Acceptance Testing - PowerPoint PPT Presentation

1 / 117
About This Presentation
Title:

Acceptance Testing

Description:

Acceptance Testing ... – PowerPoint PPT presentation

Number of Views:435
Avg rating:3.0/5.0
Slides: 118
Provided by: tdiTexas
Category:

less

Transcript and Presenter's Notes

Title: Acceptance Testing


1
Acceptance Testing
2
Acceptance Testing of Fire Protection Systems 101
  • Touch on all types of Fire Sprinkler of systems
  • Fire Pumps and Standpipes
  • Requirements for Acceptance Testing per NFPA and
    the State Fire Marshal
  • Industry Jargon and Common terminology
  • State Rules- Texas Insurance Code Chapter 6003
    28 TAC SS 34.700
  • Information in these slides comes from NFPA
    Standards 13, 14 and 20

3
Defining Terms
  • Authority Having Jurisdiction
  • Listed and Approved
  • Shall vs. Should
  • Hydrostatic Testing And Cover
  • Add and Relocates (Remodels) vs. New System
    installs
  • Main Drain Test

4
  • Control Valve Testing
  • Tagging Requirements
  • System Type- Wet, Dry, Preaction and Deluge with
    specific differences and required tests for each
  • Specific Application System- ESFR, Control Mode,
    Residential, Double Interlock, etc

5
Authority Having Jurisdiction (AHJ)
  • 3.2.2 An organization, office or individual
    responsible for enforcing the requirements of a
    code or standard, or for approving equipment,
    materials, an installation, or a procedure

6
Examples
  • Fire Chief, Fire Marshal
  • Labor Department
  • Health Department- TDADS
  • Building Official, Electrical Inspector, Plumbing
    Inspector
  • Insurance Organizations and their Representatives
  • Commanding Officer on Base

7
essentially
Anyone with a vested interest in the system
performing as intended
8
Listed
  • 3.2.2 Equipment, materials, or services
    included in a list published by an organization
    that is acceptable to the authority having
    jurisdiction.

9
Approved
  • 3.2.1 Acceptable to the authority having
    jurisdiction

Approved Materials
All materials and methods for installation are to
conform to Chapter 6 of NFPA 13- 2007 or the
individual product listings and approvals. When
in doubt..
10
Make the installing contractor prove it to your
satisfaction!!!!
  • If it looks incorrect, it probably is
  • Be wary of new products, have contractor provide
    cut sheets when in doubt
  • Good review with thorough walk through at hydro
    at end of job

11
  • Your interpretation of the codes and standards is
    to be met or proven incorrect- codes/ standards
    are in writing- not inferred
  • Sometimes corners are cut by unscrupulous
    contractors
  • Some poor installs are mistakes or human error
    - BUT.

12
Report repeat offenders to the State Fire
Marshals office!!!
13
REMEMBER
  • You are the last line of defense to ensure the
    end user gets what they expect and paid for!!!
    These are your customers, you are their expert!
  • Poor installs fail annual inspections and cost
    the owner money later for repairs

14
Shall
  • 3.2.4 Indicates a mandatory requirement.

Should
3.2.5 Indicates a recommendation or that which
advised but not required.
15
System Acceptance
  • Acceptance Testing of systems is contained in
    Chapter 24 of NFPA 13-2007 Edition
  • All required tests are listed, but required extra
    heads and some paperwork is not.

16
Hydrostatic Test
  • Section 24.2.1- All piping and attached
    appurtenances subjected to system working
    pressure shall be hydrostatically tested at 200
    psi (13.8 bar) and shall maintain that pressure
    without loss for two hours

17
  • Section 24.2.1.2- Portions of systems normally
    subjected to working pressures in excess of 150
    psi (10.4 bar) shall be tested as described in
    24.2.1.1 at a pressure of 50 psi (3.5 bar) in
    excess of working pressure

18
Things to watch at Hydro
  • Need to know expected pump churn pressure and
    expected system working pressure, are PRVs
    required?
  • Hydrostatic test pressure is taken at the bottom
    of the system, not the top (Section 24.2.1.8)

19
  • Know the limits of the materials- pressure
    limitations of fittings and sprinkler heads
  • If there is freeze potential, an interim
    pneumatic air test at 40 psi can be conducted for
    24 hours per 24.2.2. This does not remove or
    replace the requirement for a hydrostatic test.

20
  • This test is referred to as a Hydro Test or
    Cover Inspection
  • All systems require this type of test- Sprinkler,
    Standpipe, Pump
  • In new construction the pipe should not be
    covered up during the test
  • A procedure for removing test blanks must be
    in place

21
  • Retrofits are typically covered up. These are
    existing buildings and not all areas are
    accessible. Use your own judgment.
  • Walk systems during the two hour test, look for
    leaks. Small leaks are not cause for concern.
  • Excessive water leakage and pressure drop are
    cause for failure and re-test of system

22
Hydro Test Procedure
  • Contractor should have system pumped up above 200
    psi or 50 above working pressure, prior to your
    arrival to remove air pockets
  • Note Pressure on gauge upon arrival.
  • Walk system- look for leaks.

23
  • While walking system, note areas that are in need
    of repair or changes required in the system to
    installing contractor.
  • At end of two hour period, note pressure (loss if
    any). Have Contractor drain system to zero the
    gauge out in your presence.

24
Things to Keep in Mind
  • FDC piping is often overlooked- Needs to be
    tested _at_ 150psi after repair/ replacement- Sec
    24.2.1.10
  • Temperature changes affect system pressure during
    hydro.
  • Trapped air in the system takes time to escape,
    if the system has not been pumped up for some
    time then air will escape.

25
Add and Relocates
  • 24.2.1.4- Modifications affecting 20 or fewer
    sprinklers shall not require testing in excess of
    system working pressure

26
  • Per Section 24.2.1.5- Modifications above 20
    sprinklers, isolate the affected portion of the
    system and hydro
  • Per Section 24.2.1.6- Modifications that cannot
    be isolated (i.e.. Relocated drops) shall not
    require tested in excess of system working
    pressure

27
Main Drain Test
  • 24.2.3.4.1 The main drain valve shall be opened
    and remain open until system pressure stabilizes
  • 24.2.3.4.2 The static and residual pressures
    shall be recorded on the contractors material
    and test certificate
  • Use the bottom gauge

28
  • Often overlooked
  • Required on State white tags
  • Provides baseline water supply test information
    to measure water supply deterioration in
    subsequent NFPA 25 Inspections.
  • This is required on all systems! The importance
    cannot be stressed enough!

29
Size of main drains
  • Table 8.16.2.4.2-Drain Size_________
  • Riser or Main Size Size of Drain Connection
  • Up to 2 in. 3/4 in. or larger
  • 21/2 in., 3 in., 31/2 in. 11/4 in. or larger
  • 4 in. and larger 2 in. only
  • No test orifices on main drains!!!! Need fully
    open for Main Drain Test. Listed Test and drain
    assemblies are acceptable if capable of full
    flow.

30
Operational Tests
  • Referred to as a Final
  • While performing this test, an inspection should
    be performed. Things to look for
  • Loaded or painted sprinkler heads
  • Adequate coverage of all spaces
  • Missing pieces or incorrect install
  • Tamper and flow switch operation
  • Fire Alarm System should be on Test

31
Walk the space- Check head coverage
  • Light Hazard
  • 225 Sq Ft
  • Max. 15 X 15
  • Ordinary Hazard
  • 130 Sq Ft
  • Max. 15 ft X 8-8

32
  • Extra Hazard
  • 100 Sq Ft
  • Max. 10 X 10 or 12 X 8-4
  • Storage, ESFR, Control Mode
  • Look up each individual section- these change
    often
  • Request the sprinkler cut sheet from the
    Contractor- these are specific application and
    may have some special requirements

33
Obstructions
  • Depending on the type of head and the obstruction
  • Refer to Chapter 8 in NFPA 13- 07.
  • All types of heads are broken down individually

34
(No Transcript)
35
Alarm Initiating Devices
36
Testing Alarm Switches
  • Inspectors test connection should have at least
    1 inch pipe connected to a corrosion resistant
    orifice equal to the size of the smallest orifice
    on the system.
  • Open ITC all the way, alarm should sound in less
    than 5 minutes

37
  • If bell goes off too quick, have contractor
    adjust delay on alarm device to account for water
    hammer in city water to avoid nuisance alarms.
  • Ensure cover is on WF switch after test is
    performed
  • Call the monitoring company- verify signals are
    correct for the space/ bldg

38
Valve Tamper Switches
39
Testing Tamper Switches
  • 8.16.1.1.2.1- Valves on connections to water
    supplies, sectional control valves, and other
    valves in supply pipes to sprinklers and other
    fixed water based fire suppression systems shall
    be supervised by one of the following

40
  • Central station, proprietary, or remote station
    signaling at a constantly attended point
  • Local signaling service that will cause the
    sounding of an audible signal at a constantly
    attended point
  • Valves locked in the correct position
  • Valves in fenced enclosures under the owners
    control

41
Testing Tampers
  • 24.2.3.5.1 All control valves shall be fully
    closed and opened under system water pressure to
    ensure proper operation
  • Check the valve operation
  • Check Tamper operation and signal to monitoring
    company

42
24.2.4- Pressure Reducing Valves
43
Common Misinterpretation
  • PRVs should be a Pressure Reducing Valve- NOT
    Restricting or Relief Valve
  • True PRVs Reduce pressure under both Flow and
    Static Conditions
  • NFPA 14-07 Sec. 3.3.16.4
  • NFPA 13-07 Sec. 8.16.1.2.1

44
Where Required
  • Sprinkler-When working pressure exceeds 175 psi
    unless all downstream components are rated for
    the higher pressure
  • Standpipe-For Fire Hose Valves where pressure
    exceeds 175 psi on 2-1/2 FHVs pressure shall be
    limited to 100 psi- 1-1/2 valves can be of
    regulating type

45
(No Transcript)
46
PRV Requirements-Fire Sprinkler
  • 8.16.1.2.2- Pressure gauges shall be on the inlet
    and outlet sides of each pressure reducing valve
  • 8.16.1.2.3- A relief valve of not less than ½
    shall be provided on the discharge side set to
    operate at a pressure not exceeding 175 psi.

47
  • 8.16.1.2.4- A listed indicating valve shall be
    provided on the inlet side of each PRV, unless
    the PRV meets the listing requirements for use as
    an indicating valve.
  • 8.16.1.2.5- Means shall be provided downstream of
    all PRVs for flow tests at sprinkler demand

48
Acceptance Testing PRVs
  • 24.2.4.1- Each pressure-reducing valve shall be
    tested upon completion of installation to insure
    proper operation under flow and no-flow
    conditions.
  • 24.2.4.2- Testing shall verify device regulates
    outlet at maximum and normal conditions

49
  • 24.2.4.3- The results of the flow test of each
    PRV shall be recorded on the contractors
    material and test certificate
  • 24.2.4.4- The results shall include the static
    and residual inlet pressures, static and residual
    outlet pressures and the flow rate

50
Standpipe Hose Valve PRVs- NFPA 14-07 11.5.4
  • Ask for PRV Testing Logs to show work was
    completed
  • NFPA 14- 7.2 requires 1-1/2 hose valves residual
    pressure limited to 100 psi and 2-1/2 hose
    valves static and residual pressure limited to
    100 psi where pressure exceeds 175 psi

51
Backflow Prevention Assemblies-8.17.4.6
  • A.8.17.4.6- Where backflow prevention devices are
    installed, they should be in an accessible
    location to provide service and maintenance

52
  • 8.17.4.6.1- Means shall be provided downstream of
    all backflow prevention valves for flow tests at
    system demands
  • A.8.17.4.6.1 describes the describes the methods
    available- essentially ensuring the backflow will
    not restrict the system demand

53
Backflow Prevention Assemblies
Where are they Required???
  • Section 23.1.8 references AWWA M14, Recommended
    Practice for Backflow Prevention and Cross
    Connection Control and the public Health AHJ
    requirements

54
Backflow Prevention Acceptance Testing-24.2.5
  • 24.2.5.1- The backflow prevention assembly shall
    be forward flow tested to ensure proper
    operation.
  • 24.2.5.2- The minimum flow rate shall be the
    system demand, including hose stream

55
  • A copy of the state or local test report
    performed by a TCEQ approved tester should be
    attached to the riser
  • An approved inspection by the local Health AHJ
    should be provided prior to final.

56
Circulating Closed Loop Systems
  • These are covered in 24.3.
  • Requires certification of pressure ratings for
    auxiliary devices and proof of pressure test in
    all modes of operation
  • Discharge tests to be per 6.9.1- the five minute
    requirement

57
Wet Pipe System
  • For Heated Buildings
  • Commercial
  • Industrial
  • Residential
  • Hospitals
  • Educational
  • Retail
  • Most Common Sprinkler System
  • Easiest to Maintain and Operate
  • Requires the Least Amount of Testing

58
Wet System
59
Wet System Tests and Requirements
  • Hydrostatic and Cover
  • Walkthrough and Final
  • Operational (Alarms, Tamper, Main Drain Test)
  • Confirm Code compliance
  • Ensure correct number of spare heads are left on
    site per NFPA 13-2007 Section 6.2.9- Dry heads
    not required. Sprinkler Wrench is.

60
Wet System Riser Reqts
  • New systems to have White Tag and Blue ITM Tag
  • All additions over 20 heads are to have a new
    white tag added
  • Hydraulic Placard and General Information Sign
  • PRV test tags on each PRV
  • Backflow certification and Inspection by Plumbing
    Dept

61
Dry Pipe System
  • For Non-Heated Buildings
  • Commercial
  • Industrial
  • Parking Garages
  • Building Exteriors

62
Dry Pipe System
63
Dry System Tests and Requirements -24.2.2
  • Hydrostatic and Cover
  • Walkthrough and Final
  • Operational (Alarms, Tamper, Main Drain Test)
  • Confirm Code compliance
  • Ensure correct number of spare heads are left on
    site per NFPA 13-2007 Section 6.2.9- Dry heads
    not required. Sprinkler Wrench is.

64
Dry Systems Also Require
  • In addition to 200 psi hydrostatic test- an air
    leakage test is required
  • 40 psi of air for 24 hours- any leakage in excess
    of 1-1/2 psi shall be corrected

65
System Operational Test
  • 24.2.3.2 covers operational test
  • Trip test of valve and any quick opening devices-
    time how long it takes for water to be discharged
    from the inspectors test connection.
  • Verify it is per 7.2.3.6 and record it on the
    Contractors Material and Test Certificate

66
Water Delivery per NFPA 13- 2007
67
Air Compressor Testing
  • 7.2.6.2.2- The air supply shall have a capacity
    capable of restoring normal air pressure in the
    system within 30 minutes
  • A.7.2.6.2.20- When a single compressor serves
    multiple systems, the 30 minute fill time is
    based in the largest system

68
Dry System Riser Reqts
  • New systems to have White Tag and Blue ITM Tag
  • All additions over 20 heads are to have a new
    white tag added
  • Hydraulic Placard and General Information Sign
  • PRV test tags on each PRV
  • Backflow certification and Inspection by Plumbing
    Dept

69
Pre Action System
  • For Environmentally Sensitive Areas
  • Computer Rooms
  • Surgical Suites
  • Tele-Data Switch Rooms
  • Fine Art Storage Rooms

70
Pre Action System
71
Preaction Requirements -24.2.3.3
  • Hydrostatic and Cover
  • Walkthrough and Final
  • Operational (Alarms, Tamper, Main Drain Test)
  • Confirm Code compliance
  • Ensure correct number of spare heads are left on
    site per NFPA 13-2007 Section 6.2.9- Dry heads
    not required. Sprinkler Wrench is.

72
Preaction Systems Also Require
  • Test the preaction valve operation in accordance
    with the manufacturers instructions- ask for
    literature if there is any questions on operation
  • Test manual and remote control activation- this
    can be electric, pneumatic or a combination

73
  • Is the piping supervised? Sec. 7.3.2.4 requires
    supervision to ensure system integrity.
  • If supervisory air or nitrogen is used- it needs
    to conform to 7.2.6 for dry systems
  • 30 minute refill requirement.
  • Also needs to maintain a minimum supervisory
    pressure of 7 psi.

74
Preaction Riser Reqts
  • New systems to have White Tag and Blue ITM Tag
  • All additions over 20 heads are to have a new
    white tag added
  • Hydraulic Placard and General Information Sign
  • PRV test tags on each PRV
  • Backflow certification and Inspection by Plumbing
    Dept

75
Deluge System
  • For Highly Flammable Areas
  • Aircraft Hangers
  • Solvent Processing
  • Dynamite Plants

76
Deluge System
77
Deluge System Requirements -24.2.3.3
  • Hydrostatic and Cover
  • Walkthrough and Final
  • Operational (Alarms, Tamper, Main Drain Test)
  • Confirm Code compliance
  • Ensure correct number of spare heads are left on
    site per NFPA 13-2007 Section 6.2.9- Dry heads
    not required. Sprinkler Wrench is.

78
Deluge Systems Also Require
  • Test the deluge valve operation in accordance
    with the manufacturers instructions- ask for
    literature if there is any questions on operation
  • Test manual and remote control activation- this
    can be electric, pneumatic or hydraulic

79
  • Flow Testing of the system to ensure hydraulic
    performance. Calibrated gauges are to be used at
    different points on the system
  • These gauge readings are to be compared to the
    hydraulic calculations
  • Detection devices are to be automatically
    supervised

80
Deluge Riser Reqts
  • New systems to have White Tag and Blue ITM Tag
  • All additions over 20 heads are to have a new
    white tag added
  • Hydraulic Placard and General Information Sign
  • PRV test tags on each prv
  • Backflow certification and Inspection by Plumbing
    Dept

81
Standpipe System
  • For Multi-level
  • Buildings
  • Per AHJ

82
Stand Pipe System
83
Standpipe System Tests and Requirements
  • Hydrostatic and Cover
  • Walkthrough and Final
  • Operational (Alarms, Tamper, Main Drain Test)
  • Confirm Code compliance and hose thread
    compatibility
  • Flow test through roof manifold testing approved
    water source- fire pump, FD pumper truck, etc.

84
  • PRV tests. Ask for test log
  • Main Drain flow tests- record on material test
    certificate
  • Dry and semi automatic shall be trip tested to
    deliver 250 GPM at the hydraulically most remote
    hose connection within 3 minutes
  • Air testing applies per dry systems in NFPA 13

85
  • Open and close each valve manually- make sure
    hose caps are on prior to testing
  • Check for proper signage

86
Fire Pump
87
(No Transcript)
88
Fire Pump Tests and Requirements
  • Per NFPA 20- 2007 Edition Chapter 14
  • Piping to be hydrostatically tested per NFPA 13
    reqs
  • All piping sizes to be verified per table 5.25
    (a) by rated pump flow

89
(No Transcript)
90
  • All factory supplier representatives are to be in
    attendance during field acceptance tests- AHJ
    should be notified
  • As a minimum, proof of the initial startup and
    field acceptance test report should be provided
    at Fire Marshal final

91
  • A copy of the certified pump test characteristic
    curve shall be available for comparison of the
    field acceptance test.
  • Compare the curves to ensure the pump meets its
    factory specs.

92
  • Pump shall be run at minimum, rated and peak
    loads
  • How is this determined??
  • Minimum is 0 GPM or churn
  • Rated is the rating of the pump
  • i.e.. 1000 GPM pump needs to be tested at 1000
    GPM
  • Maximum is 150 of pump rating- a 1000 GPM rated
    pump is capable of 1500 GPM flow

93
  • Per NFPA 14- 2007, Section 6.2.1- Pumps shall
    furnish not less than 150 percent of rated
    capacity at not less than 65 percent of total
    rated head.
  • 6.2.2- The shutoff head shall not exceed 140
    percent of rated head for any type of pump.

94
  • Example 1- Pump is rated for 750 GPM _at_ 100 psi
  • 150 percent of load-
  • 1.5 X 750 1125
  • 65 percent of total rated head-
  • .65 X 100 65 psi
  • Pump should provide 65 psi MINIMUM at 1125 GPM

95
  • Example 2- Maximum Shutoff
  • 100 psi Fire pump
  • Maximum Shutoff Head-
  • 1.4 X 100 psi 140 psi
  • Pump shutoff pressure should not be over 140
    psi.

96
  • Keep in mind that is the Fire Pump shutoff
    pressure- the jockey of maintenance pump will add
    10 more psi to the working pressure of the system

97
(No Transcript)
98
(No Transcript)
99
(No Transcript)
100
(No Transcript)
101
  • Test fire alarm signals in Fire Pump control
    panel
  • Pump Run
  • A/C Power Fail
  • Phase Reversal
  • Normal power and alternate power

102
State Requirements
  • What does 28 TAC 34.700 The Fire Sprinkler
    Rules require for new systems and system
    modifications?

103
  • White Original Installation Tag

104
  • To be affixed to riser after new install or
    scheduled testing and maintenance.
  • To remain on riser for the life of the system-
    provides baseline water flow information for
    subsequent inspections.
  • Work for this tag to be filled out by licensed
    RME-G or RME-I.

105
  • Blue Inspection Testing and Maintenance Tag

106
  • To be affixed to riser after new install or
    scheduled testing and maintenance.
  • To remain on riser for minimum of five years-
    only to be removed by employee of authorized firm
  • Work for this tag to be filled out by licensed
    RME-G or RME-I.

107
  • Blue Service Tag

108
  • To be affixed to riser after every service
    performed
  • To remain on riser for minimum of five years-
    only to be removed by employee of authorized firm
  • Work for this tag to be filled out by Installer-
    license not needed
  • If anything is found to be impaired, a yellow or
    red tag need to be affixed as well.

109
Contractors Material and Test Certificates
  • Ensure these are filled out in their entirety and
    affixed to the riser in a protective sheath. The
    owner will want these at a later date.

110
(No Transcript)
111
(No Transcript)
112
(No Transcript)
113
(No Transcript)
114
Hydraulic Placard
  • Used in future work on system
  • Often lost over the years
  • Should be metal and permanently marked per NFPA
    13- 07

115
(No Transcript)
116
Design Criteria
  • NFPA Codes 13, 13R, 13D, 14, 20, 22, 24, 25
    101
  • UBC
  • IBC
  • IFC
  • Local AHJs
  • Other Jurisdictions Architect, Engineer
    Owner
  • Insurance Underwriter

117
Post Construction Inspections and Maintenance
  • Required per NFPA 25 and all Local Jurisdictions
  • Texas requires Licensed Inspectors
  • Identify changes in
  • Occupancy and use
  • Ceiling and finishes (i.e.. Painted and loaded
    heads)
  • Added building features(Decks, Canopies, Clouds)
  • Ensure system operation
  • Find system deficiencies and repair them in a
    timely
  • manner
Write a Comment
User Comments (0)
About PowerShow.com