Title: SEVERN TRENT SERVICES
1Wet Pipe Sprinkler System Expansion Chamber Sal
es Presentation October 2004
2FIRE-X-TROLFeatures Benefits
- Absorbs expanded antifreeze solution
- Diaphragm expansion chamber (4X cycles of a
bladder style tank)
- Protects system and components from thermal
expansion
- UL listed
- for use with fire protection antifreeze systems
per NFPA 13
- ASME
- Designed, constructed, and tested per ASME
Section VIII, Division 1 Standards
- Available code and non-code
3FIRE-X-TROLFeatures Benefits
- Pre-charge is separated from system fluid
- 5X safety factor by design
- Protects system and components from thermal
expansion
- Helps prevent system hydraulic lock-up
- Required when backflow prevention device is used
(most local regulations)
- Seismic restraints available (vertical models)
- Antifreeze compatible
- (Glycerine and Propylene Glycol)
- Broad range of sizes
- 4 to 90 gallons (15 341 ltr.)
4FIRE-X-TROL How does the Fire-X-Trol work?
- It is installed between the backflow preventer
and fill cup
- Its sealed-in dry air/nitrogen pre-charge
chamber prevents antifreeze solution from
entering it until the system pressure exceeds the
pre-charge pressure. - As the antifreeze solution temperature rises,
expanded system fluid enters the Fire-X-Trol
non-corrosive reservoir.
- The Fire-X-Trol absorbs the pressure increase,
keeping system pressure below maximum system
rating.
- As the fluid temperature decreases, pressure in
the dry air /nitrogen chamber forces system fluid
out of the expansion chamber and back into the
system.
5FIRE-X-TROL
- Materials of Construction
- All steel body construction with stainless steel
system connection
- Polypropylene Liner Material
- Diaphragm Material UL certified high-performance
elastomeric compound
- Coating FPT Red
- Maximum Operating Conditions
- Maximum Working Pressure 175 psig (12 bar)
- Operating Temperature -20 F (-29 C) to 200 F (93
C)
- Factory pre-charge 25 psig (1.7 bar)
6FIRE-X-TROL Models
7FIRE-X-TROL Installation Schematic
In-Line Models
Stand Models
8FIRE-X-TROL Installation Schematic
Isolate expansion chamber during system hydro
test. Install in supply line between backflow p
reventer and fill cup connection.
9FIRE-X-TROL Installation Schematic
Isolate expansion chamber during system hydro
test. Install in supply line between backflow p
reventer and fill cup connection.
10Fire-X-Trol used with Backflow Preventer
- NFPA 13 requirement
- As stated in NFPA 13, 7.5.3.3
- Where the connection between the antifreeze
solution and the wet pipe incorporates a backflow
prevention device, a listed expansion chamber of
appropriate size and pre-charged air pressure
shall be provided to compensate for thermal
expansion of the antifreeze solution
11FIRE-X-TROL Installation
- Visually inspect FIRE-X-TROL for any damage.
- Hydraulic system pressure must be at zero.
- Attach nitrogen or dry air supply to expansion
chamber charging valve
- Dry air -50 F / -46 C dew point or lower
- Pre-charge to 2 psig (0.14 bar) below system
static pressure at tank location.
- Never pre-charge below 25 of the system maximum
rated pressure.
- Remove charging hose. Carefully test charging
valve for leakage.
- Replace plastic cap.
12Antifreeze Solution Table
13Sizing Chart
Note1 AMTROL recommends installing a pressure
reducing valve before the backflow preventer.
Note 2 The system pressure is too close to the
maximum working pressure. NFPA 13 recommends
installing a pressure reducing valve before the
backflow preventer.
14Sizing Chart
Note1 AMTROL recommends installing a pressure
reducing valve before the backflow preventer.
Note 2 The system pressure is too close to the
maximum working pressure. NFPA 13 recommends
installing a pressure reducing valve before the
backflow preventer.
15FIRE-X-TROL Warranty and Lead-time
- Warranty
- Limited (1) year warranty
- Lead-time
- 10 working days
- Safety stock inventory for quicker delivery if
required
16FIRE-X-TROL FAQs
- Q What division does Fire suppression systems
fall under?
- A Division 13.
- Q What does NFPA stand for?
- A National Fire Protection Agency
- Q What fluids can be used with the Fire-X-Trol
expansion chamber?
- A Glycerine-water and propylene glycol-water
mixtures.
- Q What is a Wet Pipe Antifreeze system?
- A Antifreeze systems are typically used as
subsystems of a wet pipe system and are intended
to protect small areas that could be exposed to
freezing temperatures.
17FIRE-X-TROL FAQs
- Q What happened to the recommended 40-gallon
(151 liter) limit for antifreeze systems?
- A This recommendation has been deleted in the
NFPA 13 2002 edition. There is no limit to the
size of an antifreeze system.
- Q Is a reduced-pressure zone backflow
prevention device required in an antifreeze
system?
- A Many local regulations require that a
backflow prevention device be used in the system
to guard against any potential contamination of
the public water supply. - Q Is an expansion chamber required when a
backflow prevention device is used?
- A Yes. Section 7.5.3.3 of NFPA 13 requires the
use of an expansion chamber.
18FIRE-X-TROL FAQs
- Q Does antifreeze-water solution expand and
contract?
- A Yes. The solution will expand and contract
with changes in temperature. The amount of
expansion and contraction depends upon total
temperature change and the density of the
specific solution used. - Q Is the Fire-X-Trol UL Listed?
- A Yes. The Fire-X-Trol is UL listed and was
subject to extensive UL testing for
compatibility with antifreeze solutions and to
assure that the quality of the - Fire-X-Trol meets fire protection standards.
- Q What are the advantages of an AMTROL
diaphragm tank?
- A In extensive cyclic testing and with the
performance proven AMTROL diaphragm technology,
a diaphragm can typically accommodate 4X the
cycles of a bladder style tank.