Resident Physics Lectures - PowerPoint PPT Presentation

1 / 36
About This Presentation
Title:

Resident Physics Lectures

Description:

Kilovoltage X tube current X exposure time. kVp X mA X sec. Three Phase (constant potential ... 1.35 X Kilovoltage X tube current X exposure time. 1.35 X ... – PowerPoint PPT presentation

Number of Views:193
Avg rating:3.0/5.0
Slides: 37
Provided by: george45
Category:

less

Transcript and Presenter's Notes

Title: Resident Physics Lectures


1
Resident Physics Lectures
  • Christensen, Chapter 2B
  • Tube Ratings

George David Associate Professor Department of
Radiology Medical College of Georgia
2
Heat Units
  • A unit of energy
  • Single Phase Definition
  • Kilovoltage X tube current X exposure time
  • kVp X mA X sec
  • Three Phase (constant potential/high frequency)
    Definition
  • 1.35 X Kilovoltage X tube current X exposure time
  • 1.35 X kVp X mA X sec

3
Heat Units
Heat Units
Single Phase Exposure
  • 70 kVp
  • 200 mA
  • 0.25 second
  • 70 X 200 X 0.25 3500 heat units

?
4
Heat Units
Heat Units
Three Phase Exposure
  • 60 kVp
  • 100 mA
  • 0.1 second
  • 60 X 100 X 0.1 X 1.35 810 heat units

?
5
Heat is the Enemy
X-Ray Tube
Heat
6
Tube Rating Chart
  • Indicates load limit tube can safely accept
  • Based upon
  • Tube construction
  • High VoltageWaveform

7
Tube, Target, Ratings
  • surface area bombarded by electrons
  • focal spot size (actual)
  • target angle
  • anode diameter
  • Melting point
  • Heat transfer
  • Anode rotation speed

8
Tube Rating Charts
  • single exposure
  • multiple rapid exposure (angiographic) capability

9
Single Exposure Rating Charts
  • Tube specific
  • Incorporated in virtually all generators
  • prevents illegal single exposures
  • Better ratings (more heat allowed) for
  • Large focal spot
  • High speed anode rotation

10
Typical Single-Exposure Tube Rating Chart
  • shows maximum exposure time for single exposure
    at given kV mA

11
Example
  • What is the maximum exposure time at 90 kVp 300
    mA?

12
Example
  • What is the maximum exposure time at 120 kVp
    400 mA?

Cant do 120 kVp at 400 mA for any exposure time.
?
13
Single Exposure Rating Charts
  • Actually 8 charts combining
  • generator
  • single phase (1F)
  • three phase (3F)
  • focal spot
  • small
  • large
  • anode speed
  • standard (3400 rpm)
  • high (9600 rpm)

1FSFS3400 RPM
3FSFS3400 RPM
1FLFS3400 RPM
3FLFS3400 RPM
1FSFS9600 RPM
3FSFS9600 RPM
1FLFS9600 RPM
3FLFS9600 RPM
14
On-Board Tube Rating Charts
  • Checks to see if legal exposure at low-speed
    rotation.
  • Automatically switches to high speed anode
    rotation as needed
  • Locks out illegal exposures

Safe at3400rpm?
Safe at9600rpm?
No
No
No ExposureAllowed
Yes
Yes
Allow 3400 rpm Exposure
Allow 9600 rpm Exposure
15
Kilowatt Rating
  • Ability of x-ray tube to make single exposure of
    reasonable duration (usually .1 sec.)
  • Found on tube rating chart
  • standard assumptions
  • Use 0.1 sec. exposure time
  • Three phase chart
  • high speed rotor rotation

16
Kilowatt Rating (cont.)
  • Units
  • 1 watt 1 volt X 1 amp
  • 1 watt 1 kilovolt X 1 mA
  • 1 kilowatt (kW) 1 kilovolt X 1 mA / 1000
  • kW rating for a standard 0.1 sec exposure
  • kW rating kVp X mA / 1000
  • use maximum mA at given kVp _at_ .1 sec

17
Kilowatt Rating (cont.)
  • 100 kVp exposure usually used
  • For a 100 kVp, .1 sec exposure
  • kW rating mA / 10
  • Use maximum mA at 100 kVp, .1 sec.
  • Each focal spot has its own kW rating

X
Interpolate!
32 kW
18
Anode Thermal Characteristics Chart
  • 2 charts in one
  • cooling curve in absence of heating
  • anode heating
  • for continuous heat input (fluoroscopy)

19
Continuous Heating - Fluoroscopy
  • Fluoro almostalways single phase
  • Find appropriate curve
  • HU/sec kVp X mA
  • Follow from current heat to right for fluoro time

20
Continuous Heating - Fluoroscopy
  • Technique
  • 100 kVp
  • 6 mA
  • 600 HU/sec
  • Start with50,000 HU
  • Fluoro for3 minutes

105,000 HU
x
x
3 minutes
21
Cooling
  • Start on cooling curve with current heat units
  • 110,000 for this example
  • Cool for2 minutes

x
x
40,000 HU
x
2 minutes
22
Angiographic Rating Chart
  • Provides maximum heat units per exposure for
    given of
  • exposures per second
  • total exposures

Total of Exposures
Exposurespersecond
Maximum Load in Peak kV X mA X sec.
23
Example
  • How many total exposures can be done at
  • 90 kVp
  • 100 mAs
  • 3 frames / sec.

90 X 100 9000 (Maximum Load)
Total of Exposures
13
Exposurespersecond
Maximum Load in Peak kV X mA X sec.
24
Tube Rating Considerations
  • ability of tube to withstand multiple exposures
    during several hours of heavy use depends upon
  • anode storage / cooling curves
  • housing storage / cooling curves
  • housing cooling can be improved with
  • fans
  • oil / water circulators

25
Tube Damage
Warning
26
Anode Damage
  • heat capacity exceeded
  • melted spots on anode
  • thermal shock (high mA on cold anode)
  • can cause cracks in anode (tube death)

27
Protecting the Anode
  • Tube warm-up
  • Eliminates thermal shock from high mA exposures
    on cold anode
  • Warm-up needed whenever tube cold
  • once in the morning not sufficient if tube not
    used for several hours

28
High Voltage Arcs
  • electrons move from filament to tube housing
    instead of to anode
  • can be caused by filament evaporation
  • deposition of filament on glass envelope as
    result of
  • high filament currents
  • long filament boost time
  • reduce by not holding first trigger longer than
    needed
  • very short exposure with instantaneously very
    high mA
  • Generator often drops off line

29
Tube Insert Damage
  • Bearing Damage
  • prevents proper rotation of anode
  • anode can run too slow
  • anode can stop
  • results in thermal damage to anode (melted
    spots)
  • Filament break
  • renders one focal spot completely inoperative

30
Reducing Tube Wear Lower mA
80 kVp 500 mA, 0.1 sec
80 kVp 100 mA, 0.5 sec
or
  • Both exposure are 50 mAs
  • Same radiation to image receptor
  • Same dose to patient

Dont smoke that tube
31
Reducing Tube Wear Lower mA
80 kVp 500 mA, 0.1 sec
80 kVp 100 mA, 0.5 sec
or
  • Low mA reduces tube wear
  • filament temperatures lower
  • reduces filament evaporation

Dont smoke that tube
32
Reducing Tube Wear Lower mA
80 kVp 500 mA, 0.1 sec
80 kVp 100 mA, 0.5 sec
or
  • use lowest mA (and largest focal spot) consistent
    with patient motion considerations
  • Large focal spot allows higher mA to be used

Dont smoke that tube
33
Reducing Tube Wear Raise kVp
70 kVp 100 mAs
90 kVp 40 mAs
or
  • High kVp exposures require less heat units for
    same film density
  • higher kVp more penetrating
  • High kVp also reduces patient exposure
  • More penetrating beam
  • BUT higher kVp reduces contrast
  • Use highest kVp consistent with required contrast

Dont smoke that tube
34
Reducing Tube Wear
  • Reduce use of high speed anode rotation
  • use longer times instead of higher kV and/or mA
  • High speed rotation greatly increases bearing
    wear
  • generators automatically select high speed for
    high combinations of kV mA
  • BUT longer exposure times
  • increase exposure time patient motion
  • use lowest mA consistent with patient motion
    considerations

Dont smoke that tube
35
Reducing Tube Wear
  • Reduce first trigger holding time
  • Reduces bearing wear
  • Reduces tube rotation time
  • Reduces filament evaporation
  • filament evaporation can lead to tube arcing
  • Holding first trigger sometimes necessary
  • synchronizing breathing for children

Dont smoke that tube
36
Oil Leaks
  • May be accompanied by air bubble in housing
  • Eventually causes high voltage arcing
  • Requires immediate service attention
Write a Comment
User Comments (0)
About PowerShow.com