Power Quality Impacts of Distributed Generation - PowerPoint PPT Presentation

1 / 38
About This Presentation
Title:

Power Quality Impacts of Distributed Generation

Description:

Renewed interest in Grid-connected DG. Utility Perspective. T & D ... CHP and Improved Reliability. Incentives from Utility. Commercial ... Fuse blows. or ... – PowerPoint PPT presentation

Number of Views:1518
Avg rating:3.0/5.0
Slides: 39
Provided by: roger160
Category:

less

Transcript and Presenter's Notes

Title: Power Quality Impacts of Distributed Generation


1
Power Quality Impacts of Distributed Generation
  • Roger C. DuganSr. Consultant
  • Electrotek Concepts, Inc.
  • Tennessee Tech.
  • February 9, 2004

2
Introduction
  • Renewed interest in Grid-connected DG
  • Utility Perspective
  • T D Capacity Relief
  • Hedge against high market prices
  • End User Perspective
  • CHP and Improved Reliability
  • Incentives from Utility
  • Commercial Power Producer
  • Sell kWh or ancillary services

3
Emphasis of This Presentation
  • Units connected to distribution (MV)
  • Typically lt 10 MW
  • Commonly 1-2 MW
  • Frequently owned by end user
  • Impact of these units on Power Quality
  • Operating conflicts
  • We will look at a few of the many

4
OverCurrent Protection Conflicts
5
Typical Overcurrent Protection
6
Only One Device Has to Operate
OperatingDevice
Fault Current
7
Transmission Fault Protection
Multiple Sources
Two Devices Must Operate to Clear Fault
8
LV Network Systems
9
Utility Fault Clearing
  • Due to cost, distribution systems are designed
    expecting only one source of fault current
  • Only one device has to operate
  • DG must disconnect to allow utility fault
    clearing process to continue
  • This is the source of most operating conflicts

10
Reduction of Reach
Utility relays and DG relays may not know
anything is wrong.
11
Reduction of Reach
  • More of a problem at peak load
  • When peaking units are likely to be connected !!
  • More of a problem for high resistance faults
  • Longer fault detection times

12
Instantaneous Reclosing
13
Reclosing
  • Most faults are temporary
  • Reclosing is prevalent in North America
  • Reclosing Interval 0.2 5 sec
  • Instantaneous lt 30 cycles

14
Reclosing, contd
  • If DG does not get off, two bad things could
    happen
  • DG is damaged by the reclose
  • Shafts
  • Winding damage
  • Fault is not cleared
  • Reduced reliability
  • Damage to utility system

15
Reclosing
DG Must Disconnect Here
16
Instantaneous Reclosing
  • Utilities use this for PQ concerns
  • Increases the probability that DG will not
    disconnect in time
  • Makes it almost a certainty that some wont
  • If 1-2 sec, most operations will be easily
    detected by DG protection
  • Some utilities use 5 sec reclose on feeders with
    DG

17
Unintended Consequences ...
18
Voltage Drop After Fault
OOPS!
19
Low Voltage After Interruption
  • A problem when there is a fault at peak loading
  • When peaking DG is likely to be on !!
  • This is often the most limiting condition for how
    much DG can be accommodated without change
  • Particularly on rural feeders
  • 500 1000 kW

20
Ferroresonance
  • Sometimes Conflicting Interconnect Requirements
    Collide

21
Ferroresonance
DG Required to have separate Transformer and
disconnect at first sign of trouble
G
2) DG breaker detects negative sequence and trips
leaving transformer isolated on cable capacitance
with no load/generation
1) Fuse blows or switch opens
3) Ferroresonance develops
22
Ferroresonance
23
Ferroresonance Waveform
24
Reduced Insulation
25
Arrester Duty for SLG
26
Varying Generation
27
Varying Generation Example
10 000 ft
10 000 ft
20 000 ft
Regulator
115 kV
12.47 kV
500 kW
1000 kW
600 kvar
Wind Gen
336 MCM ACSR
8 MW
(Untransposed)
Unbalanced impedances
Rapidly-varying load
28
Varying Generation
1-Phase Regulators
Regulator Operations
29
Transformer Connection and Ground Faults
30
Grd Wye-Delta Connection
  • Some claim this is the best way to interconnect
    DG
  • Same way as nearly all central station generation
    is connected
  • However, most utilities dont allow this
    connection on their system.

31
Wye-Delta Connection
32
Problems with Wye-Delta
  • Increases ground fault current
  • Interferes with coordination
  • Faulted Circuit Indicators get fooled
  • Transformer subject to failure
  • Special design and/or neutral reactor
  • Utilities often discourage Specials

33
On Wye-Wye
  • Most common U.S. connection
  • Generally well behaved
  • Does not block Triplen Harmonics
  • Leads to Harmonic Surprise when many machines
    paralleled with utility system
  • Also occurs with Delta-Wye
  • 2/3 pitch machines lessens the impact

34
Conclusions
  • Interconnected DG likely to increase
  • DG must adapt to Distribution protection system
  • Too much infrastructure already in place to
    overhaul the system to better accommodate DG
  • Who would pay for it? Non-participating
    ratepayers?

35
Conclusions
  • DG impact on Power Quality
  • Often good for individual end users
  • Largest gainers Those with high-value product
    that suffer sustained interruptions
  • But, should not expect power quality improvement
    in all areas
  • Maybe slightly negative for utility
  • Contributes to operating conflicts
  • Can we see it in the Average indices?

36
Conclusions, contd
  • Revisit Overcurrent Protection
  • Utilities may have to change some practices
  • Instantaneous reclosing ?
  • Use of line fuses
  • Tradeoffs for Transformer Connections
  • WYE-Delta good for DG but not for ground fault
    coordination
  • Special engineering reqd for some DG application.

37
Despite These Conflicts
  • DG can almost always be successfully engineered
  • Larger conflict may be over who pays
  • Some long-standing utility practices may have to
    be changed

38
How Much DG ?
  • What is the No Changes Penetration Limit ?
  • Typical 15 of feeder capacity
  • 5 - 10 if Rural
Write a Comment
User Comments (0)
About PowerShow.com