
slurries
18Ball Valve
- Advantages
- Low cost
- High capacity
- Low leakage and maintenance
- Tight sealing with low torque
- Disadvantages
- Poor throttling characteristics
- Prone to cavitation
19Butterfly Valve
20Butterfly Valve
- Best Suited Control Linear, Equal percentage
- Recommended Uses 1. Fully open/closed or
throttling services2. Frequent operation3.
Minimal fluid trapping in line - Applications Liquids, gases, slurries, liquids
with suspended solids
21Butterfly Valve
- Advantages
- Low cost and maintenance
- High capacity
- Good flow control
- Low pressure drop
- Disadvantages
- High torque required for control
- Prone to cavitation at lower flows
22Plug Valve
23Plug Valve
- Best Suited Control Quick Opening
- The valve is positioned by turning a lever
- A quarter turn of the handle will completely open
or close a plug valve - Advantages When line of flow through a plug
valve is straight, so when it is open there is
very little turbulence and pressure drop
24Diaphragm Valve
25Diaphragm Valve
- The stem of the valve is used to push down a
flexible diaphragm, which in turn blocks the path
of the fluid. There are two different
classifications of diaphragm valve based on the
geometry of the valve body - Weir type - A weir is cast into the body, and
when closed, the diaphragm rests on the weir,
restricting the flow - Straight-through type - The bore runs laterally
through the body and a wedge shaped diaphragm is
used to make the closure
26Diaphragm Valve
- Application
- Suitable for handling aggressive fluids and for
those containing suspended solids
27Check Valve
28Check Valve
- Non-return valve
- Application To avoid backflow
29Valve Actuator, Operation And Troubleshooting
30Valve Actuator, Operation And Troubleshooting
- Control Valve A valve used in automatic control
situations that is positioned by a controller.
Any manual valve can be adapted into a control
valve by attaching an actuator to the valve body. - Actuator A device that mechanically moves the
stem of a control valve in response to a signal
from a controller. - Controller An instrument that automatically
positions a control valve. A controller uses the
energy of compressed air, hydraulic fluid
pressure, or electricity to send signals to an
actuator. - Positioner A device that helps the actuator
move the valve stem into the correct position.
31Control Valve
32Body Styles
- Control valves can be designed to have one or two
openings for fluid to pass through. - A valve that has one flow opening is called a
single- ported valve. - Single-ported valves are often used because they
are inexpensive, require little maintenance, and
are resistance to leakage once closed. - The disadvantage of a single valve is that fluid
pressure working against one side of the valve
plug makes the valve difficult to position.
33Body Styles
- While in double-ported valve, there are two paths
for fluid to flow through. - Because of its design, a double-ported valve can
handle higher flow rates than a single-ported
valve of the same size. - Since pressure is exerted somewhat evenly across
the plugs, a double-ported valve is easier to
position than a single-ported valve. - The characteristics of double-ported valves makes
them especially good for throttling service
34(No Transcript)
35Pneumatic Actuator
- The actuator contains a diaphragm and a spring.
It receives compressed air or pneumatic signals
from the controller. - A pneumatic actuator uses compressed air, or air
pressure to move the stem of a control valve. - The compressed air is introduced above the
diaphragm. The air pressure tries to push the
diaphragm down. The spring tries to keep the
diaphragm up. - When the air pressure against the top of the
diaphragm exceeds the force of the spring, the
valve stem is pushed downward and the valve
closes.
36Pneumatic Actuator
- This type of valve is called an air-to-close
valve. Increasing the air pressure above the
diaphragm in an air-to-close valve causes the
valve to close. - Some valves are air-to-open which is increasing
the air pressure to this actuator causes the
valve to open. Air pressure in this actuator
builds up below the diaphragm. - The design of this valve makes it and air-to-open
valve. - Hence, what is important for an operator to know
is whether increasing air pressure opens or
closes a valve. An operator also needs to know
whether a valve fails in the open or closed
position.
37Electrical Actuator
- Some actuators use the energy of electricity to
position a control valve. A solenoid is an
example of this type of actuator. - The solenoid consists of an iron core that slides
in and out of wire coil. - When electrical current is sent through the coil,
a strong magnetic field is set up inside it. This
magnetic field pulls the iron core up into the
coil. When the current stops, the magnetic field
collapses. And, the core is pushed out of the
coil by a spring.
38Electrical Actuator
- The iron core of the solenoid is attached to a
valve stem. An electrical signal from the
controller magnetizes the coil. This pulls the
core up, and the valve is closed. - When the flow of current stops, the core is
pushed out of the coil by the spring, and the
valve opens. - Because of the way a solenoid actuator positions
a valve, it can only be used for on-off service.
39Solenoid Valve
40Introduction to Control Valve
Control Valves Device that manipulates a
flowing fluids, such as gas, steam, water, or
chemical compound, to compensate for the load
disturbance and keep the regulate
process variables as close as possible to the
desired set point
41Control Valve Actuator Nomenclature
- Fail Open, FO or Air To Close, ATC
- A condition wherein the valve port remains open
in the event of - loss of actuator loading pressure to the
diaphragm - - No air/pneumatic, Valve in Open condition
- - 4 mA Fully Open, 20 mA Fully Closed
- Fail Closed, FC or Air To Open, ATO
- The condition wherein the valve port remains
closed in the event - of loss of actuator loading pressure to the
diaphragm - - No air/pneumatic, Valve in Closed condition
- - 4 mA Fully Closed, 20 mA Fully Open
42Control Valve Actuator Nomenclature
1.0 Valve Positioner / Pneumatic Positioner
- The primary function is to ensure that the
control valve stem position is directly
proportional to the respective value of
instrument o/p pressure, regardless of stuffing
box friction, spring hysteresis or off balance
forces on the valve plug - Positioners also
provide a convenient means of changing the
effective o/p pressure range of the controller
and also of changing the valve action 2.0
Actuator Spring - A spring, enclosed in the
yoke, to move the actuator stem in a direction
opposite to that created by diaphragm
pressure 3.0 Actuator Stem - A rod-like
extension of the diaphragm plate to permit
convenient connection to valve plug stem 4.0
Diaphragm - A flexible pressure responsive
element which transmits force to the diaphragm
plate and actuator stem 5.0 Direct Acting
Actuator (ATC) - An actuator in which the
actuators stems extends with increasing diaphragm
force 6.0 Dynamic Force - a force produced
by the fluid pressure on control valve components
while valve is throttling
43Control Valve Actuator Nomenclature
7.0 Fail Closed - A condition
wherein the valve port remains closed in the
event of loss of actuator loading pressure to
the diaphragm 8.0 Fail Open - A
condition wherein the valve port remains open in
the event of loss of actuator loading pressure to
the diaphragm 9.0 PDTC - Push Down
To Close, referring to the motion required to
seat the closure member of a control valve 10.0
PDTO - Push Down To Open, referring to the
motion required to fully open the closure member
of a control valve 11.0 Reverse Acting Actuator
(ATO) - An actuator construction in which
the actuator stem retracts with increasing
diaphragm pressure 12.0 Seat Load - The
total amount of system force, in pounds, that is
exerted against a fully closed control valve plug
or closure member 13.0 Spring Rate
(K) - The measurement of a spring to
determine its stiffness. Defined as the amount of
force in LBs. required to compress the
spring one inch 14.0 Stiffness - The
ability of the actuator to freeze the valve plug
in a desired position. A function of spring rate
44Troubleshooting
- Although an operator is not usually responsible
for repairing valves, he should be able to
identify problems so that the appropriate
maintenance or instrument personnel can be called
in. - This requires troubleshooting skills on the part
of the operator. The problems that occur in
manually-operated valves are often easy to
detect, such as a broken hand wheel or stripped
screw threads. - If the operating mechanism is working properly,
but the valve still wont open or close, you can
assume the problem is inside the valve.
45Troubleshooting
- Check valves do not have an external operating
mechanism. So, when a check valve is not
preventing a reversal of flow, you know the
problem is inside the valve body. - Control valves are usually more difficult to
troubleshoot because more things can go wrong
with them. If a control valve fails, your first
action should be check the controllers signal to
the actuator or valve. - If the signal is incorrect, you know the failure
is being caused by the controller.
46Troubleshooting
- Sometimes the signals from the controller to the
actuator are disrupted by a leak, blockage, or
short in the line that connects these two
components. So, a control valve failure can also
be caused by a problem in the signal transmission
system. Most control valves are equipped with
some type of valve position indicator. - Another possibility is that the actuator is not
working properly. If the diaphragm in a pneumatic
actuator is torn or ruptured, it will not respond
to changes in air pressure. - A burned out coil or motor will cause an
electrical actuator to malfunction.