Branch Circuits Chapter 2 - PowerPoint PPT Presentation

1 / 68
About This Presentation
Title:

Branch Circuits Chapter 2

Description:

Branch Circuits Chapter 2 * * * * * * * * * * * * * * * Conductor size #3--cont. For this circuit with a 8.75 amp load, the circular mills of the conductors can be ... – PowerPoint PPT presentation

Number of Views:285
Avg rating:3.0/5.0
Slides: 69
Provided by: biosystem9
Category:

less

Transcript and Presenter's Notes

Title: Branch Circuits Chapter 2


1
Branch CircuitsChapter 2
2
Introduction
  • The purpose of branch circuits is to carry the
    current from the service entrance panel (SEP) to
    the electrical devices.
  • Three common types of current are used in
    agricultural buildings
  • 120 volt (108 125)
  • 240 volt (220 250)
  • Three phase

Why are a range of voltages listed?
What happens when the voltage drops below 108 V?
What happens when the voltage goes above 124 V?
3
Service Entrance Panel (SEP)
  • The service entrance panel (load center) is the
    entry point for the electricity into the
    building.
  • The size (amp capacity) of the load center is
    determined by the number of circuits and total
    amp load for the building.
  • Current NEC regulations require that the load
    center have a master disconnect.
  • The entrance panel must be grounded with a NEC
    approved earth connection.

What is an NEC earth connection?
4
Service Entrance Panel SEP Load Center
  • Master Disconnect

120/240 V Service
Service Entrance Neutral
Service Hot Conductors
Metal Box
Breaker
Non-conducting base
Grounding Bar
Non-conducting Attachment bars
Circuit Neutral Ground Connections
Conducting Attachment bars
Ground
Bonding Screw
Neutral
240 V Circuit
120 V
120 V
120 V Branch Circuit Hot (black) Conductor
Earth Ground
120 V Branch Circuit Ground (bare) Conductor
120 V Branch Circuit Neutral (white) Conductor
5
SEP--cont.
  • The 120/240 service is attached to the master
    disconnect (breaker).
  • From master breaker each hot conductor is
    connected to one of the conducting breaker bars.
  • The 120/240 neutral conductor is attached to the
    grounding bar.
  • A 120 volt breaker attaches by snapping onto one
    conducting and one non-conducting bar in the load
    center.
  • For a 240 volt circuit two individual breakers
    may be used and the levers are pined together or
    a combination breaker may be used.

6
Grounding
  • Branch circuits have two different types of
    grounds.
  • System
  • Equipment

System grounding is accomplished by one of the
two current carrying conductors (white).
What is another term for the system ground?
What is the insulation color of the system ground?
What is the insulation color of the equipment
ground?
7
Grounding - Equipment
  • Equipment grounding is the bonding of all non
    current carrying metal components back to the
    SEP.
  • The equipment ground is designed to provide a low
    resistant circuit to the earth in the event of a
    short from the energized conductor to any
    metallic component.
  • Must make a complete, low resistance circuit from
    all metallic electrical devices in the system to
    the earth.

Equipment ground
What hazard is created if the equipment ground is
interrupted?
8
120 V Circuits
  • 120 V circuits have 3 or 4 conductors
  • one energized (hot) conductor Black or red
  • one neutral conductor White
  • one ground conductor. Bare or green

What does PVC stand for?
What other common building component is made from
PVC
9
240 V Circuits
  • 240 Volt circuits have three conductors
  • Two hot
  • Equipment ground
  • Neutral circuit is not required unless both 240
    and 120 circuits are supplied by the device.
  • The 240 Volt electrical service to the SEP will
    have a neutral so both 240 and 120 Volt branch
    circuits can be used.

10
Three Circuit Types
  • General purpose branch circuits
  • Individual branch circuits
  • Motor

11
General Purpose Branch Circuits
  • Designed for temporary loads such as lights and
    DCOs (Duplex Convenience Outlets) under 1500 W.
  • Minimum 12 AWG
  • Fused at 20 amps
  • No more than ten (10) DCOs or light fixtures per
    circuit. (Fig. 2-3, pg 21)
  • Recommended location for DCOs (Table 1-12, pg 18).

12
Special Purpose Branch circuits
  • Used for known specific loads
  • Stationary motors
  • Stationary appliances
  • SPOs (Special Purpose Outlets)
  • Usually used for loads greater than 20 amps240
    V.

What would be an example of an SPO in an
agriculture building?
13
Motor Circuits
  • Use 240 V whenever possible.
  • Reduces amperage load on circuit
  • Reduces stray voltage potential
  • Five (5) horsepower and larger should be 3 phase.

14
Motor Circuitscont.
  • Branch circuits for electric motors have four (4)
    requirements (Fig 2-6 through 9, pg 23-26)
  • Branch circuit, short circuit protection
  • A disconnecting means
  • A controller
  • Overload protection
  • Summary Table 2-1, pg 26

15
Motor CircuitsShort Circuit Protection
  • Fuse or circuit breaker
  • For motor circuits they must have greater
    capacity than full load current.
  • Motor starting load is higher than the running
    loadSCP devices must be able to handle temporary
    overload.
  • Inverse time breaker
  • Time delay fuses
  • Maximum size
  • Inverse time breaker 2.50 times full load
    current
  • Time delay fuses 1.75 times full load current.

16
Motor CircuitsShort Circuit Protection--example
  • Determine the required SCP for a 120 V circuit
    for a ½ horsepower, single phase motor.
  • Determine the required SCP for a 240 V circuit
    for a 1/6 horsepower, single phase motor.
  • Smallest breaker is 10 A
  • SolutionUse 10 A breaker in the SEP and install
    a 4 to 6 amp fuse inline with the motor.

17
Motor CircuitsDisconnecting Means
  • Each motor or motor circuit must have an
    individual disconnecting means.
  • The disconnecting means must disconnect all hot
    wires.
  • The DM must clearly indicate whether it is on or
    off.

18
Motor CircuitsDisconnecting Means-cont.
  • Must be located within sight and within 50 feet
    of the controller and the motor.
  • Disconnecting Means
  • Stationary motors can use the circuit switch as
    long as correct size.
  • Portable motors the plug and receptacle is
    acceptable.
  • The circuit switch can be a snap switch as long
    as the motor is 2 hp or less and its capacity is
    equal to or 1.25 times greater than the motor
    full load rating.

What is a snap switch?
19
Motor CircuitsController
  • A controller is a device used to automatically
    start and stop a motor.
  • Only required to open enough conductors to stop
    the motor.
  • One wire for 120 240 V single phase.
  • Must be located within sight and 50 feet of the
    motor.
  • Thermostats, variable speed controllers and
    timers are considered to be a controller.

Is a heater/airconditioner thermostat within
sight and 50 feet of the furnace/airconditioner?
If not, does this meet code?
20
Motor CircuitsControllercont.
  • Current rating must be greater than or equal to
    motor full load rating, or a magnetic starter
    must be used.
  • For 1/3 hp and less portable motors the plug and
    receptacle can function as the controller.
  • If motor is 2 hp or less, a snap switch an serve
    as the controller.
  • If a knife switch is operated by hand, it can
    serve as both the disconnecting means and the
    controller.

What is a magnetic starter?
21
Motor CircuitsControllerMagnet Starter
22
Motor CircuitsOverload protection
  • Motors and conductors must be protected from
    overloads.
  • Because motors draw more current for starting
    that running, the overload protection device must
    allow temporary overload on the circuit but not
    allow the overload to last long enough to damage
    the motor.

When magnetic starters are used the overload
protection is usually included in the starter.
Common practice to use a heater device to trip
the controller before the conductors or motor
overheats. One hp and larger motors have
specific requirements based on the design and
size of the motor.
23
Motor CircuitsOverload protectioncont.
  • For motors less than 1 hp, and manually started,
    the circuit breaker or fuse can serve as the OPD.
  • Smaller motors may include a built in overload
    protection switch.

24
Motor CircuitsOverload protectioncont.
  • Critical issue is if a manual restart or
    automatic restart is used.
  • Manual restart is usually used unless the motor
    operates a critical function such as a
    ventilation fan in a chicken house.

Why?
25
Branch Circuit Conductors
26
Sizing Conductors
  • Conductors are usually considered single
    wires.
  • Cables are multiple conductors in the same
    sheathing.
  • Conductor are sized using two systems
  • American Wire Gauge (AWG)
  • circular mills (cmil).

27
Sizing Conductorscont.
  • AWG
  • Numbers run from 40 to 0000
  • AWG numbers only apply to non-ferrous metals.
  • The larger the number--the smaller the diameter
    of the wire.
  • cmils
  • Circular-mils (cmils) is a unit used to describe
    the cross-sectional area of wire.
  • A mil 0.001 inch
  • AWG sizes greater than 0000 are sized in
    thousands of circular mils (kcmil)
  • AWG 8 and higher are usually multiple strands.
  • The diameter of multiple strand wire in cmils is
    the cmils of each strand times the number of
    strands.

28
Sizing Conductorscont.
  • The minimum size of an individual conductor is
    determined by two factors.
  • Ampacity
  • Voltage drop

What is ampacity?
What is voltage drop?
29
Ampacity--Resistivity
  • All materials will conduct electricity.
  • Good conducting materials have low resistance.
  • The resistance of a conductor depends on the
    physical properties of the material (?), the
    length (ft) of the conductor and the
    cross-sectional area of the conductor (cmils).
  • Expressed in an equation

A cross-sectional area in cmils (diameter in
mils)2 1mil 0.001 in
30
Example--Resistance
  • What is the resistivity of a 1/2 inch steel rod
    that is 12 feet long?
  • Steel 100 ohm-cmil/foot

Electricity for Agricultural Applications, Bern
31
Voltage Drop
  • When electricity passes through a resistance heat
    is generated.
  • Heat is energy
  • The loss energy shows up as voltage drop.
  • All conductors have resistance all conductors
    have voltage drop.
  • What must be avoided is excessive voltage drop.

What will cause excessive voltage drop?
What are some possible outcomes of a circuit with
excessive voltage drop?
32
Voltage Drop--Cont.
  • When there is no current flow, there is no
    voltage at the load.
  • A 2 voltage drop is considered normal.
  • If the voltage drop is more than 2 the circuit
    will overheat.

32
33

Three Ways of Wiring Circuits
  • The loads and electrical components in a circuit
    can be connected in three different ways
  • Series
  • Parallel
  • Series-parallel (not included)

33
34
Series Circuit
  • In a series circuit the electricity has no
    alternative paths, all of the electricity must
    pass through all of the components.
  • The total circuit resistance is the sum of the
    individual resistances.

For these calculations assume no resistance in
the conductors or connections.
Determine the total resistance for the circuit in
the illustration.
34
35
Series Circuit-cont.
To the power source, a series circuit appears as
one resistance.
  • In all circuits a voltage drop occurs as
    electricity passes through each resistance in the
    circuit.
  • The method for calculating voltage drop in series
    circuits is different than the method for
    parallel circuits.

35
36
Parallel Circuits
  • In parallel circuits the electricity has
    alternative paths.
  • The amount of current in each path is determined
    by the resistance of that path. Electricity
    follows the path of least resistance
  • Because there are alternative paths, the total
    resistance of the circuit is not the sum of the
    individual resistances.
  • In a parallel circuit The inverse of the total
    resistance is equal to sum of the inverse of each
    individual resistance.

36
37
Parallel Circuits--cont.
An alternative equation is
When a circuit has more than two resistors,
select any two and reduce them to their
equivalent resistance and then combine that
resistance with another one in the circuit until
all of the resistors have been combined.
37
38
Parallel Circuit Resistance
Determine the total resistance for the circuit in
the illustration.
or
or
38
39
Circuits Summary
  • When the source voltage, and the total resistance
    of the circuit is known, amperages and voltages
    can be determine for any part of a circuit.
  • In a series circuit the amperage is the same at
    all points in the circuit, but the voltage
    changes with the resistance.
  • In a parallel circuit the amperage changes with
    the resistance, but the voltage is the same
    throughout the circuit.

39
40
Calculating Voltage In A Series Circuit
  • What would V1 read in the illustration?
  • Ohms Law states
  • Therefore
  • At this point there is insufficient data because
    I (amp) is unknown.
  • Using Ohms Law to solve for the current in the
    circuit
  • Knowing the amount of current we can calculate
    the voltage drop.

Note circuit conductors behave like resistors in
series.
40
41
Determining Voltage In A Parallel Circuit
Assuming no resistance in the conductors, the two
volt meters in the illustration will have the
same value--source voltage.
41
42
Determining Amperage In A Series Circuit
  • Determine the readings for A1 and A2 in the
    illustration.
  • In a series circuit the electricity has no
    alternative paths, therefore the amperage is the
    same at every point in the circuit.
  • The current in the circuit is determined by
    dividing the voltage by the circuit resistance.

42
43
Determining Amperage in a Parallel Circuit
  • Determine the readings for amp meters A1 and A2
    in the circuit.
  • In a parallel circuit the amperage varies with
    the resistance.
  • In the illustration, A1 will measure the total
    circuit amperage, but A2 will only measure the
    amperage flowing through the 6.3 Ohm resistor.
  • To determine circuit amperage the total
    resistance of the circuit must be calculated

43
44
Determining Amperage in a Parallel Circuit--cont.
When the total resistance is known, the circuit
current (Amps) can be calculated.
Total current is
A1 12.76 A
When the circuit current (Amps) is known, the
current for each branch circuit can be calculated.
Branch current is
A2 1.9 A
44
45
Conductor Size
  • The conductor size is determined by seven (7)
    factors.
  • the load on the circuit
  • the voltage of the circuit
  • the distance from the load to the source
  • the circuit power factor
  • the type of current (phases)
  • the ampacity of the conductor
  • the allowable voltage drop

The type of insulation is determined by the
environment.
46
Insulation
  • The common types used in Agriculture.

90o C 194o F
Electricity for Agricultural Applications, Bern
47
Environment--cont.
  • The selection of insulation is very important
    because the life of the conductor is usually
    determined by the life of the insulation.
  • Conductors never wear out.
  • Insulation deteriorates over time.
  • Insulation reacts with oxygen, ammonia, oil,
    gasoline, salts, UV and water.

48
Determining Conductor Size
  • The first step is to determine answers for five
    of the seven factors. These are
  • the load on the circuit
  • the voltage of the circuit
  • the distance from the load to the source
  • the circuit power factor
  • the type of current (phases)
  • Once these are known, the remaining two factors
    are used to determine the conductor size.
  • the ampacity of the conductor
  • the allowable voltage drop

49
Determining Conductor Size--cont.
  • Circuit load
  • The circuit load is the amperage used by the
    electrical device, or the size of over current
    protection device that will be used.
  • Circuit voltage
  • Circuit voltage is the source voltage.
  • Distance from source
  • The distance between the source and the load is
    not used as often as the run.
  • The run is the total amount of conductor that is
    used to connect the load to the source.
  • Power factor
  • The power factor for reactive loads is less than
    one.
  • The power factor for resistance loads is equal to
    one.
  • The number or phases must be know.
  • Three phase current can use smaller diameter
    wires.

50
Determining Conductor Size--cont.
  • Once values are known for the first five factors,
    the last two are used to determine the minimum
    conductor size.
  • Ampacity is the largest load that a conductor is
    designed to carry regardless of length.
  • Voltage drop is the amount of energy that is lost
    from the electricity passing through the
    resistance of the conductors.

51
Ampacity
  • Ampacity refers to the current carrying ability
    of the conductor.
  • Ampacity is dependent on the conductor
    resistance, the allowable operating temperature
    of the insulation and the heat dissipation
    ability of the conductor.
  • Ampacity increases with conductor size.
  • Ampacity for copper is higher than the ampacity
    for aluminum.
  • Ampacity is higher for conductors which have
    higher temperature ratings.
  • Exceeding the ampacity rating increases the heat
    of the insulation.
  • The amount of damage that occurs is a function of
    the amount of overload and the duration of the
    overload.
  • Ampacity ratings for conductors can be determined
    from tables such as 33-19. (Agricultural
    Mechanics)

52
Ampacity-cont.
  • Ampacity can be calculated, but tables present
    this information.
  • Example what is minimum size of conductor with
    THWN insulation in conduit, operating on 120
    volts that should be used to carry 15 amps?

AWG 14 ??
Note Based on ampacity, 14 is sufficient, but
according to the NEC 12 is smallest size of wire
that can be used under any conditions using 120 V.
Pg 35 Wiring handbook
53
Sizing Conductors by Voltage Drop
  • Voltage drop is the result of a current passing
    through a resistance.
  • Example
  • What is the percent voltage drop at the service
    entrance panel for the building in the
    illustration?

54
Example--cont.
  • The first step is to determine the total
    resistance of the circuit.

In this example the resistance for each conductor
is determined separately.
55
Example--cont.
This circuit diagram illustrates the resistance
of the conductors.
56
Example--cont.
  • The next step is to determine the voltage drop
    and the percentage drop.
  • Voltage drop is
  • Percent voltage drop is
  • This is an unacceptable voltage drop.
  • Picking the wire size first must not be the best
    way.

The conductor size is determined by calculating
the allowable resistance for the desired voltage
drop.
57
Voltage Drop Example--cont.
  • A voltage drop of 4.09 is excessive.
  • Results of excessive voltage drop.
  • The heat output of a resistance heater will
    decrease more than 8 because power output is
    proportional to the square of the voltage.
  • The useable light from an incandescent lamp will
    drop about 10.
  • Five (5) possible solutions
  • Decrease the load.
  • Use larger conductors.
  • Reduce the distance between the load and the
    source.
  • Use a conductor that has a lower resistance.
  • Use a higher voltage.
  • Of these 5 options, number 2 and 5 are usually
    the only practical solution.

58
Voltage Drop Example--cont.
  • If the voltage is increased to 240 V, what will
    be the percent voltage drop?

2.04 is an acceptable loss for this electrical
service.
59
Designing For Acceptable Voltage Drop
  • Because all conductors have resistance, it can
    not be eliminated from the circuit.
  • Therefore, circuits are designed for a specific
    voltage drop.
  • Maximum of 2 in branch circuits is common
    standard
  • NEC allows up to 3 maximum in branch circuit at
    farthest power outlet
  • NEC allows 5 maximum drop in feeder and branch
    circuit combined

60
Conductor Size Equation
  • The equation for calculating the conductor size
    (cmils) for a specified voltage drop

Note it is common practice to add 10 to the
length to account for the resistance of the
connections.
61
Conductor Size Example -1
  • Using the resistivity equation, determine the
    size of conductor that should be used to power an
    grow lamp that draws 6.6 amps and is operating on
    single phase and 120 volts. The grow lamp is
    located 75 feet from the nearest source. Copper
    conductors will be directly buried and a 2
    voltage drop is acceptable.

62
Conductor Size Example-cont.
4705.39 cmil AWG 12 Ampacity 12 Voltage
Drop 12
Note 10 has been added for connections.
63
Resistivity Equations
  • Because of inductance in the conductor, the
    equation for copper is usually changed for design
    purposes to
  • 22 constant for copper
  • I Circuit load (amp)
  • l Run (distance)
  • E Allowable voltage drop (V)

The resistivity equation for aluminum conductors
is changed to
Note in these equations the length is the one
way length, not the total length.
64
Conductor Size Example 2
  • Using the table method, determine the size of
    copper conductor that should be used to provide
    electrical service to a livestock building that
    is located 65 feet from the source. The service
    is 120 V and the estimated load for the building
    is 35 amps. UF-B cable and a 2 voltage drop
    will be used.

First determine minimum size based on ampacity.
Second determine size based on VD
AWG 8
AWG 6
65
Conductor Size Example 3
  • Determine by calculation, using the standard
    equation, the size of conductor that will be
    required to provide service to a 120 V, 1-1/2 hp
    water pump that is located 250 feet from its
    source. The conductors with be copper and
    directly buried. A 2 voltage drop is
    acceptable. The motor has a power factor of
    0.70.
  • The standard equation for copper requires values
    for amperage, voltage and length.
  • The load on the circuit, amperage, must be
    determined first.
  • 1 hp 746 watts, but when determining conductor
    sizes for electric motors it is common practice
    to use 1,000 watts per horsepower.

66
Conductor size 3--cont.
  • For this circuit with a 8.75 amp load, the
    circular mills of the conductors can be
    determined by

The conductor size is
6 26,240 cmil 8 16,510 cmil.
Which size should be used?
67
Conductor Sizing Conclusion
  • For short distances, ampacity determines the
    minimum conductor size.
  • For long distances, voltage drop determines the
    minimum size.

Because long and short are relative terms, both
ampacity and voltage drop must be checked when
sizing conductors.
68
Questions ?
Write a Comment
User Comments (0)
About PowerShow.com