Title: FIRE ALARM SYSTEM
1(No Transcript)
2FIRE ALARM SYSTEM Smoke
Partitions
3Long Term Care Facilities shall have a complete
fire alarm system installed in accordance with
NFPA 101, Chapter 18.3.4, 2000 edition.
Facilities licensed prior to August 28, 2007 that
do not meet this standard shall have until
December 31, 2008 to comply.
4Fire Alarm System Installation
- The system shall be installed and maintained per
NFPA 72
- Plans must be submitted to DHSS for review and
approval
- Shall be designed by qualified personnel
- Installed by qualified personnel or installation
supervised by qualified personnel.. go to - WWW.DFS.DPS.Mo.gov for guidance
5Fire alarm system at a minimum shall include
- Interconnected smoke detectors
- Automatic transmission to the fire department,
dispatching agency or central monitoring company - Manual pull stations at each required exit and
attendants station - Heat detectors
- Audible visual alarm indicators
6ALSO
- Monitored battery backup control panel
- All components shall be listed by UL or FM for
use in commercial fire alarm systems
7Fire alarm system coverage shall include
- All rooms
- Halls
- Storage areas
- Basements, attics, lofts
- Elevator shafts
- Enclosed stairways
- Dumb waiter shafts, and chutes
- Note this includes sprinkler heads connected to
the fire alarm
8New Amended rules Fire Alarm
- Two types of facilities
- A. Facilities that did not have a
complete fire alarm system prior to
August 28, 2007. - B. Facilities that had a complete fire alarm
system prior to August 28, 2007. Some
Grandfathering
9Facilities that did not have a
complete fire alarm system prior to August
28, 2007. 2007 did not have fire alarm
- Coverage by Sprinkler Type
- 1. NFPA 13 Facilities- sprinkler heads everywhere
- 2. NFPA 13R facilities- no heads- attic, closets,
restrooms - 3. Non-Sprinkled facilities
In 2007
10Detection coverage in NFPA 13 Facilities, 1999
edition 2007 did not have fire alarm
- Smoke Detectors
- Corridors spaces open to the corridors (no door
between). - No more than 30 apart.
- No point on the ceiling more than 21 from a
detector. - All required detectors shall be connected to
the fire alarm system. No heat detectors required.
In 2007
11Detection coverage in NFPA 13R Facilities, 1999
edition 2007 did not have fire alarm
- ?Smoke Detectors
- Corridors spaces open to the
corridors - (no door between). No more than
30 apart. - No point on the ceiling more
than 21 from a detector. - ?Heat Detectors
- In accessible spaces not
protected by - sprinkler heads (spacing per
NFPA 72, 1999). - Exceptions
- Bathrooms NOT exceeding 55 sq. ft.
- Clothes, linen closets pantries
NOT - exceeding 24 sq. ft. only if
walls and ceiling of limited - combustible or non-combustible
materials.
In 2007
12Detection coverage in Non-Sprinkled Facilities
2007 did not have fire alarm
- Full coverage detection system.
- Smoke Detectors
- 1.All Habitable spaces except
prohibited environment - 2. No more than 30 apart
- 3. No point on ceiling more than
21 from a detector - Heat Detectors
- Kitchens, laundries, bathrooms,
mechanical rooms, attics - Exceptions
- Bathrooms NOT exceeding 55 sq. ft.
- Clothes, linen closets pantries
NOT - exceeding 24 sq. ft. only if
walls and ceiling of limited - combustible or non-combustible
materials.
In 2007
13Facilities that had a complete fire alarm system
prior Aug. 28,2007. Some Grandfathering 2007
had a fire alarm
- Previous/existing Rules for smoke detectors till
2013 - Smoke detectors interconnected to the complete
fire alarm system shall be located no more than
thirty feet (30') apart in the corridors or
passageways with no point in the corridor or
passageway more than fifteen feet (15') from a
detector and no point in the building more than
thirty feet (30) from a detector. In facilities
licensed prior to November 13, 1980, smoke
detectors located every fifty feet (50') will be
acceptable. I/II Issue Replacement detectors
with same type to ensure compliance with 50
distance.
14Temporary grandfathering for Facilities without
an approved sprinkler system 2007 had a fire
alarm system
- shall have one (1) or more individual home-type
smoke detectors per resident-use room. The
individual home-type smoke detectors shall be
UL-approved battery-powered detectors that sense
smoke and automatically sound an alarm which can
be heard throughout the facility. I/II Issue
Heard throughout the facility. Intent is that the
alarm can be heard at no less than seventy (70)
decibels (dBA) at pillow level in the room the
smoke detector is installed to comply with 1999
edition of NFPA 72.
In 2007
15No Grandfathering for Heat Detection 2007 had a
fire alarm system
- Heat detectors, interconnected to the fire alarm
system, shall be installed in areas where
environmental influences may cause nuisance
alarms, unless the area is protected by an
approved sprinkler system. Such areas include,
but are not limited to kitchens, laundries,
bathrooms, mechanical air handling rooms, and
attic spaces. Bathrooms not exceeding fifty-five
(55) square feet are exempt from having a heat
detector if the wall and ceilings are surfaced
with limited-combustible or non-combustible
material
Matters not 2007
16Facility procedures
- All facilities shall test and maintain the
complete fire alarm system in accordance with
NFPA 72, 1999 edition. I/II
- Facilities shall test by activating the complete
fire alarm system at least once a month. I/II
17Documentation
- Facilities shall maintain a record of the
complete fire alarm tests, inspections and
certifications. III
18ALARM SYSTEM TESTING
- Be tested annually by qualified personnel
- All facilities shall have inspections and written
certifications of the complete fire alarm system
completed by an approved qualified service
representative in accordance with NFPA 72,
1999 edition, at least annually. I/II
19Monthly testing shall
- Include a visual check of all initiating and
warning devices and the alarm control panel
- Control panel shall be inspected to ensure
indicating lights are in the correct position and
the proper color - The panel has not been silenced
- No supervisory audio signal present
20If fire alarm system malfunctions
- If the fire alarm is in alarm or trouble mode and
is unable to be reset for 4 hours or more - a
fire watch must be initiated and DHSS and the
local Fire Department shall be contacted - If system does not reset, contact the monitoring
and fire alarm companies
21Smoke Compartments Amended rules
- Every floor shall be divided into not less than
two smoke compartments with each compartment not
exceeding 150 feet in length.
- Each smoke section shall be separated by one-hour
fire rated walls that are continuous from outside
wall-to-outside wall and from floor-to-floor or
floor-to-roof deck. - Exception Facilities with floor dimensions that
do not exceed 75 feet in length or width
22Smoke Compartments Amended rules
- Partial grandfathering
- All facilities licensed prior to 12-31-87 and 20
or fewer beds prior to 08-28-07
- Permits termination at underside of a monolithic
or suspended ceiling that is a continuous
membrane with smoketight joints. - Doors shall be at least 1-3/4 solid doors or
equivalent. - No above plenum use.
23Carbon Monoxide Alarms
- Not required but highly recommended
- Colorless, odorless gas- higher health risk to
elderly and infants - Can be a stand alone device
- One detector per wing or smoke compartment in the
hallway - Can be battery operated
- Replacement every five years
24Full Coverage Smoke Detection System
- Not required but highly recommended
- Interconnected smoke detectors in combination
with sprinkler heads in all habitable spaces - No point on any ceiling space greater than 21
feet from a smoke detector
25Questions ?
26(No Transcript)