Title: Acceptance Testing
1Acceptance Testing
2Acceptance Testing of Fire Protection Systems 101
- Touch on all types of Fire Sprinkler of systems
- Fire Pumps and Standpipes
- Requirements for Acceptance Testing per NFPA and
the State Fire Marshal - Industry Jargon and Common terminology
- State Rules- Texas Insurance Code Chapter 6003
28 TAC SS 34.700 - Information in these slides comes from NFPA
Standards 13, 14 and 20
3Defining Terms
- Authority Having Jurisdiction
- Listed and Approved
- Shall vs. Should
- Hydrostatic Testing And Cover
- Add and Relocates (Remodels) vs. New System
installs - Main Drain Test
4- Control Valve Testing
- Tagging Requirements
- System Type- Wet, Dry, Preaction and Deluge with
specific differences and required tests for each - Specific Application System- ESFR, Control Mode,
Residential, Double Interlock, etc
5Authority Having Jurisdiction (AHJ)
- 3.2.2 An organization, office or individual
responsible for enforcing the requirements of a
code or standard, or for approving equipment,
materials, an installation, or a procedure
6Examples
- Fire Chief, Fire Marshal
- Labor Department
- Health Department- TDADS
- Building Official, Electrical Inspector, Plumbing
Inspector - Insurance Organizations and their Representatives
- Commanding Officer on Base
7essentially
Anyone with a vested interest in the system
performing as intended
8Listed
- 3.2.2 Equipment, materials, or services
included in a list published by an organization
that is acceptable to the authority having
jurisdiction.
9Approved
- 3.2.1 Acceptable to the authority having
jurisdiction
Approved Materials
All materials and methods for installation are to
conform to Chapter 6 of NFPA 13- 2007 or the
individual product listings and approvals. When
in doubt..
10Make the installing contractor prove it to your
satisfaction!!!!
- If it looks incorrect, it probably is
- Be wary of new products, have contractor provide
cut sheets when in doubt - Good review with thorough walk through at hydro
at end of job
11- Your interpretation of the codes and standards is
to be met or proven incorrect- codes/ standards
are in writing- not inferred - Sometimes corners are cut by unscrupulous
contractors - Some poor installs are mistakes or human error
- BUT.
12Report repeat offenders to the State Fire
Marshals office!!!
13REMEMBER
- You are the last line of defense to ensure the
end user gets what they expect and paid for!!!
These are your customers, you are their expert! - Poor installs fail annual inspections and cost
the owner money later for repairs
14Shall
- 3.2.4 Indicates a mandatory requirement.
Should
3.2.5 Indicates a recommendation or that which
advised but not required.
15System Acceptance
- Acceptance Testing of systems is contained in
Chapter 24 of NFPA 13-2007 Edition - All required tests are listed, but required extra
heads and some paperwork is not.
16Hydrostatic Test
- Section 24.2.1- All piping and attached
appurtenances subjected to system working
pressure shall be hydrostatically tested at 200
psi (13.8 bar) and shall maintain that pressure
without loss for two hours
17- Section 24.2.1.2- Portions of systems normally
subjected to working pressures in excess of 150
psi (10.4 bar) shall be tested as described in
24.2.1.1 at a pressure of 50 psi (3.5 bar) in
excess of working pressure -
18Things to watch at Hydro
- Need to know expected pump churn pressure and
expected system working pressure, are PRVs
required? - Hydrostatic test pressure is taken at the bottom
of the system, not the top (Section 24.2.1.8)
19- Know the limits of the materials- pressure
limitations of fittings and sprinkler heads - If there is freeze potential, an interim
pneumatic air test at 40 psi can be conducted for
24 hours per 24.2.2. This does not remove or
replace the requirement for a hydrostatic test.
20- This test is referred to as a Hydro Test or
Cover Inspection - All systems require this type of test- Sprinkler,
Standpipe, Pump - In new construction the pipe should not be
covered up during the test - A procedure for removing test blanks must be
in place
21- Retrofits are typically covered up. These are
existing buildings and not all areas are
accessible. Use your own judgment. - Walk systems during the two hour test, look for
leaks. Small leaks are not cause for concern. - Excessive water leakage and pressure drop are
cause for failure and re-test of system
22Hydro Test Procedure
- Contractor should have system pumped up above 200
psi or 50 above working pressure, prior to your
arrival to remove air pockets - Note Pressure on gauge upon arrival.
- Walk system- look for leaks.
23- While walking system, note areas that are in need
of repair or changes required in the system to
installing contractor. - At end of two hour period, note pressure (loss if
any). Have Contractor drain system to zero the
gauge out in your presence.
24Things to Keep in Mind
- FDC piping is often overlooked- Needs to be
tested _at_ 150psi after repair/ replacement- Sec
24.2.1.10 - Temperature changes affect system pressure during
hydro. - Trapped air in the system takes time to escape,
if the system has not been pumped up for some
time then air will escape.
25Add and Relocates
- 24.2.1.4- Modifications affecting 20 or fewer
sprinklers shall not require testing in excess of
system working pressure
26- Per Section 24.2.1.5- Modifications above 20
sprinklers, isolate the affected portion of the
system and hydro - Per Section 24.2.1.6- Modifications that cannot
be isolated (i.e.. Relocated drops) shall not
require tested in excess of system working
pressure
27Main Drain Test
- 24.2.3.4.1 The main drain valve shall be opened
and remain open until system pressure stabilizes
- 24.2.3.4.2 The static and residual pressures
shall be recorded on the contractors material
and test certificate - Use the bottom gauge
28- Often overlooked
- Required on State white tags
- Provides baseline water supply test information
to measure water supply deterioration in
subsequent NFPA 25 Inspections. - This is required on all systems! The importance
cannot be stressed enough!
29Size of main drains
- Table 8.16.2.4.2-Drain Size_________
- Riser or Main Size Size of Drain Connection
- Up to 2 in. 3/4 in. or larger
- 21/2 in., 3 in., 31/2 in. 11/4 in. or larger
- 4 in. and larger 2 in. only
- No test orifices on main drains!!!! Need fully
open for Main Drain Test. Listed Test and drain
assemblies are acceptable if capable of full
flow.
30Operational Tests
- Referred to as a Final
- While performing this test, an inspection should
be performed. Things to look for - Loaded or painted sprinkler heads
- Adequate coverage of all spaces
- Missing pieces or incorrect install
- Tamper and flow switch operation
- Fire Alarm System should be on Test
31Walk the space- Check head coverage
- Light Hazard
- 225 Sq Ft
- Max. 15 X 15
- Ordinary Hazard
- 130 Sq Ft
- Max. 15 ft X 8-8
32- Extra Hazard
- 100 Sq Ft
- Max. 10 X 10 or 12 X 8-4
- Storage, ESFR, Control Mode
- Look up each individual section- these change
often - Request the sprinkler cut sheet from the
Contractor- these are specific application and
may have some special requirements
33Obstructions
- Depending on the type of head and the obstruction
- Refer to Chapter 8 in NFPA 13- 07.
- All types of heads are broken down individually
34(No Transcript)
35Alarm Initiating Devices
36Testing Alarm Switches
- Inspectors test connection should have at least
1 inch pipe connected to a corrosion resistant
orifice equal to the size of the smallest orifice
on the system. - Open ITC all the way, alarm should sound in less
than 5 minutes
37- If bell goes off too quick, have contractor
adjust delay on alarm device to account for water
hammer in city water to avoid nuisance alarms. - Ensure cover is on WF switch after test is
performed - Call the monitoring company- verify signals are
correct for the space/ bldg
38Valve Tamper Switches
39Testing Tamper Switches
- 8.16.1.1.2.1- Valves on connections to water
supplies, sectional control valves, and other
valves in supply pipes to sprinklers and other
fixed water based fire suppression systems shall
be supervised by one of the following
40- Central station, proprietary, or remote station
signaling at a constantly attended point - Local signaling service that will cause the
sounding of an audible signal at a constantly
attended point - Valves locked in the correct position
- Valves in fenced enclosures under the owners
control
41Testing Tampers
- 24.2.3.5.1 All control valves shall be fully
closed and opened under system water pressure to
ensure proper operation - Check the valve operation
- Check Tamper operation and signal to monitoring
company
4224.2.4- Pressure Reducing Valves
43Common Misinterpretation
- PRVs should be a Pressure Reducing Valve- NOT
Restricting or Relief Valve - True PRVs Reduce pressure under both Flow and
Static Conditions - NFPA 14-07 Sec. 3.3.16.4
- NFPA 13-07 Sec. 8.16.1.2.1
44Where Required
- Sprinkler-When working pressure exceeds 175 psi
unless all downstream components are rated for
the higher pressure - Standpipe-For Fire Hose Valves where pressure
exceeds 175 psi on 2-1/2 FHVs pressure shall be
limited to 100 psi- 1-1/2 valves can be of
regulating type
45(No Transcript)
46PRV Requirements-Fire Sprinkler
- 8.16.1.2.2- Pressure gauges shall be on the inlet
and outlet sides of each pressure reducing valve - 8.16.1.2.3- A relief valve of not less than ½
shall be provided on the discharge side set to
operate at a pressure not exceeding 175 psi.
47- 8.16.1.2.4- A listed indicating valve shall be
provided on the inlet side of each PRV, unless
the PRV meets the listing requirements for use as
an indicating valve. - 8.16.1.2.5- Means shall be provided downstream of
all PRVs for flow tests at sprinkler demand
48Acceptance Testing PRVs
- 24.2.4.1- Each pressure-reducing valve shall be
tested upon completion of installation to insure
proper operation under flow and no-flow
conditions. - 24.2.4.2- Testing shall verify device regulates
outlet at maximum and normal conditions
49- 24.2.4.3- The results of the flow test of each
PRV shall be recorded on the contractors
material and test certificate - 24.2.4.4- The results shall include the static
and residual inlet pressures, static and residual
outlet pressures and the flow rate
50Standpipe Hose Valve PRVs- NFPA 14-07 11.5.4
- Ask for PRV Testing Logs to show work was
completed - NFPA 14- 7.2 requires 1-1/2 hose valves residual
pressure limited to 100 psi and 2-1/2 hose
valves static and residual pressure limited to
100 psi where pressure exceeds 175 psi
51Backflow Prevention Assemblies-8.17.4.6
- A.8.17.4.6- Where backflow prevention devices are
installed, they should be in an accessible
location to provide service and maintenance
52- 8.17.4.6.1- Means shall be provided downstream of
all backflow prevention valves for flow tests at
system demands - A.8.17.4.6.1 describes the describes the methods
available- essentially ensuring the backflow will
not restrict the system demand
53Backflow Prevention Assemblies
Where are they Required???
- Section 23.1.8 references AWWA M14, Recommended
Practice for Backflow Prevention and Cross
Connection Control and the public Health AHJ
requirements
54Backflow Prevention Acceptance Testing-24.2.5
- 24.2.5.1- The backflow prevention assembly shall
be forward flow tested to ensure proper
operation. - 24.2.5.2- The minimum flow rate shall be the
system demand, including hose stream
55- A copy of the state or local test report
performed by a TCEQ approved tester should be
attached to the riser - An approved inspection by the local Health AHJ
should be provided prior to final.
56Circulating Closed Loop Systems
- These are covered in 24.3.
- Requires certification of pressure ratings for
auxiliary devices and proof of pressure test in
all modes of operation - Discharge tests to be per 6.9.1- the five minute
requirement
57Wet Pipe System
- For Heated Buildings
- Commercial
- Industrial
- Residential
- Hospitals
- Educational
- Retail
- Most Common Sprinkler System
- Easiest to Maintain and Operate
- Requires the Least Amount of Testing
58Wet System
59Wet System Tests and Requirements
- Hydrostatic and Cover
- Walkthrough and Final
- Operational (Alarms, Tamper, Main Drain Test)
- Confirm Code compliance
- Ensure correct number of spare heads are left on
site per NFPA 13-2007 Section 6.2.9- Dry heads
not required. Sprinkler Wrench is.
60Wet System Riser Reqts
- New systems to have White Tag and Blue ITM Tag
- All additions over 20 heads are to have a new
white tag added - Hydraulic Placard and General Information Sign
- PRV test tags on each PRV
- Backflow certification and Inspection by Plumbing
Dept
61Dry Pipe System
- For Non-Heated Buildings
- Commercial
- Industrial
- Parking Garages
- Building Exteriors
62Dry Pipe System
63Dry System Tests and Requirements -24.2.2
- Hydrostatic and Cover
- Walkthrough and Final
- Operational (Alarms, Tamper, Main Drain Test)
- Confirm Code compliance
- Ensure correct number of spare heads are left on
site per NFPA 13-2007 Section 6.2.9- Dry heads
not required. Sprinkler Wrench is.
64Dry Systems Also Require
- In addition to 200 psi hydrostatic test- an air
leakage test is required - 40 psi of air for 24 hours- any leakage in excess
of 1-1/2 psi shall be corrected
65System Operational Test
- 24.2.3.2 covers operational test
- Trip test of valve and any quick opening devices-
time how long it takes for water to be discharged
from the inspectors test connection. - Verify it is per 7.2.3.6 and record it on the
Contractors Material and Test Certificate
66Water Delivery per NFPA 13- 2007
67Air Compressor Testing
- 7.2.6.2.2- The air supply shall have a capacity
capable of restoring normal air pressure in the
system within 30 minutes - A.7.2.6.2.20- When a single compressor serves
multiple systems, the 30 minute fill time is
based in the largest system
68Dry System Riser Reqts
- New systems to have White Tag and Blue ITM Tag
- All additions over 20 heads are to have a new
white tag added - Hydraulic Placard and General Information Sign
- PRV test tags on each PRV
- Backflow certification and Inspection by Plumbing
Dept
69Pre Action System
- For Environmentally Sensitive Areas
- Computer Rooms
- Surgical Suites
- Tele-Data Switch Rooms
- Fine Art Storage Rooms
70Pre Action System
71Preaction Requirements -24.2.3.3
- Hydrostatic and Cover
- Walkthrough and Final
- Operational (Alarms, Tamper, Main Drain Test)
- Confirm Code compliance
- Ensure correct number of spare heads are left on
site per NFPA 13-2007 Section 6.2.9- Dry heads
not required. Sprinkler Wrench is.
72Preaction Systems Also Require
- Test the preaction valve operation in accordance
with the manufacturers instructions- ask for
literature if there is any questions on operation - Test manual and remote control activation- this
can be electric, pneumatic or a combination
73- Is the piping supervised? Sec. 7.3.2.4 requires
supervision to ensure system integrity. - If supervisory air or nitrogen is used- it needs
to conform to 7.2.6 for dry systems - 30 minute refill requirement.
- Also needs to maintain a minimum supervisory
pressure of 7 psi.
74Preaction Riser Reqts
- New systems to have White Tag and Blue ITM Tag
- All additions over 20 heads are to have a new
white tag added - Hydraulic Placard and General Information Sign
- PRV test tags on each PRV
- Backflow certification and Inspection by Plumbing
Dept
75Deluge System
- For Highly Flammable Areas
- Aircraft Hangers
- Solvent Processing
- Dynamite Plants
76Deluge System
77Deluge System Requirements -24.2.3.3
- Hydrostatic and Cover
- Walkthrough and Final
- Operational (Alarms, Tamper, Main Drain Test)
- Confirm Code compliance
- Ensure correct number of spare heads are left on
site per NFPA 13-2007 Section 6.2.9- Dry heads
not required. Sprinkler Wrench is.
78Deluge Systems Also Require
- Test the deluge valve operation in accordance
with the manufacturers instructions- ask for
literature if there is any questions on operation - Test manual and remote control activation- this
can be electric, pneumatic or hydraulic
79- Flow Testing of the system to ensure hydraulic
performance. Calibrated gauges are to be used at
different points on the system - These gauge readings are to be compared to the
hydraulic calculations - Detection devices are to be automatically
supervised
80Deluge Riser Reqts
- New systems to have White Tag and Blue ITM Tag
- All additions over 20 heads are to have a new
white tag added - Hydraulic Placard and General Information Sign
- PRV test tags on each prv
- Backflow certification and Inspection by Plumbing
Dept
81Standpipe System
- For Multi-level
- Buildings
- Per AHJ
82Stand Pipe System
83Standpipe System Tests and Requirements
- Hydrostatic and Cover
- Walkthrough and Final
- Operational (Alarms, Tamper, Main Drain Test)
- Confirm Code compliance and hose thread
compatibility - Flow test through roof manifold testing approved
water source- fire pump, FD pumper truck, etc.
84- PRV tests. Ask for test log
- Main Drain flow tests- record on material test
certificate - Dry and semi automatic shall be trip tested to
deliver 250 GPM at the hydraulically most remote
hose connection within 3 minutes - Air testing applies per dry systems in NFPA 13
85- Open and close each valve manually- make sure
hose caps are on prior to testing - Check for proper signage
86Fire Pump
87(No Transcript)
88Fire Pump Tests and Requirements
- Per NFPA 20- 2007 Edition Chapter 14
- Piping to be hydrostatically tested per NFPA 13
reqs - All piping sizes to be verified per table 5.25
(a) by rated pump flow
89(No Transcript)
90- All factory supplier representatives are to be in
attendance during field acceptance tests- AHJ
should be notified - As a minimum, proof of the initial startup and
field acceptance test report should be provided
at Fire Marshal final
91- A copy of the certified pump test characteristic
curve shall be available for comparison of the
field acceptance test. - Compare the curves to ensure the pump meets its
factory specs.
92- Pump shall be run at minimum, rated and peak
loads - How is this determined??
- Minimum is 0 GPM or churn
- Rated is the rating of the pump
- i.e.. 1000 GPM pump needs to be tested at 1000
GPM - Maximum is 150 of pump rating- a 1000 GPM rated
pump is capable of 1500 GPM flow
93- Per NFPA 14- 2007, Section 6.2.1- Pumps shall
furnish not less than 150 percent of rated
capacity at not less than 65 percent of total
rated head. - 6.2.2- The shutoff head shall not exceed 140
percent of rated head for any type of pump.
94- Example 1- Pump is rated for 750 GPM _at_ 100 psi
- 150 percent of load-
- 1.5 X 750 1125
- 65 percent of total rated head-
- .65 X 100 65 psi
- Pump should provide 65 psi MINIMUM at 1125 GPM
95- Example 2- Maximum Shutoff
- 100 psi Fire pump
- Maximum Shutoff Head-
- 1.4 X 100 psi 140 psi
- Pump shutoff pressure should not be over 140
psi.
96- Keep in mind that is the Fire Pump shutoff
pressure- the jockey of maintenance pump will add
10 more psi to the working pressure of the system
97(No Transcript)
98(No Transcript)
99(No Transcript)
100(No Transcript)
101- Test fire alarm signals in Fire Pump control
panel - Pump Run
- A/C Power Fail
- Phase Reversal
- Normal power and alternate power
-
102State Requirements
- What does 28 TAC 34.700 The Fire Sprinkler
Rules require for new systems and system
modifications?
103- White Original Installation Tag
104- To be affixed to riser after new install or
scheduled testing and maintenance. - To remain on riser for the life of the system-
provides baseline water flow information for
subsequent inspections. - Work for this tag to be filled out by licensed
RME-G or RME-I.
105- Blue Inspection Testing and Maintenance Tag
106- To be affixed to riser after new install or
scheduled testing and maintenance. - To remain on riser for minimum of five years-
only to be removed by employee of authorized firm - Work for this tag to be filled out by licensed
RME-G or RME-I.
107 108- To be affixed to riser after every service
performed - To remain on riser for minimum of five years-
only to be removed by employee of authorized firm - Work for this tag to be filled out by Installer-
license not needed - If anything is found to be impaired, a yellow or
red tag need to be affixed as well.
109Contractors Material and Test Certificates
- Ensure these are filled out in their entirety and
affixed to the riser in a protective sheath. The
owner will want these at a later date.
110(No Transcript)
111(No Transcript)
112(No Transcript)
113(No Transcript)
114Hydraulic Placard
- Used in future work on system
- Often lost over the years
- Should be metal and permanently marked per NFPA
13- 07
115(No Transcript)
116Design Criteria
- NFPA Codes 13, 13R, 13D, 14, 20, 22, 24, 25
101 - UBC
- IBC
- IFC
- Local AHJs
- Other Jurisdictions Architect, Engineer
Owner - Insurance Underwriter
117Post Construction Inspections and Maintenance
- Required per NFPA 25 and all Local Jurisdictions
- Texas requires Licensed Inspectors
- Identify changes in
- Occupancy and use
- Ceiling and finishes (i.e.. Painted and loaded
heads) - Added building features(Decks, Canopies, Clouds)
- Ensure system operation
- Find system deficiencies and repair them in a
timely - manner