Title: ELECTRICAL STUFF FOR MECHANICAL ENGINEERS
1ELECTRICAL STUFFFOR MECHANICAL ENGINEERS
2ELECTRICAL DATA FOR SYSTEM DESIGN
- FLA vs. MCA
- VOLTAGE DESIGNATIONS
- VOLTAGE UTILIZATION
- VOLTAGE AND PHASE SELECTION
- FIRE ALARM ELECTRICAL SYSTEM INTERLOCKS
- MOTOR STARTERS
-
-
3FLA vs. MCA
- FLA (full load amperes)is the current the devise
draws when operating under full rated load. This
is a nameplate rating of a device such as a
motor. - MCA (minimum circuit amperes) is the minimum
allowable current rating of the circuit serving
the equipment. This equipment usually has more
than one device using electrical energy such as a
heat pump. - The MCA is calculated by multiplying the FLA of
the largest device by 125 and adding the FLA of
the other devices.
4EXAMPLE
- An example would be a heat pump or condenser unit
with a compressor with a FLA of 16.5A and two
fans at 1.3A each. - MCA16.5X1.251.31.323.3A
- If available, provide your EE with cut sheets of
the equipment that lists all of the components
and the FLA of each device. It will also
indicate the MCA and which items are 1phase and 3
phase.
5VOLTAGE DESIGNATIONS
- There are basically two voltage designations you
will encounter the system voltage and the
equipment voltage rating. The difference is the
allowance for voltage drop between the electrical
service delivery or transformer secondary and the
point of use. But, just to keep everybody
confused, we still encounter the old obsolete
voltage designations. The following is a table
listing the most common voltage designations for
motor driven equipment. THIS DOES NOT APPLY TO
RESISTANCE HEATING ELEMENTS. Resistance heating
elements MUST be rated at system voltage.
6VOLTAGE TABLES
7VOLTAGE UTILIZATION
- Can a 240 v heater be operated at 208 v? Yes
with a reduction of heat output. A 10 KW, 240
volt heater operated at 208 volts will only
provide 8.67 KW worth of heat. Can a 240 v
heater be operated at 277 v? NO! - Can a 240 volt motor be operated at 208 volts?
No! Will it run? Maybe, but with a shorten life
expectance and in violation of the NEC.
8VOLTAGE AND PHASE SELECTION
- Residential Very Small Commercial
- 120/240 volts, 1 phase
- Small Commercial
- 208Y/120 volts, 3 phase
- Large Commercial Industrial
- 480Y/277 volts, 3 phase
- Very large machinery may require higher voltages.
- For mechanical equipment rated at ½ HP or 0.5 KW
it is generally better to serve these devices at
the higher voltage and 3 phase rather than 1
phase. - Here again, review this with your EE.
9FIRE ALARM ELECTRICAL SYSTEM INTERLOCKS
- Depending on the CFM rating of an AHU, Supply Fan
(2000 CFM), Return Fan or Exhaust Fan (15,000
CFM), these devices require interlocking with the
Fire Alarm System to shut down the fans in the
event the FAS is activated. These fans may also
require smoke detectors installed within the the
duct work to both shut down the fan and activate
the FAS. - Kitchen hoods with fire suppression systems will
require interlocks to de-energize the energy
sources of all equipment under the hood, both gas
and electric.
10MOTOR STARTERS
- Coordinate with your EE as to who is providing
motor starters. For motors, 5 to 50 HP and for
most industrial projects the EE may want to
provide the motor starters and maybe the motors. - For Chillers with reduced inrush starters, it is
generally a good idea to have the chiller MFG
provide the starter. - For motors over 50 HP and for special equipment,
review with your EE. The Utility may require
reduced inrush starters. - If starters are provided under HVAC
specifications, let your EE review the specs.
11LIGHTING FIXTURES
- Vented vs Non-Vented
- Vented fixtures release a large amount of heat
into the ceiling cavity and less into the room.
This may be more efficient if the ceiling cavity
is used as a return air plenum. - If a ducted return is used non-vented fixtures
would not be a good choice. - Light-Diffuser coordination, who has the R/W?
- The Architect!
- Air handling trofferexpensive and requires more
coordination. -
12LIGHTING FIXTURES (cont)
- Interlock With Exhaust Fan
- In toilets, it is a good idea to interlock the
light switch with the exhaust fan. Relays are
available with a time delay that will allow the
fan to run for a designated period after the
lights are extinguished. - Light fixture-duct work coordination
- To install a lay-in troffer takes a clearance of
approx. 1 foot in the ceiling cavity. For large
ducts in tight ceiling cavities, coordination is
a must.
13ELECTRICAL EQUIPMENT
- Working Clearances
- Minimum Width 30 or the width of the
equipment which ever is greater. - Minimum Depth 240 or 208 v 3 ft.
- 480 v 3 1/2 to 4 ft.
- Dedicated Space
- No ducts, pipes, etc.to structure above or a
maximum of 6 ft.
14Exhibit 110.9
15Exhibit 110.12 The 30 in. wide front working
space, which is not required to be directly
centered on the electrical equipment if space is
sufficient for safe operation and maintenance of
such equipment
16Exhibit 110.19 The two distinct indoor
installation spaces required by 110.26(A) and
110.26(F) the working space and the dedicated
electrical space.
17Exhibit 110.20 The working space in front of a
panelboard required by 110.26(A). This
illustration supplements the dedicated electrical
space shown in Exhibit 110.19.
18Exhibit 110.21 The dedicated electrical space
above and below a panelboard required by
110.26(F)(1).
19ELECTRICAL EQUIPMENT (cont)
- Heat Rejection
- With the exception of transformers and motor
controls, the heat rejection from electrical
equipment is minor. For transformers, the KVA
rating X Z will give an approx. KW value. Z
approx 5. MCCs and VFDs are a bit more
complex due to the varying size of motor starters
and other factors. Ask your EE. - Environment
- Most electrical equipment and wiring is rated to
operate in an environment of of 40C (104F).
Ventilation with office air is usually adequate.
20NEMA ENCLOSURE DESIGNATION
- NEMA 1 Enclosures are intended for indoor use
primarily to provide protection against contact
with the enclosed equipment or locations where
unusual service conditions do not exist. - NEMA 2 Enclosures are intended for indoor use
primarily to provide degree of protection against
limited amounts of falling water and dirt. - NEMA 3 Enclosures are intended for outdoor use
primarily to provide degree of protection against
windblown dust, rain and sleet. Undamaged by the
formation of ice on the enclosure.
21NEMA ENCLOSURE DESIGNATION (cont)
- NEMA 3R Enclosures are intended for outdoor use
primarily to provide degree of protection against
falling rain and sleet. Undamaged by the
formation of ice on the enclosure. - NEMA 4 Enclosures are intended for indoor or
outdoor use primarily to provide degree of
protection against windblown dust and rain,
splashed water and hose directed water.
Undamaged by the formation of ice on the
enclosure. - NEMA 4X Same as NEMA 4 with corrosion
resistance. Usually stainless steel.
22NEMA ENCLOSURE DESIGNATION (cont)
- NEMA 6 Enclosures are intended for indoor or
outdoor use where occasional submersion at
limited depth may occur. Undamaged by the
formation of ice on the enclosure. - NEMA 12 Enclosures are intended for indoor use
primarily to provide protection against dust,
falling dirt and dripping non-corrosive liquids. - NEMA 13 Enclosures are intended for indoor use
primarily to provide protection against dust and
spraying of water, oil and non-corrosive
coolants. - None of these enclosures are explosion proof.
23EXPLOSION PROOF ENCLOSURES
- Explosion proof enclosures are designated by
Class, Division and Group environment. - Class I Flammable liquid or gases.
- Class II Combustible dust.
- Class III Ignitable fibers or flying.
- Division I Flammable, combustible or ignitable
products are normally present. - Division II Flammable, combustible or ignitable
products are normally contained or are only
present due to abnormal operations. - Group A, B, C, D, E, F G based upon the degree
of flammability, combustibility or ignitability
of the product.
24NEMA MOTOR ENCLOSURES
- OPEN---Motor housing is open with slots. For
clean dry areas. - ODP (Open Drip proof) -- Ventilation openings in
shield and/or frame prevents drops of liquid from
falling into motor within up to 15 degree angle
from vertical. Designed for reasonably dry,
clean, and well ventilated (usually indoors)
areas. Outdoors installation require the motor to
be protected with a cover that does not restrict
the flow of air to the motor.
25- TENV (Totally Enclosed Non-Ventilated)--No
ventilation openings, enclosed to prevent free
exchange of air (not airtight). No external
cooling fan, relies on convection cooling.
Suitable where the motor is exposed to dirt or
dampness. Not suited in very moist humid or
hazardous (explosive) air. - TEFC (Totally Enclosed Fan Cooled)--Same as TENV
with an external fan as an integral part of the
motor. The fan provides cooling by blowing air on
the outside of the motor. - TEAO (Totally Enclosed Air Over)--Dust-tight fan
and blower motors for shaft mounted fans or belt
driven fans. The motors mounted within the
airflow of the fan.
26- Totally Enclosed, Hostile and Severe
Environment--Designed for use in extreme
conditions - moist and/or chemical environments.
Not for hazardous locations. - Totally Enclosed Blower Cooled--Same as TEFC with
external fan on a power supply independent of the
inverter output. Full cooling even at lower motor
speeds. - Explosion-Proof MotorsSimilar criteria as
electrical enclosures
27MOTOR SPEED
- Calculating Motor Speed
- To Calculate the speed of a induction motor,
apply this formula - Srpm 120 x F P
- Srpm synchronous revolutions per minute.120
constantF supply frequency (in
cycles/sec)P number of motor winding
poles
28MOTOR SPEED (cont)
- Example What is the synchronous of a motor
having 4 poles connected to a 60 hz power supply? - Srpm 120 x F PSrpm 120 x
60 4Srpm 7200 4Srpm
1800 rpm
29MOTOR SPEED (cont)
- A squirrel cage induction motor is a constant
speed device. It cannot operate for any length of
time at speeds below those shown on the nameplate
without danger of burning out. - Variable Frequency Drives (VFD)
- Specify a motor rated for a VFD.
30POWER FACTOR
31MECHANICAL EQUIPMENT DATA
- Provide the EE with your best guess as to your
equipment loads ASAP. This lets him establish
his equipment size and space requirements. Data
can be revised as you proceed with your design. - Likewise the EE should be able to provide you
with his expected lighting loads in watts/SF by
areas very early.