Title: How the Power Grid Behaves
1How the Power Grid Behaves
- Tom Overbye
- Department of Electrical and Computer Engineering
- University of Illinois at Urbana-Champaign
2Presentation Overview
- Goal is to demonstrate operation of large scale
power grid. - Emphasis on the impact of the transmission syste.
- Introduce basic power flow concepts through small
system examples. - Finish with simulation of Eastern U.S. System.
3PowerWorld Simulator
- PowerWorld Simulator is an interactive, Windows
based simulation program, originally designed at
University of Illinois for teaching basics of
power system operations to non-power engineers. - PowerWorld Simulator can now study systems of
just about any size.
4Eastern Interconnect Operating Areas
Ovals represent operating areas
Arrows indicate power flow in MW between areas
5Zoomed View of Midwest
6Power System Basics
- All power systems have three major components
Generation, Load and Transmission. - Generation Creates electric power.
- Load Consumes electric power.
- Transmission Transmits electric power from
generation to load.
7One-line Diagram
- Most power systems are balanced three phase
systems. - A balanced three phase system can be modeled as a
single (or one) line. - One-lines show the major power system components,
such as generators, loads, transmission lines. - Components join together at a bus.
8Eastern North American High Voltage Transmission
Grid
Figure shows transmission lines at 345 kV or
above in Eastern U.S.
9Zoomed View of Midwest
Arrows indicate MW flow on the lines piecharts
show percentage loading of lines
10Example Three Bus System
Pie charts show percentage loading of lines
Generator
Load
Bus
Circuit Breaker
11Generation
- Large plants predominate, with sizes up to about
1500 MW. - Coal is most common source, followed by hydro,
nuclear and gas. - Gas is now most economical.
- Generated at about 20 kV.
12Loads
- Can range in size from less than a single watt to
10s of MW. - Loads are usually aggregated.
- The aggregate load changes with time, with strong
daily, weekly and seasonal cycles.
13Transmission
- Goal is to move electric power from generation to
load with as low of losses and cost as possible. - P V I or P/V I
- Losses are I2 R
- Less losses at higher voltages, but more costly
to construct and insulate.
14Transmission and Distribution
- Typical high voltage transmission voltages are
500, 345, 230, 161, 138 and 69 kV. - Transmission tends to be a grid system, so each
bus is supplied from two or more directions. - Lower voltage lines are used for distribution,
with a typical voltage of 12.4 kV. - Distribution systems tend to be radial.
- Transformers are used to change the voltage.
15Other One-line Objects
- Circuit Breakers - Used to open/close devices
red is closed, green is open. - Pie Charts - Show percentage loading of
transmission lines. - Up/down arrows - Used to control devices.
- Values - Show current values for different
quantities.
16Power Balance Constraints
- Power flow refers to how the power is moving
through the system. - At all times the total power flowing into any bus
MUST be zero! - This is know as Kirchhoffs law. And it can not
be repealed or modified. - Power is lost in the transmission system.
17Basic Power Control
- Opening a circuit breaker causes the power flow
to instantaneously(nearly) change. - No other way to directly control power flow in a
transmission line. - By changing generation we can indirectly change
this flow.
18Flow Redistribution Following Opening Line
Circuit Breaker
No flow on open line
Power Balance must be satisfied at each bus
19Indirect Control of Line Flow
Generator change indirectly changes line flow
Generator MW output changed
20Transmission Line Limits
- Power flow in transmission line is limited by a
number of considerations. - Losses (I2 R) can heat up the line, causing it to
sag. This gives line an upper thermal limit. - Thermal limits depend upon ambient conditions.
Many utilities use winter/summer limits.
21Overloaded Transmission Line
Thermal limit of 150 MVA
22Interconnected Operation
- Power systems are interconnected across large
distances. For example most of North American
east of the Rockies is one system, with most of
Texas and Quebec being major exceptions - Individual utilities only own and operate a small
portion of the system, which is referred to an
operating area (or an area).
23Operating Areas
- Areas constitute a structure imposed on grid.
- Transmission lines that join two areas are known
as tie-lines. - The net power out of an area is the sum of the
flow on its tie-lines. - The flow out of an area is equal to total gen -
total load - total losses tie-flow
24Three Bus System Split into Two Areas
Initially area flow is not controlled
Net tie flow is NOT zero
25Area Control Error (ACE)
- The area control error mostly the difference
between the actual flow out of area, and
scheduled flow. - ACE also includes a frequency component.
- Ideally the ACE should always be zero.
- Because the load is constantly changing, each
utility must constantly change its generation to
chase the ACE.
26Home Area ACE
ACE changes with time
27Inadvertent Interchange
- ACE can never be held exactly at zero.
- Integrating the ACE gives the inadvertent
interchange, expressed in MWh. - Utilities keep track of this value. If it gets
sufficiently negative they will pay back the
accumulated energy. - In extreme cases inadvertent energy is purchased
at a negotiated price.
28Automatic Generation Control
- Most utilities use automatic generation control
(AGC) to automatically change their generation to
keep their ACE close to zero. - Usually the utility control center calculates ACE
based upon tie-line flows then the AGC module
sends control signals out to the generators every
couple seconds.
29Three Bus Case on AGC
With AGC on, net tie flow is zero,
but individual line flows are not zero
30Generator Costs
- There are many fixed and variable costs
associated with power system operation. - Generation is major variable cost.
- For some types of units (such as hydro and
nuclear) it is difficult to quantify. - For thermal units it is much easier. There are
four major curves, each expressing a quantity as
a function of the MW output of the unit.
31Generator Cost Curves
- Input-output (IO) curve Shows relationship
between MW output and energy input in Mbtu/hr. - Fuel-cost curve Input-output curve scaled by a
fuel cost expressed in / Mbtu. - Heat-rate curve shows relationship between MW
output and energy input (Mbtu / MWhr). - Incremental (marginal) cost curve shows the cost
to produce the next MWhr.
32Example Generator Fuel-Cost Curve
Y-axis tells cost to produce specified power (MW)
in /hr
Current generator operating point
33Example Generator Marginal Cost Curve
Y-axis tells marginal cost to produce one more
MWhr in /MWhr
Current generator operating point
34Economic Dispatch
- Economic dispatch (ED) determines the least cost
dispatch of generation for an area. - For a lossless system, the ED occurs when all the
generators have equal marginal costs. IC1(PG,1)
IC2(PG,2) ICm(PG,m)
35Power Transactions
- Power transactions are contracts between areas to
do power transactions. - Contracts can be for any amount of time at any
price for any amount of power. - Scheduled power transactions are implemented by
modifying the area ACEACE Pactual,tie-flow -
Psched
36Implementation of 100 MW Transaction
Overloaded line
Net tie flow is now 100 MW from left to right
Scheduled Transaction
37Security Constrained ED
- Transmission constraints often limit system
economics. - Such limits required a constrained dispatch in
order to maintain system security. - In three bus case the generation at bus 3 must be
constrained to avoid overloading the line from
bus 2 to bus 3.
38Security Constrained Dispatch
Gens 2 3 changed to remove overload
Net tie flow is still 100 MW from left to right
39Multi-Area Operation
- The electrons are not concerned with area
boundaries. Actual power flows through the
entire network according to impedance of the
transmission lines. - If Areas have direct interconnections, then they
can directly transact up their tie-line capacity. - Flow through other areas is known as parallel
path or loop flows.
40Seven Bus, Thee Area Case One-line
Area Top has 5 buses
ACE for each area is zero
Area Left has one bus
Area Right has one bus
41Seven Bus Case Area View
Actual flow between areas
Scheduled flow between areas
42Seven Bus Case with 100 MW Transfer
Losses went up from 7.09 MW
100 MW Scheduled Transfer from Left to Right
43Seven Bus Case One-line
Transfer also overloads line in Top
44Transmission Service
- FERC Order No. 888 requires utilities provide
non-discriminatory open transmission access
through tariffs of general applicability. - FERC Order No. 889 requires transmission
providers set up OASIS (Open Access Same-Time
Information System) to show available
transmission.
45Transmission Service
- If areas (or pools) are not directly
interconnected, they must first obtain a
contiguous contract path. - This is NOT a physical requirement.
- Utilities on the contract path are compensated
for wheeling the power.
46Eastern Interconnect Example
Arrows indicate the basecase flow between areas
47Power Transfer Distribution Factors (PTDFs)
- PTDFs are used to show how a particular
transaction will affect the system. - Power transfers through the system according to
the impedances of the lines, without respect to
ownership. - All transmission players in network could be
impacted, to a greater or lesser extent.
48PTDFs for Transfer from Wisconsin Electric to TVA
Piecharts indicate percentage of transfer that
will flow between specified areas
49PTDF for Transfer from WE to TVA
100 of transfer leaves Wisconsin Electric (WE)
50PTDFs for Transfer from WE to TVA
About 100 of transfer arrives at TVA
But flow does NOT follow contract path
51Contingencies
- Contingencies are the unexpected loss of a
significant device, such as a transmission line
or a generator. - No power system can survive a large number of
contingencies. - First contingency refers to loss of any one
device. - Contingencies can have major impact on Power
Transfer Distribution Factors (PTDFs).
52Available Transfer Capability
- Determines the amount of transmission capability
available to transfer power from point A to point
B without causing any overloads in basecase and
first contingencies. - Depends upon assumed system loading, transmission
configuration and existing transactions.
53Reactive Power
- Reactive power is supplied by
- generators
- capacitors
- transmission lines
- loads
- Reactive power is consumed by
- loads
- transmission lines and transformers (very high
losses
54Reactive Power
- Reactive power doesnt travel well - must be
supplied locally. - Reactive must also satisfy Kirchhoffs law -
total reactive power into a bus MUST be zero.
55Reactive Power Example
Reactive power must also sum to zero at each bus
Note reactive line losses are about 13 Mvar
56Voltage Magnitude
- Power systems must supply electric power within a
narrow voltage range, typically with 5 of a
nominal value. - For example, wall outlet should supply 120
volts, with an acceptable range from 114 to 126
volts. - Voltage regulation is a vital part of system
operations.
57Reactive Power and Voltage
- Reactive power and voltage magnitude are tightly
coupled. - Greater reactive demand decreases the bus
voltage, while reactive generation increases the
bus voltage.
58Voltage Regulation
- A number of different types of devices
participate in system voltage regulation - generators reactive power output is
automatically changed to keep terminal voltage
within range. - capacitors switched either manually or
automatically to keep the voltage within a range.
- Load-tap-changing (LTC) transformers vary their
off-nominal tap ratio to keep a voltage within a
specified range.
59Five Bus Reactive Power Example
Voltage magnitude is controlled by capacitor
LTC Transformer is controlling load voltage
60Voltage Control
- Voltage control is necessary to keep system
voltages within an acceptable range. - Because reactive power does not travel well, it
would be difficult for it to be supplied by a
third party. - It is very difficult to assign reactive power and
voltage control to particular transactions.
61Conclusion
- Talk has provided brief overview of how power
grid operates. - Educational Version of PowerWorld Simulator,
capable of solving systems with up to 12 buses,
can be downloaded for free at - www.powerworld.com
- 60,000 bus commercial version is also available.