Title: Part 1. Electric Supply Stations
1Part 1. Electric Supply Stations
Rules for the Installation and Maintenance of
Electric Supply Stations and Equipment
Jack ChristofersenCeCe Thursday -- July 19, 2001
2Section 10. Purpose and Scope
- The purpose of Part 1 is to provide practical
safeguarding of persons performing installation,
operation, or maintenance duties in electric
supply stations.
3Section 10. Purpose and Scope
- The scope covers the electric supply conductors,
equipment and structural arrangements in electric
supply stations, that are accessible only to
qualified personnel including equipment employed
primarily for the utilization of electric power
used by the utility in the exercise of its
function as a utility.
4Section 11 Protective Arrangements in
Electric Supply Stations
5110. General Requirements
- A1. Types of Enclosures
- Metal fences, when used to enclose
electric supply stations having
energized electric conductors or equipment,
shall have a height not less than 7 ft overall
and shall be grounded in accordance with
Section 9.
6110. General Requirements
- A1. Types of Enclosures
- a. Fence Fabric, 7 ft or more in height
- b. A Combination of 6 ft or more or fence
fabric and utilizing 3 or more strands of
barbed wire to achieve an overall height of the
fence of not less than 7ft.
7110. General Requirements
- A2. Safety Clearance Zone
- Fences or walls, when installed as barriers for
unauthorized personnel, shall be located such
that exposed live parts are outside the safety
clearance zone as illustrated in Figure 110-1 and
shown in Table 110-1.
8110. General Requirements
Live parts must be outside of arc
7ft min.
R
Fence
R
5 ft
Fig 110-1
9110. General Requirements
30
- B. Rooms and Spaces
- All rooms and spaces shall comply with the
following requirements - 1. Construction
- They shall be as much as practical
noncombustible. - NOTE This Rule is not intended to prevent wood
poles from being used to support conductors or
equipment in electric supply stations.
10110. General Requirements
30
- B. Rooms and Spaces
- 2. Use
- They should be as much as practical free from
combustible materials, dust, and fumes and shall
not be used for manufacturing or for storage. - EXCEPTION 1 Equipment or materials essential for
maintenance of installed equipment may be stored
if guarded from live parts as required by Rule 124
11110. General Requirements
30
- B. Rooms and Spaces
- EXCEPTION 2 Materials related to station,
transmission, or distribution construction and
maintenance work may be stored in the station if
located in an area separated from the station
electric supply equipment by a fence meeting the
requirements of Rule 110A.
12110. General Requirements
30
- B. Rooms and Spaces
- EXCEPTION 3 Stored material related to station,
transmission, and distribution construction and
maintenance work in progress may be temporarily
located in a storage space meeting all of the
following requirements
13110. General Requirements
30
- B. Rooms and Spaces
- (1) Guarded or separated from live parts as
required by Rule 124 - (2) Station exits continue to meet the
requirements of Rule 113 - (3) Station working space continues to meet the
requirements of Rule 125 - (4) Access is limited to qualified personnel
- (5) The storage location and content is such that
the risk of fire does not unreasonably jeopardize
station operation.
14Section 12
Installation and Maintenance of Equipment
15120. General Requirements
A. All electric equipment shall be constructed,
installed, and maintained so as to safeguard
personnel as far as practical. B. The Rules of
this Section are applicable to both ac and dc
supply stations.
16124. Guarding Live Parts
Live Part
GUARD ZONE AT RADIUS R, SEE COLUMN 4, TABLE
124-1
VERTICAL CLEARANCE SEE COLULMN 2
TABLE 124-1
HORIZONTAL CLEARANCE SEE COLUMN 3, TABLE 124-1
Fig 124-1
17124. Guarding Live Parts
A. Types of Guards 3. Supplemental Barriers or
Guards Within Electric Supply Stations Railings
are not substitutes for complete guards. If the
vertical distance in Table 124-1 cannot be
obtained, railings or fences may be used.
Railings or fences, if used, shall be not less
than 1.07 m (3.5 ft) high and shall...
18124. Guarding Live Parts
Table 124-1 Part DHigh Voltage Direct Current
(Based on Transient Overvoltage)
19Section 15. Transformers and Regulators
20150. Current-Transformer Secondary Circuits
Protection When Exceeding 600 Volts
- (Old Rule)
- Secondary circuits, when in a primary voltage
area exceed 600 V should, except for short lead
lengths at the terminals of the transformer, have
the secondary wiring adequately protected by
means of grounded conduit or by a grounded
metallic covering. Current transformers shall
have provision for shorting the secondary wiring.
21150. Current-Transformer Secondary Circuits
Protection When Exceeding 600 Volts
- (New Rule)
- Secondary circuits, when in the vicinity of
primary circuits exceeding 600 V should, except
for short lead lengths at the terminals of the
transformer, have the secondary wiring adequately
protected by means of conduit covering or some
other protection. Any metallic covering used
shall be effectively grounded, giving appropriate
consideration to circulating currents. Current
transformers shall have provision for shorting
the secondary winding.
22Section 17. Circuit Breakers, Reclosers,
Switches, and Fuses
23170. Arrangement
Circuit breakers, reclosers, switches, and fuses
shall be so installed as to be accessible only to
persons qualified for operation and
maintenance... Conspicuous markings (such as
numbers/ letters/ symbols) shall be provided on
each device and at any remote operating points so
as to facilitate identification by employees
authorized to operate the device. No device
identification shall be duplicated within the
same supply station.