Title: Folie 1
1Chilled Beams for Laboratory HVAC Applications
TROX USA
2Chilled Ceilings and Beams Early 1980s
1980
1990
2005
Chilled Ceilings
- Buildings well insulated for heating
- Advent of personal computers
- Need to remove heat from space
3Principle of Operation Chilled Ceiling Panels
4Radiant Effect on Occupants Chilled Ceiling Panels
5Chilled Ceiling Systems
- Improved thermal comfort
- Typically combined with displacement ventilation
system - Low turbulence intensity decreases draft risks
6Chilled Ceiling Systems
- Improved thermal comfort
- Minimal space requirements
- No additional space required in ceiling cavity
- Easy to install in retrofit applications
7Chilled Ceiling Systems
- Improved thermal comfort
- Minimal space requirements
- Low energy cooling solution
- High heat transfer efficiencies using water
- Low transport costs
8 Cooling Capacity Comparison
9Chilled Ceiling Systems
- Improved thermal comfort
- Minimal space requirements
- Low energy cooling solution
- Limited Cooling Capacity
- 25 BTUH/FT2 of active panel
- 18 BTUH/FT2 of floor area (based on 70 active
ceiling)
10Chilled Ceilings and Beams Early 1990s
1980
1990
2000
2005
Chilled Ceilings
Passive Beams
- Increased equipment loads
- Greater occupant densities
- Inadequate perimeter cooling
11 Passive Chilled Beams
- Ceiling manufacturers begin to sell high free
area perforation panels competitively - Convective coils replace ceiling panels
12 Passive Chilled Beams
Concrete soffit
13Passive Chilled Beam Air Distribution Pattern
14Passive Chilled Beams
Exposed Beams
Recessed Beams
15 Passive Beam Components
Support Rods
Heat Transfer Coil
Separation Skirt
Optional Cabinet
16Passive Chilled Beams Interior Area Installation
H is between 4 and 12 in. Z should be 0.33B
Z
H
B
B x 2
17Passive Chilled Beams Perimeter Installation
B
B x 1.5
18 Passive Beam Installations
19 Passive Beam Installations
20Chilled Ceilings and Beams Mid 1990s
1980
1990
2000
2005
Chilled Ceilings
Passive Beams
Active Beams
- Continually increasing sensible loads
- Greater occupant densities
- Gypsum board tiles become common
- Combine cooling and ventilation
21Active Chilled Beams
Concrete soffit
Primary air supply
Suspended Ceiling
22Active Chilled Beam Air Distribution Pattern
23 Active Chilled Beams
- Sensible loads up to 70 BTUH/FT2
- Primary air delivered at conventional (50 to
55ºF) temperatures at or near minimum ventilation
flow rate - Can be used with fiberglass ceiling tiles or
without any ceiling
24 Active Beam Installation
25 Active Beam Installation
26Comparative Energy Costs
1.50
1.00
0.80
Typical Annual HVAC Energy Cost (/FT2)
0.48
VAV System
Passive Beam with Displacement Ventilation
Chilled Ceiling with Natural Ventilation
Active Chilled Beam
27Active Chilled Beams For Laboratory HVAC
Applications
1990
2000
2005
Chilled Ceilings
Passive Beams
Active Beams
Active Beams for Lab HVAC
28Laboratory Design Issues
- Space sensible heat gains of 60 to 70 BTUH/FT2
- Space ventilation requirements of 6 to 8 ACH-1
- Laboratories where chemicals and gases are
present require 100 OA - All air systems require 18 to 22 ACH-1 to satisfy
sensible load
29Active Chilled Beams in a General Use Laboratory
Sensible Heat Gain 65 BTUH/FT2
Ventilation Rate 8 ACH-1
30Active Chilled Beams in a General Use Laboratory
Sensible Heat Gain 65 BTUH/FT2
All Air Solution 18 ACH-1
Ventilation Rate 8 ACH-1
Air-Water Solution 8 ACH-1
31 Case Study
- Laboratory Design for Pharmaceutical Company
- Location St. Louis, MO
- Outdoor Design Conditions 94DB/75WB
- Laboratory Space 54,000 FT2
- Minimum Ventilation Rate 8 ACH-1
- Space Sensible Heat Gain 72 BTUH/FT2
32 Equipment Requirements
33 Cooling Energy Requirement Example
1000 FT2 LAB (10 CLGS)
TSHG 70 BTUH/FT2
VENTILATION 8 ACH-1
8.0
7.0
6.0
TOTAL ENERGY, ALL AIR SOLUTION
5.0
4.0
TOTAL ENERGY, AIR-WATER SOLUTION
TOTAL COOLING ENERGY (kW)
3.0
45
2.0
Chilled beam air side cooling
1.0
Chilled beam water side cooling
65
70
75
80
85
90
60
OUTDOOR TEMPERATURE (F)
34Energy Comparisons Case Study, 93/75F Outdoor
Design
- Active Chilled Beam (Parallel Sensible Cooling)
- Reduced fan power 32 from Base VAV
- Reduced cooling energy 46 from Base VAV
- Reduced ductwork sizes 18-20 ACPH to 6-8 ACH-1
- Higher Pumping energy 15 - Offset by other
savings - Higher cooling system efficiencies
- Overall 35 Reduction in Energy Costs
35Energy Comparisons Modified for 80/64F Outdoor
Design
- Active Chilled Beam (Parallel Sensible Cooling)
- Reduced fan power 32 from Base VAV
- Reduced cooling energy 30 from Base VAV
- Reduced ductwork sizes 18-20 ACPH to 6-8 ACH-1
- Higher Pumping energy 15 - Offset by other
savings - Higher cooling system efficiencies
- Overall 25 Reduction in Energy Costs
36 Equipment Requirements
37 Chilled Ceilings and Beams
TROX USA