Title: Resident Physics Lectures
1Resident Physics Lectures
- Christensen, Chapter 2B
- Tube Ratings
George David Associate Professor Department of
Radiology Medical College of Georgia
2Heat Units
- A unit of energy
- Single Phase Definition
- Kilovoltage X tube current X exposure time
- kVp X mA X sec
- Three Phase (constant potential/high frequency)
Definition - 1.35 X Kilovoltage X tube current X exposure time
- 1.35 X kVp X mA X sec
3Heat Units
Heat Units
Single Phase Exposure
- 70 kVp
- 200 mA
- 0.25 second
- 70 X 200 X 0.25 3500 heat units
?
4Heat Units
Heat Units
Three Phase Exposure
- 60 X 100 X 0.1 X 1.35 810 heat units
?
5Heat is the Enemy
X-Ray Tube
Heat
6Tube Rating Chart
- Indicates load limit tube can safely accept
- Based upon
- Tube construction
- High VoltageWaveform
7Tube, Target, Ratings
- surface area bombarded by electrons
- focal spot size (actual)
- target angle
- anode diameter
- Melting point
- Heat transfer
- Anode rotation speed
8Tube Rating Charts
- single exposure
- multiple rapid exposure (angiographic) capability
9Single Exposure Rating Charts
- Tube specific
- Incorporated in virtually all generators
- prevents illegal single exposures
- Better ratings (more heat allowed) for
- Large focal spot
- High speed anode rotation
10Typical Single-Exposure Tube Rating Chart
- shows maximum exposure time for single exposure
at given kV mA
11Example
- What is the maximum exposure time at 90 kVp 300
mA?
12Example
- What is the maximum exposure time at 120 kVp
400 mA?
Cant do 120 kVp at 400 mA for any exposure time.
?
13Single Exposure Rating Charts
- Actually 8 charts combining
- generator
- single phase (1F)
- three phase (3F)
- focal spot
- small
- large
- anode speed
- standard (3400 rpm)
- high (9600 rpm)
1FSFS3400 RPM
3FSFS3400 RPM
1FLFS3400 RPM
3FLFS3400 RPM
1FSFS9600 RPM
3FSFS9600 RPM
1FLFS9600 RPM
3FLFS9600 RPM
14On-Board Tube Rating Charts
- Checks to see if legal exposure at low-speed
rotation. - Automatically switches to high speed anode
rotation as needed - Locks out illegal exposures
Safe at3400rpm?
Safe at9600rpm?
No
No
No ExposureAllowed
Yes
Yes
Allow 3400 rpm Exposure
Allow 9600 rpm Exposure
15Kilowatt Rating
- Ability of x-ray tube to make single exposure of
reasonable duration (usually .1 sec.) - Found on tube rating chart
- standard assumptions
- Use 0.1 sec. exposure time
- Three phase chart
- high speed rotor rotation
16Kilowatt Rating (cont.)
- Units
- 1 watt 1 volt X 1 amp
- 1 watt 1 kilovolt X 1 mA
- 1 kilowatt (kW) 1 kilovolt X 1 mA / 1000
- kW rating for a standard 0.1 sec exposure
- kW rating kVp X mA / 1000
- use maximum mA at given kVp _at_ .1 sec
17Kilowatt Rating (cont.)
- 100 kVp exposure usually used
- For a 100 kVp, .1 sec exposure
- kW rating mA / 10
- Use maximum mA at 100 kVp, .1 sec.
- Each focal spot has its own kW rating
X
Interpolate!
32 kW
18Anode Thermal Characteristics Chart
- 2 charts in one
- cooling curve in absence of heating
- anode heating
- for continuous heat input (fluoroscopy)
19Continuous Heating - Fluoroscopy
- Fluoro almostalways single phase
-
- Find appropriate curve
- HU/sec kVp X mA
- Follow from current heat to right for fluoro time
20Continuous Heating - Fluoroscopy
- Technique
- 100 kVp
- 6 mA
- 600 HU/sec
- Start with50,000 HU
- Fluoro for3 minutes
105,000 HU
x
x
3 minutes
21Cooling
- Start on cooling curve with current heat units
- 110,000 for this example
- Cool for2 minutes
x
x
40,000 HU
x
2 minutes
22Angiographic Rating Chart
- Provides maximum heat units per exposure for
given of - exposures per second
- total exposures
Total of Exposures
Exposurespersecond
Maximum Load in Peak kV X mA X sec.
23Example
- How many total exposures can be done at
- 90 kVp
- 100 mAs
- 3 frames / sec.
90 X 100 9000 (Maximum Load)
Total of Exposures
13
Exposurespersecond
Maximum Load in Peak kV X mA X sec.
24Tube Rating Considerations
- ability of tube to withstand multiple exposures
during several hours of heavy use depends upon - anode storage / cooling curves
- housing storage / cooling curves
- housing cooling can be improved with
- fans
- oil / water circulators
25Tube Damage
Warning
26Anode Damage
- heat capacity exceeded
- melted spots on anode
- thermal shock (high mA on cold anode)
- can cause cracks in anode (tube death)
27Protecting the Anode
- Tube warm-up
- Eliminates thermal shock from high mA exposures
on cold anode - Warm-up needed whenever tube cold
- once in the morning not sufficient if tube not
used for several hours
28High Voltage Arcs
- electrons move from filament to tube housing
instead of to anode - can be caused by filament evaporation
- deposition of filament on glass envelope as
result of - high filament currents
- long filament boost time
- reduce by not holding first trigger longer than
needed - very short exposure with instantaneously very
high mA - Generator often drops off line
29Tube Insert Damage
- Bearing Damage
- prevents proper rotation of anode
- anode can run too slow
- anode can stop
- results in thermal damage to anode (melted
spots) - Filament break
- renders one focal spot completely inoperative
30Reducing Tube Wear Lower mA
80 kVp 500 mA, 0.1 sec
80 kVp 100 mA, 0.5 sec
or
- Both exposure are 50 mAs
- Same radiation to image receptor
- Same dose to patient
Dont smoke that tube
31Reducing Tube Wear Lower mA
80 kVp 500 mA, 0.1 sec
80 kVp 100 mA, 0.5 sec
or
- Low mA reduces tube wear
- filament temperatures lower
- reduces filament evaporation
Dont smoke that tube
32Reducing Tube Wear Lower mA
80 kVp 500 mA, 0.1 sec
80 kVp 100 mA, 0.5 sec
or
- use lowest mA (and largest focal spot) consistent
with patient motion considerations - Large focal spot allows higher mA to be used
Dont smoke that tube
33Reducing Tube Wear Raise kVp
70 kVp 100 mAs
90 kVp 40 mAs
or
- High kVp exposures require less heat units for
same film density - higher kVp more penetrating
- High kVp also reduces patient exposure
- More penetrating beam
- BUT higher kVp reduces contrast
- Use highest kVp consistent with required contrast
Dont smoke that tube
34Reducing Tube Wear
- Reduce use of high speed anode rotation
- use longer times instead of higher kV and/or mA
- High speed rotation greatly increases bearing
wear - generators automatically select high speed for
high combinations of kV mA - BUT longer exposure times
- increase exposure time patient motion
- use lowest mA consistent with patient motion
considerations
Dont smoke that tube
35Reducing Tube Wear
- Reduce first trigger holding time
- Reduces bearing wear
- Reduces tube rotation time
- Reduces filament evaporation
- filament evaporation can lead to tube arcing
- Holding first trigger sometimes necessary
- synchronizing breathing for children
Dont smoke that tube
36Oil Leaks
- May be accompanied by air bubble in housing
- Eventually causes high voltage arcing
- Requires immediate service attention