ELECTRICAL STUFF FOR MECHANICAL ENGINEERS - PowerPoint PPT Presentation

1 / 31
About This Presentation
Title:

ELECTRICAL STUFF FOR MECHANICAL ENGINEERS

Description:

If available, provide your EE with cut sheets of the equipment that ... over 50 HP and for special equipment, review with your EE. ... Class III: Ignitable ... – PowerPoint PPT presentation

Number of Views:109
Avg rating:3.0/5.0
Slides: 32
Provided by: PAPA56
Category:

less

Transcript and Presenter's Notes

Title: ELECTRICAL STUFF FOR MECHANICAL ENGINEERS


1
ELECTRICAL STUFFFOR MECHANICAL ENGINEERS
2
ELECTRICAL DATA FOR SYSTEM DESIGN
  • FLA vs. MCA
  • VOLTAGE DESIGNATIONS
  • VOLTAGE UTILIZATION
  • VOLTAGE AND PHASE SELECTION
  • FIRE ALARM ELECTRICAL SYSTEM INTERLOCKS
  • MOTOR STARTERS

3
FLA vs. MCA
  • FLA (full load amperes)is the current the devise
    draws when operating under full rated load. This
    is a nameplate rating of a device such as a
    motor.
  • MCA (minimum circuit amperes) is the minimum
    allowable current rating of the circuit serving
    the equipment. This equipment usually has more
    than one device using electrical energy such as a
    heat pump.
  • The MCA is calculated by multiplying the FLA of
    the largest device by 125 and adding the FLA of
    the other devices.

4
EXAMPLE
  • An example would be a heat pump or condenser unit
    with a compressor with a FLA of 16.5A and two
    fans at 1.3A each.
  • MCA16.5X1.251.31.323.3A
  • If available, provide your EE with cut sheets of
    the equipment that lists all of the components
    and the FLA of each device. It will also
    indicate the MCA and which items are 1phase and 3
    phase.

5
VOLTAGE DESIGNATIONS
  • There are basically two voltage designations you
    will encounter the system voltage and the
    equipment voltage rating. The difference is the
    allowance for voltage drop between the electrical
    service delivery or transformer secondary and the
    point of use. But, just to keep everybody
    confused, we still encounter the old obsolete
    voltage designations. The following is a table
    listing the most common voltage designations for
    motor driven equipment. THIS DOES NOT APPLY TO
    RESISTANCE HEATING ELEMENTS. Resistance heating
    elements MUST be rated at system voltage.

6
VOLTAGE TABLES
7
VOLTAGE UTILIZATION
  • Can a 240 v heater be operated at 208 v? Yes
    with a reduction of heat output. A 10 KW, 240
    volt heater operated at 208 volts will only
    provide 8.67 KW worth of heat. Can a 240 v
    heater be operated at 277 v? NO!
  • Can a 240 volt motor be operated at 208 volts?
    No! Will it run? Maybe, but with a shorten life
    expectance and in violation of the NEC.

8
VOLTAGE AND PHASE SELECTION
  • Residential Very Small Commercial
  • 120/240 volts, 1 phase
  • Small Commercial
  • 208Y/120 volts, 3 phase
  • Large Commercial Industrial
  • 480Y/277 volts, 3 phase
  • Very large machinery may require higher voltages.
  • For mechanical equipment rated at ½ HP or 0.5 KW
    it is generally better to serve these devices at
    the higher voltage and 3 phase rather than 1
    phase.
  • Here again, review this with your EE.

9
FIRE ALARM ELECTRICAL SYSTEM INTERLOCKS
  • Depending on the CFM rating of an AHU, Supply Fan
    (2000 CFM), Return Fan or Exhaust Fan (15,000
    CFM), these devices require interlocking with the
    Fire Alarm System to shut down the fans in the
    event the FAS is activated. These fans may also
    require smoke detectors installed within the the
    duct work to both shut down the fan and activate
    the FAS.
  • Kitchen hoods with fire suppression systems will
    require interlocks to de-energize the energy
    sources of all equipment under the hood, both gas
    and electric.

10
MOTOR STARTERS
  • Coordinate with your EE as to who is providing
    motor starters. For motors, 5 to 50 HP and for
    most industrial projects the EE may want to
    provide the motor starters and maybe the motors.
  • For Chillers with reduced inrush starters, it is
    generally a good idea to have the chiller MFG
    provide the starter.
  • For motors over 50 HP and for special equipment,
    review with your EE. The Utility may require
    reduced inrush starters.
  • If starters are provided under HVAC
    specifications, let your EE review the specs.

11
LIGHTING FIXTURES
  • Vented vs Non-Vented
  • Vented fixtures release a large amount of heat
    into the ceiling cavity and less into the room.
    This may be more efficient if the ceiling cavity
    is used as a return air plenum.
  • If a ducted return is used non-vented fixtures
    would not be a good choice.
  • Light-Diffuser coordination, who has the R/W?
  • The Architect!
  • Air handling trofferexpensive and requires more
    coordination.

12
LIGHTING FIXTURES (cont)
  • Interlock With Exhaust Fan
  • In toilets, it is a good idea to interlock the
    light switch with the exhaust fan. Relays are
    available with a time delay that will allow the
    fan to run for a designated period after the
    lights are extinguished.
  • Light fixture-duct work coordination
  • To install a lay-in troffer takes a clearance of
    approx. 1 foot in the ceiling cavity. For large
    ducts in tight ceiling cavities, coordination is
    a must.

13
ELECTRICAL EQUIPMENT
  • Working Clearances
  • Minimum Width 30 or the width of the
    equipment which ever is greater.
  • Minimum Depth 240 or 208 v 3 ft.
  • 480 v 3 1/2 to 4 ft.
  • Dedicated Space
  • No ducts, pipes, etc.to structure above or a
    maximum of 6 ft.

14
Exhibit 110.9
15
Exhibit 110.12 The 30 in. wide front working
space, which is not required to be directly
centered on the electrical equipment if space is
sufficient for safe operation and maintenance of
such equipment
16
Exhibit 110.19 The two distinct indoor
installation spaces required by 110.26(A) and
110.26(F) the working space and the dedicated
electrical space.
17
Exhibit 110.20 The working space in front of a
panelboard required by 110.26(A). This
illustration supplements the dedicated electrical
space shown in Exhibit 110.19.
18
Exhibit 110.21 The dedicated electrical space
above and below a panelboard required by
110.26(F)(1).
19
ELECTRICAL EQUIPMENT (cont)
  • Heat Rejection
  • With the exception of transformers and motor
    controls, the heat rejection from electrical
    equipment is minor. For transformers, the KVA
    rating X Z will give an approx. KW value. Z
    approx 5. MCCs and VFDs are a bit more
    complex due to the varying size of motor starters
    and other factors. Ask your EE.
  • Environment
  • Most electrical equipment and wiring is rated to
    operate in an environment of of 40C (104F).
    Ventilation with office air is usually adequate.

20
NEMA ENCLOSURE DESIGNATION
  • NEMA 1 Enclosures are intended for indoor use
    primarily to provide protection against contact
    with the enclosed equipment or locations where
    unusual service conditions do not exist.
  • NEMA 2 Enclosures are intended for indoor use
    primarily to provide degree of protection against
    limited amounts of falling water and dirt.
  • NEMA 3 Enclosures are intended for outdoor use
    primarily to provide degree of protection against
    windblown dust, rain and sleet. Undamaged by the
    formation of ice on the enclosure.

21
NEMA ENCLOSURE DESIGNATION (cont)
  • NEMA 3R Enclosures are intended for outdoor use
    primarily to provide degree of protection against
    falling rain and sleet. Undamaged by the
    formation of ice on the enclosure.
  • NEMA 4 Enclosures are intended for indoor or
    outdoor use primarily to provide degree of
    protection against windblown dust and rain,
    splashed water and hose directed water.
    Undamaged by the formation of ice on the
    enclosure.
  • NEMA 4X Same as NEMA 4 with corrosion
    resistance. Usually stainless steel.

22
NEMA ENCLOSURE DESIGNATION (cont)
  • NEMA 6 Enclosures are intended for indoor or
    outdoor use where occasional submersion at
    limited depth may occur. Undamaged by the
    formation of ice on the enclosure.
  • NEMA 12 Enclosures are intended for indoor use
    primarily to provide protection against dust,
    falling dirt and dripping non-corrosive liquids.
  • NEMA 13 Enclosures are intended for indoor use
    primarily to provide protection against dust and
    spraying of water, oil and non-corrosive
    coolants.
  • None of these enclosures are explosion proof.

23
EXPLOSION PROOF ENCLOSURES
  • Explosion proof enclosures are designated by
    Class, Division and Group environment.
  • Class I Flammable liquid or gases.
  • Class II Combustible dust.
  • Class III Ignitable fibers or flying.
  • Division I Flammable, combustible or ignitable
    products are normally present.
  • Division II Flammable, combustible or ignitable
    products are normally contained or are only
    present due to abnormal operations.
  • Group A, B, C, D, E, F G based upon the degree
    of flammability, combustibility or ignitability
    of the product.

24
NEMA MOTOR ENCLOSURES
  • OPEN---Motor housing is open with slots. For
    clean dry areas.
  • ODP (Open Drip proof) -- Ventilation openings in
    shield and/or frame prevents drops of liquid from
    falling into motor within up to 15 degree angle
    from vertical. Designed for reasonably dry,
    clean, and well ventilated (usually indoors)
    areas. Outdoors installation require the motor to
    be protected with a cover that does not restrict
    the flow of air to the motor.

25
  • TENV (Totally Enclosed Non-Ventilated)--No
    ventilation openings, enclosed to prevent free
    exchange of air (not airtight). No external
    cooling fan, relies on convection cooling.
    Suitable where the motor is exposed to dirt or
    dampness. Not suited in very moist humid or
    hazardous (explosive) air.
  • TEFC (Totally Enclosed Fan Cooled)--Same as TENV
    with an external fan as an integral part of the
    motor. The fan provides cooling by blowing air on
    the outside of the motor.
  • TEAO (Totally Enclosed Air Over)--Dust-tight fan
    and blower motors for shaft mounted fans or belt
    driven fans. The motors mounted within the
    airflow of the fan.

26
  • Totally Enclosed, Hostile and Severe
    Environment--Designed for use in extreme
    conditions - moist and/or chemical environments.
    Not for hazardous locations.
  • Totally Enclosed Blower Cooled--Same as TEFC with
    external fan on a power supply independent of the
    inverter output. Full cooling even at lower motor
    speeds.
  • Explosion-Proof MotorsSimilar criteria as
    electrical enclosures

27
MOTOR SPEED
  • Calculating Motor Speed
  • To Calculate the speed of a induction motor,
    apply this formula
  • Srpm 120 x F            P
  • Srpm synchronous revolutions per minute.120  
    constantF       supply frequency (in
    cycles/sec)P       number of motor winding
    poles

28
MOTOR SPEED (cont)
  • Example What is the synchronous of a motor
    having 4 poles connected to a 60 hz power supply?
  • Srpm 120 x F            PSrpm 120 x
    60            4Srpm 7200             4Srpm
    1800 rpm

29
MOTOR SPEED (cont)
  • A squirrel cage induction motor is a constant
    speed device. It cannot operate for any length of
    time at speeds below those shown on the nameplate
    without danger of burning out.
  • Variable Frequency Drives (VFD)
  • Specify a motor rated for a VFD.

30
POWER FACTOR
31
MECHANICAL EQUIPMENT DATA
  • Provide the EE with your best guess as to your
    equipment loads ASAP. This lets him establish
    his equipment size and space requirements. Data
    can be revised as you proceed with your design.
  • Likewise the EE should be able to provide you
    with his expected lighting loads in watts/SF by
    areas very early.
Write a Comment
User Comments (0)
About PowerShow.com