Title: NESC Subcommittee 2
1NESC Subcommittee 2
IEEE
Ewell T. (Tim) Robeson Carolina Power Light
Co. July 19, 2001
2 NESC Grounding Methods
- Presentation Objectives
- Working Group 2.1 Report- Section 2 Definitions.
Definitions for different types of grounded or
ungrounded electric supply systems. - Subcommittee 2- Section 9, Grounding Methods for
Electric Supply and Communications Facilities,
2002 NESC
3NESC Working Group 2.1
- Established 1996 -Provide definitions of methods
to ground electric supply systems. - Proposed Definitions appear in the 2002 NESC
Pre-print. Comment period resulted in some
revision.
4Grounding Definitions
- Section 2- New definitions related to system
grounding. - Multigrounded/multiple grounded system
- Neutral conductor
- Shield wire conductor
- Single grounded/unigrounded
- Ungrounded system
5NESC Subcommittee 2
- Section 9 revisions
- Rule number system changed (Example- Rule 93. is
now Rule 093.) - Metallic (underline is an addition)
- Part (Strikethrough is a deletion)
6Section 9 Revisions
- Rule 093AMetallic electrical equipment cases or
the structural metal frame of a building or
structure may serve as part of a grounding
conductor to an acceptable grounding electrode.
7Section 9 Revisions, Cont..
- Rule 093C4. EXCEPTION Arrester grounding
conductors may be copper-clad or aluminum-clad
steel wire having not less than 30 of the
conductivity of solid copper or aluminum wire of
the same diameter, respectively.
8Section 9 Revisions, Cont..
- Rule 094B2b. Longer rods or multiple rods may be
used to reduce the ground resistance. Spacing
between multiple rods should be not less than 1.8
m (6 ft) - EXCEPTION Other dimensions or configurations may
be used if their suitability is supported by a
qualified engineering study
9Section 9 Revisions, Cont..
- Rule 096C. Multi-grounded systems
- RECOMMENDATION This Rule may be applied to
shield wire(s) used as lightning protection
conductor(s), which is grounded at the source and
that meets the multigrounding requirements of
this Rule
10Section 9 Revisions, Cont..
- Rule 097A. (Note 3 has moved to note 4 and a new
note 3 is added)3. Shield wires of power
circuits -
11Section 9 Revisions, Cont..
- 097B- The grounding conductors of either of the
equipment classes detailed in Rules 97A1, and
97A2, and 97A3 may be interconnected utilizing a
single grounding bonding conductor, provided - 2. The secondary neutral, or the grounded
secondary phase conductor is common with or
connected to primary neutral, or a shield
wire...
12Section 9 Revisions, Cont..
- Rule 097D. Ungrounded or Single-Grounded and
Multi-Grounded Systems - 1. Ungrounded or Single-Grounded SystemsWhere
the secondary neutral is not interconnected with
the primary surge-arrester grounding - . The primary grounding conductor, or the
secondary grounding conductor, shall be insulated
for 600 V.
13Section 9 Revisions, Cont..
- Rule 097G. Except where separation is required in
Rule 97A, communication systems messengers are to
be grounded on a joint use structure containing
an electric supply grounding electrode conductor,
the grounding system of the communication system
should be bonded with the grounding electrode
conductor of the electric supply system. Where
the electric supply utility is maintaining
isolation between primary and secondary neutrals,
the communication system ground shall be
connected to the primary ground conductor.
14Section 9 Revisions, Cont..
- Rule 099C. Bonding of Electrodes
- A bond not smaller than AWG No. 6 copper or
equivalent shall be placed between the
communication grounding electrode and the supply
system neutral grounding electrode where separate
electrodes are used in or on the same building or
on the same served structure.
15Section 9 Revisions, Cont..
Rule 099C. Bonding of Electrodes, Cont.
- A bond not smaller than AWG No. 6 copper or
equivalent shall be..served structure. - RECOMMENDATION If water piping is used as a
bonding means, care must be taken to assure that
the metallic path is continuous between
electrodes. - Note See NEC Article 800-40(d) for
corresponding NEC requirements.
16?? Questions ??
IEEE
Thank you! Ewell T. (Tim) Robeson, PE Carolina
Power Light Co. July 19, 2001
17Part 1. Electric Supply Stations
Rules for the Installation and Maintenance of
Electric Supply Stations and Equipment
Jack ChristofersenCeCe Thursday -- July 19, 2001
18Section 10. Purpose and Scope
- The purpose of Part 1 is to provide practical
safeguarding of persons performing installation,
operation, or maintenance duties in electric
supply stations.
19Section 10. Purpose and Scope
- The scope covers the electric supply conductors,
equipment and structural arrangements in electric
supply stations, that are accessible only to
qualified personnel including equipment employed
primarily for the utilization of electric power
used by the utility in the exercise of its
function as a utility.
20Section 11 Protective Arrangements in
Electric Supply Stations
21110. General Requirements
- A1. Types of Enclosures
- Metal fences, when used to enclose
electric supply stations having
energized electric conductors or equipment,
shall have a height not less than 7 ft overall
and shall be grounded in accordance with
Section 9.
22110. General Requirements
- A1. Types of Enclosures
- a. Fence Fabric, 7 ft or more in height
- b. A Combination of 6 ft or more or fence
fabric and utilizing 3 or more strands of
barbed wire to achieve an overall height of the
fence of not less than 7ft.
23110. General Requirements
- A2. Safety Clearance Zone
- Fences or walls, when installed as barriers for
unauthorized personnel, shall be located such
that exposed live parts are outside the safety
clearance zone as illustrated in Figure 110-1 and
shown in Table 110-1.
24110. General Requirements
Live parts must be outside of arc
7ft min.
R
Fence
R
5 ft
Fig 110-1
25110. General Requirements
30
- B. Rooms and Spaces
- All rooms and spaces shall comply with the
following requirements - 1. Construction
- They shall be as much as practical
noncombustible. - NOTE This Rule is not intended to prevent wood
poles from being used to support conductors or
equipment in electric supply stations.
26110. General Requirements
30
- B. Rooms and Spaces
- 2. Use
- They should be as much as practical free from
combustible materials, dust, and fumes and shall
not be used for manufacturing or for storage. - EXCEPTION 1 Equipment or materials essential for
maintenance of installed equipment may be stored
if guarded from live parts as required by Rule 124
27110. General Requirements
30
- B. Rooms and Spaces
- EXCEPTION 2 Materials related to station,
transmission, or distribution construction and
maintenance work may be stored in the station if
located in an area separated from the station
electric supply equipment by a fence meeting the
requirements of Rule 110A.
28110. General Requirements
30
- B. Rooms and Spaces
- EXCEPTION 3 Stored material related to station,
transmission, and distribution construction and
maintenance work in progress may be temporarily
located in a storage space meeting all of the
following requirements
29110. General Requirements
30
- B. Rooms and Spaces
- (1) Guarded or separated from live parts as
required by Rule 124 - (2) Station exits continue to meet the
requirements of Rule 113 - (3) Station working space continues to meet the
requirements of Rule 125 - (4) Access is limited to qualified personnel
- (5) The storage location and content is such that
the risk of fire does not unreasonably jeopardize
station operation.
30Section 12
Installation and Maintenance of Equipment
31120. General Requirements
A. All electric equipment shall be constructed,
installed, and maintained so as to safeguard
personnel as far as practical. B. The Rules of
this Section are applicable to both ac and dc
supply stations.
32124. Guarding Live Parts
Live Part
GUARD ZONE AT RADIUS R, SEE COLUMN 4, TABLE
124-1
VERTICAL CLEARANCE SEE COLULMN 2
TABLE 124-1
HORIZONTAL CLEARANCE SEE COLUMN 3, TABLE 124-1
Fig 124-1
33124. Guarding Live Parts
A. Types of Guards 3. Supplemental Barriers or
Guards Within Electric Supply Stations Railings
are not substitutes for complete guards. If the
vertical distance in Table 124-1 cannot be
obtained, railings or fences may be used.
Railings or fences, if used, shall be not less
than 1.07 m (3.5 ft) high and shall...
34124. Guarding Live Parts
Table 124-1 Part DHigh Voltage Direct Current
(Based on Transient Overvoltage)
35Section 15. Transformers and Regulators
36150. Current-Transformer Secondary Circuits
Protection When Exceeding 600 Volts
- (Old Rule)
- Secondary circuits, when in a primary voltage
area exceed 600 V should, except for short lead
lengths at the terminals of the transformer, have
the secondary wiring adequately protected by
means of grounded conduit or by a grounded
metallic covering. Current transformers shall
have provision for shorting the secondary wiring.
37150. Current-Transformer Secondary Circuits
Protection When Exceeding 600 Volts
- (New Rule)
- Secondary circuits, when in the vicinity of
primary circuits exceeding 600 V should, except
for short lead lengths at the terminals of the
transformer, have the secondary wiring adequately
protected by means of conduit covering or some
other protection. Any metallic covering used
shall be effectively grounded, giving appropriate
consideration to circulating currents. Current
transformers shall have provision for shorting
the secondary winding.
38Section 17. Circuit Breakers, Reclosers,
Switches, and Fuses
39170. Arrangement
Circuit breakers, reclosers, switches, and fuses
shall be so installed as to be accessible only to
persons qualified for operation and
maintenance... Conspicuous markings (such as
numbers/ letters/ symbols) shall be provided on
each device and at any remote operating points so
as to facilitate identification by employees
authorized to operate the device. No device
identification shall be duplicated within the
same supply station.
40National Electrical Safety Code
Whats New In 2002 Edition
Significant Changes to Section 23 - Clearances
Jerry Reding NESC Subcommittee 4 July 2001
41Summary
- Introduce Each Rule Category in Section 23
- Describe Any Significant 2002 Changes
- Brief Reason for Each Change
42Basis For Computing Clearances
43Rule 230 - General
- No Significant Changes in 2002
44Rule 231 - Structures and Other Objects
- Clearances of Supporting Structures From Other
Objects
45Rule 231A - Fire Hydrants
- Not less than 1.2 m (4 ft) ...
- Revised Rule
- Clearance changed to recommendation
- Exception aligned with previous clearance
46Rule 231B1 - From Streets, Roads,...
- Where there are curbs
- Revised Rule
- Included anchor guys
- Defined redirectional curbs
- Defined paved or swale-type curbs and placed
facilities behind such curbs
47Rule 232 - Vertical Clearances
- Vertical Clearances of Wires, Conductors, Cables,
and Equipment Above Ground, Roadway, Rail, or
Water Surfaces
48Rule 232B3 - Equipment Cases
- Clearance to Support Arms and Equipment Cases
- Revised to include Support Arms
49Rule 232B4a - Street Area Lighting
- a. The vertical clearance of street and area
lighting - Revised
- Include vertical clearances of street light
luminaries above ground.
50Table 232-1, Footnote 13
- Where this construction crosses over or runs
along alleys, not subject to truck traffic - Revised
- Clarify for use in areas not subject to truck
traffic.
51Table 232-1, Footnote 26
- When designing a line to accommodate oversized
vehicles, clearance values shall be increased by
the difference between the known height of the
oversized vehicle and 4.3 m (14 ft). - New
- Clarify treatment of large vehicles.
52Table 232-2 - Category 2a
- Add footnote 7 lessor clearances for grounded
equipment cases to Category 2a Roads, Streets,
and alleys - Revised
- Allow reduced clearances for equipment if it does
not overhang roadway.
53Rule 233 - Different Structures
- Clearances Between Wires, Conductors, and Cables
Carried on Different Supporting Structures
54Rule 234 - Other Installations
- Clearances of Wires, Conductors, Cables, and
Equipment From Buildings, Bridges, Rail Cars,
Swimming Pools, and Other Installations
55Rule 234C3a - Attached to Buildings
- Energized service drop conductors
- 1) For 0 to 750 V, Rules 230C or 230 D
- 2) For over 750V, Rule 230C1
- Revised
- Include service voltages over 750 volts.
56Rule 234C3c - Attached to Buildings
- Wires or cables attached to and run along side
the installation not less than 75 mm (3 in). - Revised
- Calls out a specific value instead of referencing
a table.
57234C3d(1) - Attached to Buildings
- EXCEPTION 1 Where the voltage between
conductors cable meets Rule 230C1 - Revised
- Include voltages and cables over 750 volts.
58Rule 234F - Grain Bins
- All portions of grain bins In addition, the
following clearances shall also apply - a. A clearance not less than 5.5 m (18 ft)
- b. horizontal clearance not less than 4.6
m (15 ft)
59Rule 234F - Grain Bins (cont)
- Revised
- Clearances based on physical distances instead of
voltage class.
60Rule 235 - Same Supporting Structure
- Clearance for Wires, Conductors, or Cables
Carried on the Same Supporting Structure
61235C2b(1) - Between Line Conductors
- c) For purposes of this determination
- Adds new rule c) which has summer loading (i),
winter loading (ii), and an exception for a
single utility with equal cables. - Revised
- Re-organized the rule for clarity under various
loading conditions. Excludes cables of same type
and single ownership.
62Rule 235H - Communication Spacing
- Clearance and Spacing Between Communication
Conductors, Cables, and Equipment - New
- Adds guidance for placing communication equipment
on structures.
63Rule 235I - Communication Antennas
- Clearances in Any Direction From Supply Line
Conductors to Communication Antennas in the
Supply Space Attached to the Same Supporting
Structure - New
- Handle communication antennas located in the
supply space, which is becoming a common practice.
64Rule 236 - Climbing Space
- Climbing Space
- No Significant Changes in 2002
65Rule 237 - Working Space
- Working Space
- No Significant Changes in 2002
66Rule 238 - Communication Supply
- Vertical Clearances Between Certain Communication
and Supply Facilities Located on the Same
Structure - No Significant Changes in 2002
67Rule 239 - Other Facilities On Structure
- Clearances of Vertical and Lateral Facilities
From Other Facilities and Surfaces on the Same
Supporting Structure
68Rule 239A6 - Guards Protection
- 6. Where guarding and protection are required by
other Rules, - New
- Clarifies such guards should completely enclose
the cable to ensure their protection.
69Table 239-1 - Footnote 5
- 5These clearances may be reduced to not more than
25 - New
- Footnote added to Row 2 of Table. Provide same
reduced clearances as conductors from guy
insulators.
70NESC 2002 Overhead Lines-Strength Loading
IEEE
Larry Slavin Telcordia Technologies, Inc. July
18, 2001
71NESC 2002Strength Loading Review
- NESC 1997
- NESC 2002 (Resolved/Final)
- Comparison
72NESC 1997Winter Storm
- Combined Ice and Wind Loading (Rule 250B)
- Heavy (0.5-in. radial ice, 40 mph wind, 0F)
- Medium (0.25-in. radial ice, 40 mph wind, 15F)
- Light (0-in. radial ice, 60 mph wind, 30F)
73(No Transcript)
74NESC 1997Summer Storm
- Extreme Wind (Structures gt60 ft Height) (Rule
250C) - 50 year recurrence (0.02 annual probability)
- Fastest-mile average speed
- Exposure C (open terrain)
- 33 ft. elevation
75Extreme Wind Map Rule 250C
76Conductor Loading
- Combined Ice and Wind, or Extreme Wind
- Vertical weight of bare conductor plus ice
- Horizontal force of wind on conductor plus ice
- Added constant to resultant (for tension, not
sag) - Corresponding temperature (0F, 15F, 30F 60F)
77Conductor Loading
ice
wind force
conductor
weight
78Loads on Line Supports
- Vertical Loads
- Dead weight of bare supports and conductors, ...
- Ice load on conductors and wires (not supports)
- Transverse Loads
- Wind force on bare structures (without ice)
- Wind force on ice-covered conductors and wires
79Loads on Line Supports
Tension
Transverse
Vertical
TOP VIEW
Tension
Angle Pull
80Loads on Line Supports
- Angles
- Unbalanced tension at corners
- Longitudinal Loads
- Unbalanced pulls
- Unequal spans
- Deadends
- ..
- Simultaneous Application of Loads
81Strength Overload FactorsSupports (Structures,
Guys, )
- Load x Overload Factor ? Strength x Strength
Reduction Factor - Overload Factor (typ.) ? 1
- Strength Reduction Factor (typ.) ? 1
- e.g., 1.0 for 50 year extreme event loadings,
or some components (conductors, ) - e.g., 1.0 for metal
82Overload Factors
- Grade of Construction
- Grade B
- Grade C
- Combined Ice-Wind vs. Extreme Wind
- Loads
- Vertical
- Transverse Loads
- Longitudinal
- Materials
- Wood
- Metal
-
83Strength (Reduction) Factors
- Grade of Construction
- Grade B
- Grade C
- ..
- Combined Ice-Wind vs. Extreme Wind
- Materials
- Wood
- Metal
- Concrete
84Conductor/Messenger Tension
- Combined Ice-Wind (60 rated strength)
- Extreme Wind (80 rated strength)
- Criteria applied with Overload Factor 1.0
- Initial unloaded tension (60F) ? 35 rated
strength - Final unloaded tension (60F) ? 24 rated
strength
85Insulators
- Combined Ice and Wind
- Cantilever (40 rated strength)
- Compression (50 rated strength)
- Tension (50 rated strength)
- Criteria applied without overload factors
- Extreme Wind
- Proper allowance should be made
86NESC 2002
Strength and Loading Requirements (Modifications)
87Status of MajorChange Proposals
- Eliminate 60 ft. exemption for Extreme Wind (CP
2151) - Rejected (WG 5.8 to study for 2007)
- Introduce New Combined Ice and Wind Map as
alternative to present Storm Loading Map, Rule
250B (CP 2309) - Rejected (map incomplete, premature, inaccurate?)
88Status of MajorChange Proposals (Contd)
- New Materials Fiber-Reinforced Composite Poles
(CP 2219, ) - Rejected (insufficient material data)
- Major Revision of Strength Loading Sections 25
- 27 (CP 2372) - Rejected (WG 5.2 to continue developing for 2007)
89Status of MajorChange Proposals (Contd)
- Uniform Treatment of Wood, Metal, Concrete
(Reinforced, Prestressed) - Consistent Overload Factors (CP 2233)
- Accepted
-
- All structures without conductors subject
- to Extreme Wind (CP 2306)
- Accepted
90Consistent Overload Factors(Wood, Metal,
Concrete)
91Status of MajorChange Proposals (Contd)
- New Extreme Wind Map (CP 2363)
- Accepted
-
- New Calculation Procedure
92New Extreme Wind Map Calculation Procedure
- ASCE 7-98 Extreme Wind Map
- 50 year recurrence (0.02 annual probability)
- Gusts (3-second average)
- Open terrain
- 33 ft. elevation
- Includes Gust Response Factors
- Height
- Span length
93New Extreme Wind Map Calculation Procedure
- Retains 60 ft. Exemption (Distribution)
941997 Extreme Wind Map Rule 250C
95New (2002) Extreme Wind Map(3 Second Gusts)
Nominal speed, 33 ft. above ground, Exposure C
96New Extreme Wind Map Calculation Procedure
- NESC-1997
- load (lbs) 0.00256 (Vmph)2 x shape factor x
projected area (ft2) - where Vmph fastest-mile (Figure 250-2, 1997)
- NESC-2002
- load (lbs) 0.00256 (Vmph)2 x shape factor x
projected area (ft2) - x kz x GRF x I
- where Vmph 3-sec. gust (New Extreme Wind
Map), - kz velocity pressure exposure coefficient,
- GRF gust response factor, and
- I importance factor (1.0)
97New Extreme Wind Map Calculation Procedure
(Contd)
- Structure kz 2.01 x (0.67h/900)(2/9.5), 60 ft
? h ? 900 ft - where h height structure (ft)
- Wire kz 2.01 x (h/900)(2/9.5), 33 ft ? h
? 900 ft - where h height attachment point (ft)
- minimum kz 0.85
98New Extreme Wind Map Calculation Procedure
(Contd)
- Structure GRF 1 2.7Es(Bs)0.5/kv2
-
- Wire GRF 1 2.7Ew(Bw)0.5/kv2
- where
- Es 0.346 x 33/(0.67h)1/7
- Ew 0.346 x 33/h1/7
- Bs 1/1 0.375h/220
- Bw 1/1 0.8L/220
- kv 1.43
- L Design Wind Span (ft)
-
99New Extreme Wind Map Calculation Procedure
(Contd)
Gust Response Factor, GRF Tabulated Values
(Structure and Wire)
100NESC
NESC 2002 vs. NESC 1997 (Comparison)
101NESC 2002 vs. NESC 1997 Comparison
- Reduced Overload Factor for Metal,
Prestressed-Concrete - Rule 250B (Combined Ice Wind)
- Transverse wind
- Grade C (not crossing)
- 1.75 vs. previous 2.20
- Affects distribution and transmission
- Extreme Wind Loading (Rule 250C)
- 3-sec. gust map calculation procedure
- Affects transmission design only (gt60 ft.)
102NESC 2002 vs. NESC 1997 Comparison (Contd)
- Distribution Lines (Combined Ice-Wind)
- Wood, Reinforced-Concrete
- no change
- Metal, Prestressed-Concrete
- reduced design load (transverse, Grade C, )
-
103NESC 2002 vs. NESC 1997 Comparison (Contd)
- Transmission Lines
- Wood, Reinforced-Concrete
- no change in Combined Ice/Wind design loads
- new Extreme Wind design loads
- Metal, Prestressed-Concrete
- reduced Combined Ice/Wind design loads
(transverse, Grade C, ) -- 0.80 factor - new Extreme Wind design loads
104Transmission LinesStructures - Combined Ice
Wind
Transverse Wind Load
105Transmission LinesStructures - Extreme Wind
Transverse Wind Load
106Transmission LinesStructures - Extreme Wind
Transverse Wind Load
107Transmission LinesConductors - Combined Ice
Wind
Transverse Wind Load
108Transmission Lines Conductors - Extreme Wind
Transverse Wind Load
109Transmission LinesConductors
- Examples
- (Transverse Wind Load)
Woo
110Transmission Lines - ExamplesStorm Loadings
Selected
111Transmission LinesConductors
- Heavy Storm District
- (Wood)
Woo
112Wood Transmission Heavy Storm Area, Grade B,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
113Wood Transmission Heavy Storm Area, Grade B,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
114Wood Transmission Heavy Storm Area, Grade B, 50
x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
115Wood Transmission Heavy Storm Area, Grade C,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
116Wood Transmission Heavy Storm Area, Grade C,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
117Wood Transmission Heavy Storm Area, Grade C, 50
x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
118Transmission LinesConductors
- Heavy Storm District
- (Steel)
Woo
119Steel Transmission Heavy Storm Area, Grade B,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
120Steel Transmission Heavy Storm Area, Grade B,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
121Steel Transmission Heavy Storm Area, Grade B,
50 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
122Steel Transmission Heavy Storm Area, Grade C,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
123Steel Transmission Heavy Storm Area, Grade C,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
124Steel Transmission Heavy Storm Area, Grade C,
50 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
125Transmission LinesConductors
- Medium Storm District
- (Wood)
Woo
126Wood Transmission Medium Storm Area, Grade B,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
127Wood Transmission Medium Storm Area, Grade B,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
128Wood Transmission Medium Storm Area, Grade C,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
129Wood Transmission Medium Storm Area, Grade C,
100x2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
130Transmission LinesConductors
- Medium Storm District
- (Steel)
Woo
131Steel Transmission Medium Storm Area, Grade B,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
132Steel Transmission Medium Storm Area, Grade B,
100x2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
133Steel Transmission Medium Storm Area, Grade C,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
134Steel Transmission Medium Storm Area, Grade C,
100x2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
135Transmission LinesConductors
- Light Storm District
- (Wood)
Woo
136Wood Transmission Light Storm Area, Grade B,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
137Wood Transmission Light Storm Area, Grade B,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
138Wood Transmission Light Storm Area, Grade C,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
139Wood Transmission Light Storm Area, Grade C,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
140Transmission LinesConductors
- Light Storm District
- (Steel)
Woo
141Steel Transmission Light Storm Area, Grade B,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
142Steel Transmission Light Storm Area, Grade B,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
143Steel Transmission Light Storm Area, Grade C,
250 x 500
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
144Steel Transmission Light Storm Area, Grade C,
100 x 2000
250B (ice wind) -1997
250B (ice wind) -2002
250C (extreme wind) -1997
250C (extreme wind) -2002
145NESC
NESC 2002 vs. NESC 1997 (Conclusions)
146NESC 2002 vs. NESC 1997 Conclusions
- Distribution Design Loads
- Wood ? Same
- Reinforced-concrete ? Same
- Metal (Grade C) ? Reduced in Grade C
- Prestressed-concrete (Grade C) ?Reduced
in Grade C
147NESC 2002 vs. NESC 1997 Conclusions
- Transmission design loads depend upon combination
of parameters - - geographic area
- - grade of construction
- - material
- - conductor diameter
- - attachment height
- - span length
148NESC
NESC 2007 (?) Integrated Re-Write of Strength
Loading
149Integrated Re-Write of Strength Loading
- Based upon CP 2372 (Rejected for NESC-2002)
- Sags and Clearances also impacted
- Modified version proposed for NESC-2007 Edition
- To be available on NESC website (when?)
- Response form provided for reporting results of
application to actual cases!
150Integrated Re-Write of Strength Loading
- New Extreme Wind Map and wind pressure
calculation procedure - (Rule 250C, NESC-2002)
- Upgraded ASCE 7-98 Combined Ice and Wind Map
- Replaces Fig.250-1 Loading Districts
- Construction and Maintenance Loads
151Integrated Re-Write of Strength Loading
- All loads apply to all structures independent of
height, but ... - Possible wind reduction if urban/suburban and ?
60 ft. (Ref Working Group 5.8) - Ice thickness reduction for Grade C
- Velocity pressure exposure coefficient kz and
gust response factor GRF (functions of height and
span length) applied to wind pressure for both
storm loads
152Integrated Re-Write of Strength Loading
- Consistent Overload and Strength Factors
- Alternative (Option) to Present (NESC-2002)
Method ?
153Integrated Re-write of Strength Loading (Contd)
- Results from actual applications (as reported on
response forms) will be considered in developing
final proposal for 2007 Edition
154WHATS NEW IN 2002?
NESC SUBCOMMITTEE 7
- NESC Significant Changes
- Underground Lines
O. Chuck Amrhyn NESC Chairman July 19, 2001
155(No Transcript)
156RANDOM SEPARATION
157RANDOM SEPARATION
158RARANDOM SEPARATION
159RANDOM SEPARATION
160IDENTIFICATION MARKING BURIED CABLE
161New NESC Rule 323C5
- 5. Any manhole greater than 1.25 m (4 ft) in
depth shall be designed so it can be entered by
means of a ladder or other suitable climbing
device. Equipment, cables and hangers are not
suitable climbing devices. - Reason This rule was added because it was not
adequately covered in the code.
162New NESC Rule 350H
- H. The rules in this section also apply to direct
buried supply and communications cables installed
in duct that is not part of a conduit system. - (the section referenced above is section 35,
rules for direct buried cables) - Also a NOTE will be added at the beginning of
section 32 - (Underground Conduit Systems) thusly
-
163New NESC Rule 350H (cont.)
- For cables installed in a single duct not part
of a conduit system, the rules in section 35
apply. - Reason This rule was added to clarify the
intent of the code that the direct buried
cable rules in Section 35 apply to direct
buried cable in duct that is not part of
conduit system.
164Revised NESC Rule 351A1
- 351A1 Cables should be located so as to be
subject to the least disturbance practical. When
cables are Cables to be installed parallel to
other subsurface structures, but if this is not
practical, the rules on separation in Rule 352
353 or 354 shall should be followed.
165Revised NESC Rule 351A1 (cont.)
Reason This rule was revised to allow joint
use trench without qualifications as to the
practicality of it. Joint trench has become
an accepted normal practice, and if the
appropriate rules are followed, it is a safe
practice.
166Revised NESC Rule 352 and 354
- Presently the separation rules require a 12
separation between supply cables and other
underground structures, including gas and other
fuel lines. If this is not practical, or
conditions do not permit it, then a separation of
less than 12 (random lay) is OK, provided all
parties affected are in agreement and the random
lay rules are followed.
167Revised NESC Rule 352 and 354(cont.)
- The revised rules on separation will be two
distinct rules - (1) Revised Rule 353 for deliberate
separation (Equal to or Greater Than 12),
And - (2) Revised Rule 354 for random separation (Less
Than 12). -
168The most significant change is new NESC Rule
354A2 which states
- 354A2. Radical separation of supply and
communication cables or conductors from steam
lines, gas and other fuel lines shall be not
less than 12 inches and shall meet Rule 353. - The present rules do not allow a supply cable and
gas line to have a separation of less than 12
provided all the affected parties agree, but the
new Rule 354A2, as stated above, will not allow a
radical separation less than 12, even if the
parties agree to it, or if they are owned by the
same utility. The 2002 edition will have no
exceptions.
169Reason This rule was added because of the
concerns between supply and communica-tion
cables and gas lines as to adequate separation.
New Rule 354A2 (cont.)
170Revised NESC Rule 353D1, Table 353-1, Exception
- Exception Where conflicts with other underground
facilities exist, street light cables operating
at not more than 150 volts to ground may be
buried at a depth not less than 450 mm (18 in). - Reason This rule was revised because the
original intent was to allow a lessor depth only
where other underground structures existed. The
burial depth should correlate with voltage, not
the type of system being installed.
171New NESC Rule 380D
- D. Padmounted equipment, pedestals and
otherabove ground enclosures should be
located not less than1.2 m (4 ft) from
firehydrants. - ExceptionWhere conditions do not permit a
clearance of 1.2 m (4ft), a clearance of not less
than 900 mm (3 ft) is allowed. - Reason This rule was added because padmounted
equipment creates the same problems for firemen,
as do overhead structures. It will also now be
consistent with the overhead clearance section.
172Revised NESC Rule 381G1
- 381G1. Padmounted and other above ground
equipment shall have an enclosure that is either
locked or otherwise secured against unauthorized
entry. - Reason This rule was revised so that
non-padmounted equipment, such as secondary
pedestals are included.
173NESC Subcommittee 8
PART 4 RULES FOR THE OPERATION OF ELECTRIC SUPPLY
AND COMMUNICATION LINES AND EQUIPMENT
Jim Tomaseski International Brotherhood of
Electrical Workers July 18, 2001
174NESC Subcommittee 8Work Rules
- PURPOSE IS TO PROVIDE
- PRACTICAL WORK RULES
175NESC Subcommittee 8Work Rules
- HARMONIZED WITH
- OSHA FINAL RULES
- 1910.137 1910.269
176NESC Subcommittee 8Work Rules
- RULE 410A2 - TRAINING
- DEMONSTRATED PROFICIENCY
- NESC AND OTHER RULES
177NESC Subcommittee 8Work Rules
- RULE 411D
- SIGNS AND TAGS
- WARNING SIGNS ? EMPLOYEE SAFETY
178NESC Subcommittee 8Work Rules
- RULE 423C4
- AIR SPACE OR BARRIER
- WITH TORCH OR FLAME NEAR
- EXPOSED GAS OR FUEL LINE
179NESC Subcommittee 8Work Rules
- RULE 423D5
- SHORING PROVISIONS
180NESC Subcommittee 8Work Rules
- RULES 431A1 431A2
- JOINT USE
- COMMUNICATIONS SUPPLY
- ENERGIZED UNTIL DE-ENERGIZED
- AND GROUNDED
181NESC Subcommittee 8Work Rules
- RULE 431B
- ALTITUDE CORRECTION FACTORS
- MINIMUM APPROACH DISTANCES CORRECTED FOR
COMMUNICATION WORKERS
182NESC Subcommittee 8Work Rules
- TABLE 431
- APPROACH DISTANCE
- ?
- DISTANCE TO EMPLOYER
- (MATCH 441 TABLES)
183NESC Subcommittee 8Work Rules
- RULE 441A
- DEFINITION OF
- DE-ENERGIZED
184NESC Subcommittee 8Work Rules
- RULE 441A
- TWO TERMS
- DE-ENERGIZED
- DE-ENERGIZED AND GROUNDED
185NESC Subcommittee 8Work Rules
- RULE 441A3b c
- AND
- TABLE 441-6
- MAXIMUM USE VOLTAGE
186NESC Subcommittee 8Work Rules
- RULE 441A4a
- TRANSIENT OVERVOLTAGE CONTROL
- VOLTAGES ABOVE 72.5kV
187NESC Subcommittee 8Work Rules
- RULE 441A5a b
- ALTITUDE CORRECTION CALCULATION
- CLARIFICATION ONLY
188NESC Subcommittee 8Work Rules
- RULE 441B4a, b c
- SPECIAL RULES FOR WORKING ON INSULATOR ASSEMBLIES
OVER 72.5kV - 3 INSULATORS SHORTED
189NESC Subcommittee 8Work Rules
- NEW RULE 447
- MOVED FROM RULE 276
- MORE APPROPRIATE IN PART 4