EZ Positioning with SINAMICS S120 Agenda - PowerPoint PPT Presentation

About This Presentation
Title:

EZ Positioning with SINAMICS S120 Agenda

Description:

... Open New Sinamics S7 Project And Open Hardware Configuration To Confirm Configuration of Telegram Highlight the Profibus Card and View the Telegram ... – PowerPoint PPT presentation

Number of Views:140
Avg rating:3.0/5.0
Slides: 67
Provided by: KlausSc1
Category:

less

Transcript and Presenter's Notes

Title: EZ Positioning with SINAMICS S120 Agenda


1
EZ Positioning with SINAMICS S120Agenda
2
Sinamics EZ EPOS Agenda
  • Starter Basic Sinamics Drive Setup
  • Insert Drive (CU310 or CU320)
  • Auto Configure CU and Drive-CLIQ Devices
  • Starter Offline Configuration
  • Drive Configuration Wizard
  • Telegram Setup for EZ _Speed Block
  • Check S7 Hardware Configuration
  • Execute EZ_Speed Script File
  • Copy from Example Project
  • Execute and Save Project
  • Download to Sinamics
  • Step7 Simatic Manager Programming
  • Copy Needed blocks to new Program
  • Setup FB120 in new Program
  • Edit Symbol Table
  • Save and Download S7 Project

3
EZ Speed with SINAMICS S120S7 Hardware
Configuration
4
Start New Project with S7 Simatic Manager
  • Open S7 and Select File / New
  • Select new Name for Project and Press OK

5
Insert S7 300 Simatic Station
  • Right Click on New Project and insert new Object
  • Choose Simatic 300 Station
  • New Station inserted --Note Hardware Icon

6
Start Hardware Configuration
Click on Hardware Icon and Open HW Configuration
  • Open Hardware Catalogue
  • Insert S7 300 Rack, Power Supply, and CPU

7
Add Sinamics S120 in Hardware Configuration
  • Drag the drive on to the Profibus Network
  • Choose Node Address 4
  • Select Present Firmware Version (2.5)
  • Choose Telegram Type None

8
Save and Close Hardware Configuration
  • Press Save an Compile Button
  • Hardware Configuration should Save and Compile
  • Correct any errors if they occur
  • Exit the Hardware Configuration
  • HW Config must not be Open for Next Section!

9
EZ Speed with SINAMICS S120Basic Starter Online
Commissioning
10
Open Starter Program Go Online
  • Open Starter by Motor Icon for Sinamics
  • Go Online with Starter Use
  • Do not Upload to the PG!

11
Default CU310 or CU320
  • Right Click On CU310 (or CU320) and Choose
  • Target Device / Restore Factory Settings
  • Check the Box Save Factory Settings to ROM
  • Power Cycle Drive after RAM to ROM Completed

12
Complete Auto Configuration
  • Select Auto Configuration and Start Auto
    Configuration
  • Choose Control type for Motor type
  • Close after Initialization

13
Starter Offline Configuration
Go Offline with the Sinamics
  • Select Configuration under the Device Folders
  • This Configuration is under the Drive Object Used
  • Click On Configure DDS to Parameterize Drive
    Settings

14
EZ Speed with SINAMICS S120Basic Starter
Offline Commissioning
15
Open Starter Program Go Offline
  • Open Starter by Motor Icon for Sinamics

Go Offline with Starter Use
16
Open DDS (Drive Data Set)
  • From the Drive to be Commissioned Choose
  • Configuration
  • Choose Configure DDS
  • Offline Configuration Wizard is Opened

17
Control Structure Setup Vector
  • Select Speed Control with Encoder
  • Use Function Modules when Needed
  • For the Servo Extended Setpoint Channel is
    needed
  • Next, Select Continue

18
Control Structure Setup - Servo
  • Select Speed Control with Encoder
  • Use Function Modules when Needed
  • For the Servo Extended Setpoint Channel is
    needed
  • Next, Select Continue

19
Power Unit Configuration
  • Power Unit Data Up-read in Auto Configuration
    (Drive-CLIQ)
  • Confirm Device type is Correct via Part label
  • Select Continue for next Configuration Screen

20
Motor Configuration
  • Motor Data Up-read in Auto Configuration
    (Drive-CLIQ)
  • If Motor is a Drive-CLIQ Motor
  • Non Drive-CLIQ Motors can be Selected from List
  • Third Party Motors can have data entered

21
Motor Configuration
  • For Third Party Motors Select Complete Motor ID
  • Motor ID will be Completed on First Start Command
  • Motor may rotate back and forth slightly on Demo
  • Insure motor is braked for actual application if
    needed

22
Holding Brake Configuration
  • Motor Data Up-read in Auto Configuration
    (Drive-CLIQ)
  • If Motor is a Drive-CLIQ Motor
  • Non Drive-CLIQ Motors Check Motor Name Plate
  • DEMO drives do not Use Holding Brakes

23
Encoder Configuration
  • Choose Encoder Data for Non Drive CLIQ Encoder
  • Siemens and Third Party Encoders can be
    Parameterized
  • Choose 1024 HTL for the DEMO Induction Motor
  • Note Encoder 1 is from Motor Encoder

24
Technology Type
  • Choose Standard Technological Application
  • Other Option is for Fans Pumps
  • Note the Motor ID Parameter is set

25
Profibus Telegram type
  • Choose Free Telegram with BICO
  • The Profibus Telegram will be Configured Later
  • Free Telegram allows Custom Telegrams
  • Script Files will be used to Setup Telegram
    Mapping

26
Summary Data Acceptance
  • Review data and Click Finish if Complete
  • After Completing DDS Wizard Save and Compile
  • DDS Wizard Data is now Complete

27
Profibus Telegram Configuration
  • From the Drive to be Commissioned Choose
  • Configuration
  • Use Up Down Buttons to Move Drive Objects
  • CU is 1st and Drive (S) should be in Preceding
    Order
  • S7 Hardware Configuration Should be Closed!

28
Profibus Telegram Configuration
  • Select Word Length For Telegrams
  • CU Telegram not needed for Demo
  • Word Length For Telegrams
  • EZ_EPOS uses 10 words IN and 10 Words Out
  • EZ_APC_SPEED uses 10 Words IN and 10 Words
    Out
  • EZ_Basic_SPEED uses 6 Words IN and 6 Words
    Out

29
Profibus Telegram Configuration
  • Select Transfer to HW Config
  • CU Telegram will be sent to the S7 Hardware
    Config.
  • Select Yes to transfer

30
Profibus Telegram Configuration
  • Telegram has Successfully been Transferred
  • Note Blue Check Boxes
  • Save and Compile Program before Proceeding
  • Save and Compile Using Starter

31
EZ Speed with SINAMICS S120Starter Script File
32
Open Starter Program in Example S7 Given
  • Copy Script file from Example Program
  • Close Example Programs Starter and go to new
    Program

33
Create Script Folder in New Program
  • Right Click On Drive to be Commissioned
  • Expert / Insert Script Folder

Paste Script in New Script Folder
34
Open Script in New Project
  • Click On the Speed Script
  • The Script Editor Opens
  • Click inside the Script Editor area
  • The Script Editor Buttons appear on the Task Bar

35
Accept and Execute the Script
  • Click On the Accept and Execute Button
  • The script File parameterizes the drive for
    Speed Block
  • All the Drive Parameters needed by FB110 are
    Complete
  • Save and Compile the Starter Program
  • The Program is now Ready for Download

36
Download to the Drive
  • Go Online with Starter to the Drive
  • Choose Download to the Drive
  • Choose RAM to ROM
  • Drive is now ready for Operation

37
EZ Speed with SINAMICS S120S7 Simatic Manager
Programming
38
Open S7 Program S7 Hardware
  • Open New Sinamics S7 Project
  • And Open Hardware Configuration
  • To Confirm Configuration of Telegram

39
Verify Telegram Configuration
  • Highlight the Profibus Card and View the Telegram
  • Telegram will be User Defined
  • Length should be 6 words (12 bytes)

40
Download Configuration to PLC
  • Save and Compile HW Configuration
  • Download Configuration to PLC

41
Download Configuration to PLC
  • Follow S7 Sequence to Download Hardware Config
  • Select Target Module (If Multiple PLCs)
  • Restart PLC after Download
  • PLCs LED will still show Fault

42
Copy Blocks to New S7 Program
  • Open the Example Program and Copy Relevant Blocks
  • Task Bar Use Window / Arrange Horizontally

43
Copy Blocks to New S7 Program
  • Open the Example Program and Copy Relevant Blocks
  • See Example Below for Copying Blocks
  • Paste Blocks in new S7 Program
  • VAR (Variable Table) can be copied
  • VAR may need editing if Instance DB Changes
  • Instance DB will be Created in Later Step
  • Copy Relevant Profibus Communication Blocks
  • OB82, OB86, and OB122
  • SFC14 and SFC15 are PLC System Function Blocks

44
Insert FC (Function Call) for Drive(s)
  • Right Click on S7 Blocks Folder and Insert a FC
  • Edit Symbolic Name and Comments

45
Open New FC and Insert Drive FB
  • Open FC and Choose Drive FB from Catalogue
  • Note Catalogue Icon Highlighted on Task Bar
  • Insert a network and Drag FB115 on to Network

46
Insert Instance DB in Drive FB
  • DB number is Entered to Generate Instance DB
  • Enter DB115 in ???? to test with Variable
    table included
  • Multiple FB115s with Specific DBs can be used

47
Parameterize Function Block
  • Nominal RPM and Hex address from Drive
  • Use Nominal Current, Volts, Torque, and RPM for
    Demo
  • Address is same as in Hardware Config-Profibus
    for Drive
  • Address is Hex value and not decimal value
  • Save FC

48
Insert FC In OB1
  • Open OB1 Block
  • Save Program in OB1 After Inserting FC

49
Edit Symbol Table
  • Open Symbol Table and Edit Instance DB
  • Name for DB can be symbolic to Axis
  • Save Symbol Table

50
Download S7 Project to PLC
  • Open the Blocks Folder and Download the Blocks
  • Use the Download Button on the S7 Manager task
    bar
  • System data has been loaded in the Hardware
    Config
  • SFC14 and SFC15 are included with S7 PLC

51
EZ Speed with SINAMICS S120Testing Application
52
Verify Control Word One
  • Use VAR table in S7 Manager with Starter
    Diagnostics
  • Open the VAR Table Online
  • Open Starter Online
  • Set Bits 0.1 0.3 to Logical 1
  • Set Bit 0.4 to Clear Drive Fault If Needed
  • VAR Table included is addressed to DB110 if your
    test is for different DB you will need to edit
    VAR table

53
Verify Control Word One
  • Open Control Logic in Starter and Observe Bit
    0-3
  • Set Off2, OFF3, and Enable to 1
  • Toggle Bit O ON / OFF with VAR Table
  • OFF2 is Coast to Stop
  • OFF3 is Quick Ramp Down Stop
  • Enable is Pulse Enable to Drive

54
Notes on Control Word One
  • Sequence order for Bits during Operation
  • Bit 10 is High for PLC Control
  • Off2, OFF3, and Enable are set to 1
  • OFF1 (Bit 0) Transitions to 1 and remains high
  • Control Word 1 is needed for Operation

55
Run Drive from VAR Table
  • With Bit 0.1 0.3 ON
  • Set Bits 0.0 to True
  • Trigger Setpoint in DBW 2
  • Axis Should move to setpoint in DBW2
  • Note that Setpoint is Scaled 4000H to 100 speed

56
Jogging Setpoints
  • Click on Speed Setpoint Folder under Drive
  • Use New Setpoints for Jog1 and Jog2

57
Jogging Axis
  • Use Jog bits 0.5 and 0.6 to Jog Axis
  • Bit 0 must be OFF
  • Bit 0.1 Bit 0.3 Must be ON for Jogging

58
Reverse Setpoint Inhibit Direction
  • Use Bit 56.3 to Reverse Setpoint
  • Bit 61.4 can be used for Inhibit Negative
    Direction
  • Bit 61.5 can be used for Inhibit Positive
    Direction
  • Bits 61.0 61.5 Can be Fixed Setpoint Select

59
Starter Setpoint Path
  • Use the Graphics under the Setpoint Folder
  • Additional Setpoint and Scaling
  • Radio Buttons in Starter for Easy Check Out
  • Go to Next GUI Page lt1gt

lt1gt
60
Starter Setpoint Path
  • Using the Graphics in the Setpoint Folder
  • Minimum and Maximum Speeds
  • Speed Suppression
  • Go to Next GUI Page lt2gt

lt2gt
61
Starter Setpoint Path
  • Using the Graphics in the Setpoint Folder
  • Ramp Function Generator and Control
  • RFG Time Value can be set in RFG Graphic
  • Go to Next few GUI Pages lt3gt to Torque Setpoints

lt3gt
62
Starter Setpoint Path Vector Torque Control
  • Use the Graphics under the Setpoint Folder
  • Torque Control can be used via the PLC
  • Find the Signal and Torque Control Bit in the VAR

63
Starter Setpoint Path- Servo Torque Control
  • Use the Graphics under the Setpoint Folder
  • Torque Control can be used via the PLC
  • Find the Signal and Torque Control Bit in the VAR

64
Torque Control
  • Use the VAR Table to Run in Torque Control
  • Control Word 1 must be On
  • Use Bit 4.0 for Toque Control
  • Use DBW 64 for Torque Setpoint

65
FB 110 Diagnostics
  • These Status Bits and Words can be used in PLC
    Logic

66
FB 110 Block View
Thank You!
Write a Comment
User Comments (0)
About PowerShow.com