Title: Objectives
1Objectives
- To be able to properly deploy radon and radon
decay product measurement devices. - To be able to interpret the results of radon and
radon decay product measurement devices in
determining the need for mitigation. - To be able to assess the quality and confidence
of radon measurements.
2- A mitigator must be able to determine if the
initial radon measurement were conducted in
accordance with IDNS Measurement Protocols. They
are required by law to report any possible
non-compliance issues to the IDNS.
3MEASUREMENT PROTOCOLS IDNS
- Measurement location
- Short Term or long-term measurement shall be made
in EACH lowest structural area suitable for
occupancy.(Example split-level building with
basement, slab-on-grade room and a room over a
crawl space shall have measurements made in all
of the above.
4MEASUREMENT PROTOCOLSIDNS
- Measurements SHALL be made in rooms that are
regularly used, such as family rooms, living
rooms, dens, playrooms and bedrooms. - Charcoal canisters of any type SHALL not be
placed in bathrooms, kitchens, laundry rooms, spa
rooms or other areas of high humidity. - Radon in air measurements SHALL be made
concurrently with or prior to any diagnostic
radon in water measurements.
5MEASUREMENT PROTOCOLSIDNS
- MEASUREMENT DEVICES SHALL BE
- Undisturbed during the test period
- At least three feet from doors, windows to the
outside, or ventilation ducts, and out of the
direct flow of air from ventilation ducts. - At least one foot from exterior walls.
- At least 20 inches to six feet from the floor.
Some devices can be suspended from the ceiling.
6MEASUREMENT PROTOCOLSIDNS
- Four inches away from other objects horizontally
or vertically above the detector - Four feet from heat, fireplaces and furnaces, out
of direct sunlight - Measurement devices may be suspended in the
general breathing zone and, and if suspended,
shall be at least 20 inches to six feet above the
floor. Some devices can be suspended from the
ceiling.
7INITIAL MEASUREMENTS
- THE INITIAL MEASUREMENT SHALL BE A SHORT TERM
MEASUREMENT THAT MAY RANGE IN DURATION FROM 48
HOURS TO 90 DAYS, DEPENDING ON THE MEASUREMENT
DEVICE USED. - Short term measurements SHALL be made under
closed-building conditions beginning 12 hours
prior to the start of the test. - Definition Closed Building Conditions-Refer to
Illinois Adopted Rule 32, Illinois Administrative
Code, Part 422, Section 422.130b) A B
8Bedroom Nightstands or Tables Make Good Locations
9Weather Concerns forShort-Term Tests
- Tests lasting less than 96 hours shall not be
conducted during unusually severe storms or high
winds. - The National Weather Service defines a severe
storm as a storm that generates winds of 58 mph,
and or 3/4 inch diameter hail and that may
produce tornadoes -- not necessarily in that
order.
10Measurement Protocols Interpretation Depend On
Purpose
- Home Environment Testing (IDNS)
- Real Testing Guidelines for Real Estate
transaction (Rev. 4 (3667) - Post-mitigation measurements (IDNS)
- Diagnostic measurements (IDNS)
- Schools and large buildings
- Device protocols dictate SOPs
11- Home Environment Test refers to a homeowner
initiated test that is not involved in a Real
Estate Transaction
12IDNS ADOPTED RULE
- Short Term or long-term measurement shall be made
in EACH lowest structural area suitable for
occupancy.(Example split-level building with
basement, slab-on-grade room and a room over a
crawl space shall have measurements made in all
of the above. - Not a closet, bathroom, kitchen, furnace room,
storeroom, garage, crawl space, attic. - Bedrooms, family rooms, living rooms, dining
rooms are ideal, provided they are on the lowest
lived-in level.
13What room is tested?
- Bedrooms, family rooms, living rooms, dining
rooms are ideal, provided they are on the lowest
lived-in level.
14Follow-Up Measurements
- In same location as the initial test.
- Closed house conditions if follow-up test is
short-term (i.e..., if initial result is gt 10
pCi/L). - Normal lived-in conditions if follow-up test is a
long-term test (i.e..., if initial test was
between 4 and 10 pCi/L).
15Interpretation of Results
16HOME ENVIRONMENT FACTS
- If the initial measurement result is less than
4.0 pCi/L, follow-up measurements are probably
not needed. - Homeowner should test again sometime in the
future if - living patterns change and a lower level becomes
occupied, lower level should be tested. - if renovations are made in or near the building
17Interpretation of Results HOME ENVIRONMENT
- If long-term follow-up result is between 4 pCi/L
and 9.9 pCi/l follow up with a long-term test. - If short-term test if 10pCi/l or greater, follow
up with another short term test. If second result
is confirmatory, IDNS recommends mitigation. - Homes tested using this protocol should never be
mitigated on the basis of a single short-term
test. - As a Mitigator it is your responsibility to
inform homeowner that a confirmation test should
be conducted if only a single measurement has
been made.
18Real Estate Testing - Option 1Sequential Testing
19Interpreting Results of Sequential Method for
Real Estate
- Initial and secondary test placed in same
location. - No requirement that the results of each of the 2
measurements be the same. - In fact, some difference is expected because of
normal variation of radon (diurnal, barometric
pressure, rain, etc.). - Report each result and average of the two for
each individual level tested. Basement 4.1 and
4.3 4.2, Room above crawl 2.4 and 2.6 report as
2.3
20Real Estate Testing - Option 22 Simultaneous
Tests
21Simultaneous Test
- Two tests, 48 hours or longer, performed at the
same time. - Two Detectors, four inches apart, in each level
of the home in contact with the soil.
22Evaluating Simultaneous Tests
- Calculating the Relative Percent Difference
provides a measure of confidence - Average Result 1 Result 2
- 2
- RPD (Result 1 - Result 2) x 100
- Average of both results
- Should be within expected limits for type of
device used.
23Interpreting Simultaneous Real Estate Tests 1
Above and 1 Below
- If one test result is above 4.0 pCi/L and the
other is below 4.0 pCi/L, and higher one is less
than twice the lower one, use results. - Report individual readings and average.
- Examples
- Results of 3 pCi/L and 5 pCi/L are OK
- Results of 3 pCi/L and 7 pCi/L are not OK
- Report that test results are outside the
acceptable range and recommend retest.
24Interpreting Simultaneous Real Estate Test Both
Are Above 4.0
- If both tests are above 4.0 pCi/L, a 36 relative
percent difference is expected. Results used
regardless of agreement. - Report results and their average.
- Examples
- Results of 7 pCi/L and 8 pCi/L are OK
- Results of 17 pCi/L and 36 pCi/L are a concern
- Report test results are outside the acceptable
range, recommend retest.
25Interpreting Simultaneous Real Estate Tests Both
Below 4.0
- If both tests are below 4.0 pCi/L, 67 relative
percent difference (RPD) or better is expected.
Results are used regardless of RPD. - Report results and their average.
- Examples
- Results of 2 pCi/L and 3 pCi/L are OK
- Results of 1 pCi/L and 3.5 pCi/L are a concern.
- Report test results are outside acceptable range,
recommend retest.
26Real Estate Testing - Option 3A Single
Continuous Monitor
27Requirements for Use of Single Continuous Monitor
for Real Estate
- Single CR, or CW must integrate and record hourly
or more frequently. - Monitors that do not record at least hourly must
be used with another passive or active device
using either the sequential or simultaneous
method. - First four hours of test may be disregarded, but
44 contiguous hours required for average.
28Monitor for Real Estate
- Single CR, or CW must integrate and record
hourly or more - frequently.
- Monitors that do not record at least hourly must
be used with - another passive or active device using either
the sequential of - simultaneous method.
- First four hours of test may be disregarded, but
44 contiguous - hours required for average.
29Ways to Prevent or Detect Tampering
- A print-out of continuous monitor helps detect
unusual measurement swings. - Motion detectors can determine if device is
moved. - Record barometric and weather conditions.
- Record room temperatures to assess the opening of
windows. - Specialty tapes on exterior doors and windows can
be used to detect their being opened. - Place device in a particular position that
handling would be difficult or detectable. - Dont use devices that provide a read-out to
occupant. - Homeowner agreement with cost consequences.
30Ethics
- In most states radon measurements represent
confidential information between tester and
client. - Incorrect protocols Shall be brought to
attention of ILLINOIS DEPARTMENT OF NUCLEAR
SAFETY by filing a non-conformance report. - Homeowners and clients are not bound to perform
follow-up measurements, etc. but tester is to
advise and recommend to client.
31Typical Sellers Property Disclosure Form
32Post-Mitigation MeasurementsAssess Success of
Mitigation
- Perform between 24 hours and 30 days after
mitigation. Follow same protocols as original
test. - Perform in same location as pre-mitigation tests.
- A minimum short-term test is to be conducted with
an IDNS licensed LAB . - Long-term testing, and re-testing once every 2
years to be recommended.
33Diagnostic Measurements Aid the Design of a
Mitigation System
- Can be continuous monitors to determine unusual
entry patterns. - Can be sniffing measurements taken at suspected
entry points. - Are interpreted as relative indicators.
- No protocols for interpretation other than those
associated with the device itself.
34School Testing Protocols - Defacto Protocols for
Adopted Rule Part 422.130 f. 7) Large
BuildingsAdopted Rule Part 422.130.f.7
- Caution The following information is not a
complete guide to perform School of Large
Building testing. IDNS has additional resources
available. - Slab on grade Design. Measure all
frequently-occupied rooms in contact with the
ground. - Open-plan or Pod design. If sections of a pod
have moveable walls that can physically separate
them from other sections, measure each section
separately. If moveable walls are absent or
inoperable, measure the pod as one room placing
detectors every 2000 square feet. Or as directed
by device manufacturer.
35School Testing Protocols - Defacto Protocols for
Large Buildings
- Crawlspace Design. Measure all rooms directly
above an enclosed crawlspace. - Basement Design. In addition to measuring all
frequently-occupied basement rooms, measure all
rooms above the basement that have at least one
wall with substantial contact with the ground. - Do test offices, classrooms, gyms, cafeterias,
etc. - Follow all other protocols for specific
placement of device.