N.F.P.A. 13R - PowerPoint PPT Presentation

1 / 28
About This Presentation
Title:

N.F.P.A. 13R

Description:

N.F.P.A. 13R Justin Bohlmann FIR-204 Table of Contents What is NFPA 13R? Grandfather Clause Identification Types of Sprinkler ... – PowerPoint PPT presentation

Number of Views:246
Avg rating:3.0/5.0
Slides: 29
Provided by: facultySun
Category:
Tags: 13r

less

Transcript and Presenter's Notes

Title: N.F.P.A. 13R


1
N.F.P.A. 13R
  • Justin Bohlmann
  • FIR-204

2
Table of Contents
  • What is NFPA 13R?
  • Grandfather Clause
  • Identification
  • Types of Sprinkler Systems
  • Wet-Pipe
  • Dry and Pre-action
  • Sprinkler Heads
  • Upright
  • Pendant
  • Sidewall
  • An Overview of The Sprinkler System
  • Rated Pressure
  • Temperature
  • The use of reconditioned equipment
  • Post Indicator Valve
  • Protection from Hazards
  • Working Plans
  • Testing
  • Water Supply
  • Fire Department Connection
  • Water Flow Alarms
  • Where are Sprinklers Not Needed?
  • Maintenance
  • Source Page

3
What is N.F.P.A 13R?
  • This standard covers the design and installation
    of Automatic Sprinkler Systems in residential
    occupancies up to and including four stories in
    height

4
Grandfather Clause
  • 1.3 Retroactivity
  • Unless otherwise specified, the provisions of
    this standard shall not apply to facilities,
    equipment, structures, or installations that
    existed or were approved for construction or
    installation prior to the effective date of the
    standard

5
Identification
  • Sprinkler Systems
  • Control, Drain, and Test Valves
  • Securing the Sign
  • What needs to be on the sign

6
Types of Sprinkler Systems
  • Wet Pipe
  • Pre-action
  • Dry Pipe

7
Wet Pipe
  • May be used were piping is installed in areas
    that can be reliably maintained at a temperature
    above 40 degrees Fahrenheit

8
Dry and Pre-action
  • These systems are used when piping cannot be
    maintained at a temperature of 40 degrees
    Fahrenheit or greater
  • Where these systems are installed they shall be
    installed under N.F.P.A. 13 (The Standard for the
    Installation of Sprinkler Systems )

9
Upright and Pendant Sprinkler Heads
  • Heads that have not been listed with specific
    positioning criteria shall be positioned so that
    the deflectors are within 1in.-4in from the
    ceiling
  • Must be located 3 ft from obstructions
  • Center of obstruction to the center of the head
  • Where heads cannot be placed 3ft from an
    obstruction they shall be placed at either side
    of the obstruction

10
Sidewall Sprinkler Heads
  • Sidewall heads shall be located so that their
    deflectors are 4in.-6in. From the ceiling
  • Must be located 5 ft from obstructions
  • Center of obstruction to the center of the head
  • Where heads cannot be placed 5ft from an
    obstruction they shall be placed at either side
    of the obstruction

11
The Sprinkler System
12
Rated Pressure
  • Manufacturers recommendations
  • for sprinkler heads
  • Follow unless they are less than
  • 175 psi for aboveground
  • 150 psi for underground
  • Piping
  • 175 psi
  • Fittings
  • 175 psi

13
Temperature
  • Sprinkler heads must be color coded in accordance
    with Table 5.1.1.5.1
  • Corrosion resistive heads
  • Recessed, flushed, or concealed sprinklers
  • Liquid in bulb-type sprinklers

14
Reconditioned Equipment
  • Valves and Devices
  • Sprinkler Heads

15
Post Indicator Valve
16
Protection
  • Corrosion
  • Freezing
  • Hazardous Areas

17
Working Plans
  • Must be approved by the AHJ
  • Changes from original plan must also be approved
    through the AHJ
  • These plans must provide
  • Plan of each floor
  • Easily duplicated

18
Working Plans
  • Indicate
  • Name of owner and occupant
  • Location
  • Point of compass
  • Ceiling construction
  • Location of fire walls and partitions
  • Occupancy
  • Concealed spaces

19
Working Plans
  • Indicate ( Cont)
  • Areas where there are no sprinklers
  • Size of the city main
  • Make and manufacture's of the sprinklers
  • Number of sprinklers
  • Location of alarm bells
  • All control valves and connections
  • Underground piping
  • Name and address of contractor

20
Testing
  • Installer must perform all required tests prior
    to submitting request for approval
  • The AHJ is required to be present during the
    conduction of testing for approval
  • Hydrostatic Pressure

21
Water Supply
  • Every system must have at least one automatic
    supply of water and it must be able to supply a
    system demand for at least 30 min.
  • If a fire pump is installed it must be installed
    under NFPA 20 The Standard for the Installation
    of Stationary Pumps for Fire Protection

22
Fire Department Connection (FDC)
  • At least one fire department connection shall be
    provided for buildings that exceed 2000 square
    ft
  • They must be
  • At least 1 ½ in orifice size
  • Must be labeled for what building or area it
    covers or protects

23
Sprinkler Head Specifications
  • If a sprinkler is to be located in an area with a
    temperature less than 100 degrees Fahrenheit the
    head shall be an ordinary temperature rated
    sprinkler
  • If the temperature exceeds 101 degrees Fahrenheit
    then an intermediate-rated sprinkler must be used

24
Sprinkler Head Specifications
  • Sprinklers located under direct sunlight or in
    unventilated areas such as attics or storage
    closets, shall be of an intermediate temperature
    classification

25
Water Flow Alarms
  • An alarm shall be installed to notify the
    occupants of a water flow in the building
  • If the building is maintained by an Automatic
    Fire Detection System the water flow alarm shall
    be connected to the system

26
Where are Sprinklers not Needed?
  • In Bathrooms which do not exceed 55ft
  • In closets, and pantries under the following
    conditions
  • The area does not exceed 24ft.
  • The walls and ceilings are surfaced with
    noncombustible or limited combustible materials
  • Porches, Balconies, or stairs that are open and
    attached

27
Maintenance
  • The owner shall be required for the maintenance
    and the condition of the sprinkler system and
    shall keep it in normal condition
  • Systems shall be inspected, tested, and
    maintained under the direction of NFPA 25 The
    standard for the Inspection, Testing, and
    Maintenance of Water-Based Fire Protection
    Systems

28
Sources
  • N.F.P.A 13R The Standard For The Installation of
    Sprinkler Systems in Residential Occupancies up
    to and Including Four Stories in Height
  • N.F.P.A. Handbook Sec. 10 Ch. 11 Pg. 185
    Automatic Sprinkler Systems
Write a Comment
User Comments (0)
About PowerShow.com