Title: AS-Interface Safety now included!
1AS-Interface Safety now included!
2AS-Interface Safe - Headlines
- Integration of all binary safety-related
components in AS-Interface, such as - Emergency stop
- Protective door switch
- Safety light barriers/grids
- Contactor controls, etc.
- Combined operation of standard and safety-related
components via the yellow AS-i cable - Fail-safe PLC or special master not necessary due
to safety monitor - It is possible to form groups of safe signals
within a network - Diagnostics via standard master/standard PLC
3Features of the system
- Can be used up to control category 4 according to
EN 954 -1 - Response time max. 35 ms
- Approved by BIA1 and TÃœV2
- Full compatibility with all other AS components
according to EN 50 295 - Use of the standard AS-Interface protocol
- Maximum extension of the system with 31 safe
slaves - Stop category 0 or 1 can be set
- Compatable with AS-Interface V2.1
4Safety-related and standard components in an
AS-Interface network
Standard PLC andstandard master
Safety monitor
Safe emergency stop button
Safe module
Safe light grid
AS-i power unit
Safe position switch
Safe light barrier
5Safety Monitor
- Monitor for monitoring safe slaves
- 1 or 2 two-channel enable circuit for safe
switching off - Several safety monitors in one AS-Interface
system are possible - Diagnostics via LEDs, configuration software and
AS-Interface/controls - Parameters can be set for the following
functions - Contactor control
- Stop category 0 and 1
- Restart inhibit
- Local acknowledgement
- Enabling switch
6Dynamic code tables guarantee the transmission
of safe data in AS-Interface
Safety-related slave
Safety monitor
Standard PLC andstandard master
AS-i power unit
Master call
Slave response
7AS-Interface Safe guarantees a maximum response
time of 35 ms
8Circuit diagram safety monitor with one enable
circuit
1.13/1.14 1.23/1.24 Enable ciruits 1.32 Signal
circuit 1.Y1 On button optional 1.Y2 Feedback
circuit
9Diagnostics via AS-i
With no address of the Safety-Monitor 0000
means Safety device OFFCode means Safety
device ON Disadvantages- no Monitor failures are
detected - not all Device failures
are detected - no defined reason
given for activation With an ASI address of the
Safety-Monitor The status of the monitor and all
relevant devices can be transfered into the PLC.
A function block for the S7 is available. Advantag
es - detailed diagnostics including monitor
failure, timing error
waiting for start, test neccessary, and slave
address
10LEDs AS-Interface Safety Monitor
Meaning of Colors (1,2,3), Example
L24 V
L
Ready Waiting for Start Test neccessary open,
close door ON all OK Timer active Stopcat.
1 OFF Emergency Stop pressed Fault only one
channel of a two channel device operated
correctly
2.Y1
Siemens
SERVICE
K1
K2
K3
K4
L24 V
M/N
M
11Easy grouping of safety signals with AS-Interface
Safe
Standard-PLC andstandard-master
safety monitor
safety monitor
AS-i power unit
Safe emergency stop button
safemodule
Safe emergency stop button
Safe emergency stop button
12What happens if ...
- ... a slave is defective
- You can take an identical substitute slave. The
safety monitor accepts this as a substitute and
internally adjusts to the new code table. The
safety protocol must be updated. - ... the safety monitor is defective
- The configuration data of the system is stored in
the monitor and if necessary can be directly
transmitted to the new monitor. In addition a
safety check must be carried out, i.e. all safe
components must be actuated and their functioning
checked by a competent person.
13Can you ...
- ... add a safe slave to an existing network?
- Yes! The monitor accepts additional safe slaves.
The safety protocol must then be updated. - ... remove safe slaves from an existing network?
- No! To prevent manipulation this is not possible.
If a safe slave is removed, the safety monitor
switches off and will not switch on again until a
new configuration is down loaded into the monitor
via a PC. - ... run AS-Interface Safe under Version 2.1?
- All components of Safety at Work can be run under
the extended AS-Interface specification Version
2.1. Safe slaves are, however, always single
slaves, as they need a complete AS-Interface
address. A mixed configuration is possible but
you must take into acccount that A and B
addresses eliminate the full address from your
configuration table.
14AS-Interface Safe can be configured quickly and
easily via Drag Drop
- Assignment of the slaves to the output switching
elements - Operating modes can be set
- Mode 1 Stop - Category 0 0
- Mode 2 Stop - Category 0 1
- Mode 3 Stop - Category 0
two-hand operation - Mode 4 Stop - Category 0 door
latching - Downloading of the processed data withpassword
protection - Protection against manipulation of the
configuration data - Protocol of the configuration
- In the case of error, monitoring of the system
status
15Configuration Software
Devices with direct access to the safe output
Available Devices (placeable by drag and drop
to the corresponding column)
Devices with no direct accsess to the safe
output
16Example Configuration of an OR
1
2
5
3
6
4
1-6 configuration sequence
17The AS-Interface Safety concept is recognised by
TÃœV and BIA
BIA Berufsgenossenschaftliches Institut für
ArbeitssicherheitTÃœV Technischer
Ãœberwachungsverein
18AS-Interface Safe offers a wide range of products
- Safety monitor with one or two two-channel enable
circuits - Safe modules for connecting standard sensors
- Emergency Stop button for direct connection
- Position switches for direct connection
- Light barriers for direct connection
- Light grids and light curtains for direct
connection
19Compact Module K 45 F
- 1 safe input with applications of category 3/4
- 2 safe inputs with applications of category 2
- If with applications of category 2 only one input
is used, input 2 must be bridged with a jumper
(MLFB......)
20Compact Module K 60 F
- 2 safe inputs with applications of category 2
- 1 safe input with applications of category 3/4
- If with applications of category 2 only one input
is used, input 2 must be bridged with a jumper
(MLFB......) - In addition there are 2 non-safe standard outputs
21SIGNUM 3SB3AS-Interface Safe
- Direct connection of safety-related switchgear to
standard AS-i - Emergency Stop control device latches
simultaneously (EN418) with the positively driven
opening of the contact elements (EN60947-5-1) - No conventional wiring necessary
- Approved up to category 4 according to EN954-1
22SIGUARD Light Curtains and Light Grids 3RG78 42
AS-Interface Safe
- Safe direct connection to AS-Interface
- Light curtains and light grids type 4 according
to EN, IEC 61496-1, 2 - Category 4 according to EN 954-1
- Light curtains with resolution 14, 30, 50 and 90
mm - 2, 3 and 4-ray light grids
- Protective field heights of 150 to 3000 mm
- Max. distance 0.8 m-18 m(0.3 m-6 m with 14 mm
resolution,60 m for light grids)