Title: November 2004
1Top Ten Approaches to Lowering Fan Energy in
Cleanrooms
2First the Basics
- Fan Power CFM x Pressure Drop (in inches)
6345 x Fan Eff x Motor Eff
3Ten Use Best-in-class Motors
Use Motor Master Software
4Nine Use Efficient Fans
5Eight Use Variable Speed Drives
- Thank you cube law!
- Often fan systems are turned down after startup.
This is done most efficiently and most simply
with VSDs.
6Seven Select a Low Pressure Drop System
- Recirculation Air Handling Systems in Cleanrooms
- Pressurized Plenum
- Ducted Hepa
- Fan Filter Units
7Six Use Low Face Velocity Air Handlers
8Five Use Demand Controlled FiltrationTimeclock,
occupancy sensor or particle counter
40 setback 70 energy savings
9Four Select Most Efficient FFUs
FFU Performance is a function of - Airflow
(CFM) NOT Velocity - Filter Efficiency -
External Static
10Three Exhaust Optimization
- Turn off canopy and snorkel when not in use
- Lower Exhaust Air Change Rates when unoccupied
- Minimum Air Change Rates 12 ACH, 10 ACH, 8
ACH, 6 ACH??
Wet Bench - 574 to 254 scfm
Vertical Furnace - 628 to 474 scfm
Courtesy of Northwest Energy Efficiency Alliance
Website (www.nwalliance.org)
11Two- Use Mini Environments
- Can be coupled with reduction in overall
cleanliness rating - Wafertech
12One - Select Appropriate Air Change Rate
13Results when implemented as a system
14Successes Air System Optimization
15Air System Optimization 75 Savings
16To Summarize.
- 10 Use best in class motors
- 9 Use efficient fans
- 8 Use VSDs
- 7 Select a low pressure drop system
- 6 Use low face velocity air handlers
- 5 Use demand controlled ventilation Timeclock
or particle sensor - 4 Select most efficient FFUs
- 3 Exhaust Optimization
- 2 - Use Mini Environments
- 1 Select appropriate air change rate